1MRK 506 382-UEN A
20.2.2.3
20.2.3
20.2.3.1
20.2.3.2
Line distance protection REL650 2.2 IEC
Technical manual
Technical data
Table 629:
SFP - Optical ethernet port
Quantity
Number of channels
Standard
Type of fiber
Wave length
Optical connector
Communication speed
Table 630:
SFP - Galvanic RJ45
Quantity
Rated value
Number of
Up to 6 single or 3 redundant or a combination of single and redundant links for
channels
communication using any protocol
Standard
IEEE 802.3u 100BASE-TX
Type of cable
Cat5e FTP
Connector
Type RJ45
Communication
Fast Ethernet 100 Mbit/s
Speed
Table 631:
NUM: Communication ports
NUM
Ethernet connection type
Power supply module (PSM)
Introduction
The power supply module is used to provide the correct internal voltages and full
isolation between the IED and the battery system. An internal fail alarm output is
available.
Alternative connectors of Ring lug or Compression type can be ordered.
Design
There are two types of the power supply module. They are designed for different
DC input voltage ranges see table 632. The power supply module contains a built-
IED hardware
Rated value
4 single or 2 redundant can be used for single or
redundant communication using any protocol
IEEE 802.3u 100BASE-FX
62.5/125 mm multimode fibre
1310 nm, Class 1 laser safety
Type LC
Fast Ethernet 100 Mbit/s
GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v2
4 Ethernet ports
1 Basic, 3 Optional
SFP Optical LC or Galvanic RJ45
Section 20
SEMOD55319-1 v1
SEMOD55310-2 v11
IP15594-1 v1
M11595-3 v6
IP14278-1 v1
M6377-3 v2