hit counter script

GE T60 Instruction Manual page 396

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

GROUPED ELEMENTS
5
For phase distance zone 2, there is a provision to start the zone timer with other distance zones or loop the pickup
flag to avoid prolonging phase distance zone 2 operation when the fault evolves from one type to another or
migrates from the initial zone to zone 2. Assign the required zones in the trip output function to accomplish this
functionality.
5-214
Figure 5-111: Phase distance zone 1 OP logic
Figure 5-112: Phase distance zone 2 OP logic
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents