CHAPTER 5: SETTINGS
When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None are
set to the last protocol saved (that is, IEEE C37.118 or IEC 61850-90-5) to any aggregators, as both IEEE C37.118 and
IEC 61850-90-5 simultaneous streaming is not possible.
PMU AGGREGATOR1 PROTOCOL
protocol is supported at a time in a device, this setting applies to all PMU aggregators.
— Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output stream, this
PMU AGGREGATOR1 IDCODE
identifies the ID of the aggregator, which is only used if there is more than 1 PMU mapped into an aggregator.
— If set to "Yes," aggregator 1 includes the PMU1 data set in the reporting data stream.
PMU AGGREGATOR1 PMU1
AGGREGATOR1 does not include PMU1 data set in the report if set to "No."
Only PMUs with same reporting rate can be assigned to the same PMU AGGREGATOR.
SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PMU AGGREGATOR 1 C37.118 AGGR 1
CONFIGURATION
C37.118 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1 TCP PORT
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 UDP PORT
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 PDC CONTROL
be executed on the PMU. The control is accomplished via an extended command frame. The relay decodes the first word
of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator supports 16 FlexLogic
operands, as shown in the table. The operands are asserted for five seconds following reception of the command frame. If
the new command frame arrives within the five-second period, the FlexLogic operands are updated, and the five-second
timer restarts. This setting enables or disables the control. When enabled, all 16 operands for each aggregator are active;
when disabled, all 16 operands for each aggregator remain reset.
Table 5-22: FlexLogic operands supported by aggregator
Operand type
ELEMENT:
Synchrophasor, phasor data,
concentrator
as above
as above
as above
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
C37.118 AGGR 1
CONFIGURATION
90-5 AGGR 1
CONFIGURATION
— Selects if the IEEE C37.118 or IEC 61850-90-5 technical report is used. Because one
PMU AGGREGATOR 1
TCP PORT: 4712
PMU AGGREGATOR 1:
UDP PORT: 4713
PMU AGGREGATOR 1:
PDC CONTROL: Disabled
— Selects the TCP port number to be used by this aggregator for network reporting. All ports,
— Selects the UDP port number to be used by this aggregator for network reporting. All ports,
— The synchrophasor standard allows for user-defined controls originating at the PDC, to
Operand syntax
AGTR1 PDC CNTRL 1
AGTR1 PDC CNTRL 2
AGTR1 PDC CNTRL 3
AGTR1 PDC CNTRL 16
See below
See below
Range: 0 to 65534
Range: 0 to 65534
Range: Disabled, Enabled
Operand description
Phasor data concentrator asserts control bit 1, as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network
Phasor data concentrator asserts control bit 16, as
received via the network
SYSTEM SETUP