Page 1
E6581440 TOSVERT VF-PS1 series ® BACnet Option unit Function Manual BCN001Z NOTICE 1. Make sure that this instruction manual is delivered to the end user of BACnet ® Option unit. 2. Read this manual before installing or operating the BACnet ® Option unit. Keep it in a safe place for reference.
Page 2
E6581440 Introduction Thank you for purchasing the BACnet ® Option unit (BCN001Z) for VF-PS1 series inverter. Before using BACnet ® Option unit, carefully read this function manual in order to completely and correctly utilize its excellent performance. After reading this function manual, please keep it handy for future reference. For details of its general handling, see an instruction manual attached with the option unit.
E6581440 1. Overview The BACnet ® option unit(BCN001Z) allows the VF-PS1 inverter to be connected into a BACnet ® network. BCN001Z is applicable for VF-PS1 software version V620 or later. 2. Names and functions The drawing below shows names and functions of main parts. 2.1.
E6581440 2.3. LED indicator The LED shows the present status of the network and error. ■Layout of LED (Green) (Red) State LEDs Comment COM LED: OFF BCN001Z board failure. ERR LED: Flashing 5 times in 1 second COM LED: OFF Communication loss was detected.
E6581440 2.4. MAC address setting The DIP switch on the circuit board of the option is used to set a MS/TP MAC address. Each DIP switch is ON when it is flipped to the lower position. The MAC address must be unique and not match any other device on a network segment.
Page 7
E6581440 OFF ON OFF OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF ON OFF ON ON OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF ON OFF OFF ON ON OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON ON OFF ON ON OFF OFF OFF ON ON...
E6581440 3. VF-PS1 Parameters 3.1. Communication parameters Set up the inverter parameters as follows. To update, reset of inverter. If these parameters are not set to correct value, this unit can not work normally. Factory Title Function Description setting 0: AUTO adaptive,1: 9600bps,2: 19200bps, Network Baudrate (*1) (*2) 0000 f831...
E6581440 3.2. Network Baudrate (f831) Set the network baudrate to f831. Set the same baudrate in the network. If set AUTO baudrate, the option unit detects network baudrate automatically. 3.3. Network error detection (f832,f851,f852) Set the network communication loss action time to f832. The network loss detection starts from the first receiving of the proper frame message.
E6581440 4. Functions This option board is based on BACnet ® “Application Specific Controller” (B-ASC). 4.1. Object / Property support Matrix This option board supports below table objects and properties. Object Type Property Binary Binary Binary Analog Analog Analog Device Input Output Value...
E6581440 4.2. Drive I/O Objects 4.2.1. Binary Input Object Instance Binary input objects allow to monitor the inverter actual terminal ON/OFF status. These objects are read only. If it is necessary to read inverter terminal output status via BACnet® network, Binary input object can be used to. Binary input #0 is FL labeled terminal monitor.
E6581440 4.2.2. Binary Output Object Instance Binary output objects allow to control output terminals via BACnet ® network. Set the terminal function parameter(see below table) before control output terminals. These commandable objects can be used for priority-array and relinquish-default property. Active / Instance ID Object Name...
E6581440 4.2.3. Binary Value Objects Instance Binary value objects allow to monitor inverter status and send command such as RUN/STOP command. Commandable objects can be used for priority-array and relinquish-default property. Binary Active/ Object Name Description Access Value ID Inactive Text Indicates the drive run status RUN/STOP ACT RUNS/READY...
E6581440 4.2.4. Analog Input Object Instance The analog input objects allow to monitor inverter analog input terminal level. These objects only read inverter parameters those are prepared as read only monitor parameters(from fe35 to fe39). These objects present-value unit is “%” unit, and present-value=100.0% mean analog input terminals are a full range input level.
E6581440 4.2.6. Analog Value Object Instance The analog value objects allow to monitor drive status such as output frequency, current and voltage. Additionally, drive speed reference can be set as Analog Value #16. Binary Object Name Description UNIT Access Value ID OUTPUT SPEED Output speed[min ](Calculate from fd00)
Property Name Property Value Object Name “VF-PS1” Object Type 8 (device) Vendor Name “TOSHIBA” Vendor Identifier Model Name “VFPS1-2007P” (depend on the VSD model) Firmware Revision “V1.00” (depend on the option software version) Application Software Version “V6.20” (depend on the VSD software version)
E6581440 5. Mailbox Function Points Mail box object allow to read/write inverter parameters via BACnet ® network. Object ID Object Name Description Set parameter individual communication number. Communication address is normally consist of characters from 0 to 9, but Analog value MBOX PARAM Interpreted hexadecimal code internally.
E6581440 6. Specifications < Environmental specification > Item Specification B C N 0 0 1 Z M o d e l n u m b e r Service environment Conforms to VF-PS1 Conforms to VF-PS1 A m b i e n t t e m p e r a t u r e Storage temperature -25 to +65 ℃...