Section 14
Monitoring
14.2
14.2.1
14.2.2
564
Table 400:
VMSQItechnical data
Function
Voltage positive sequence, U1
Voltage zero sequence, 3U0
Voltage negative sequence, U2
Phase angle
Table 401:
VNMMXU technical data
Function
Voltage
Phase angle
Gas medium supervision SSIMG
Identification
Function description
Insulation gas monitoring function
Functionality
Insulation supervision for gas medium (SSIMG) is used for monitoring the circuit
breaker condition. Binary information based on the gas pressure in the circuit
breaker is used as input signals to the function. In addition, the function generates
alarms based on received information.
Range or value
(10 to 300) V
(10 to 300) V
(10 to 300) V
(10 to 300) V
Range or value
(5 to 175) V
(5 to 175) V
IEC 61850
IEC 60617
identification
identification
SSIMG
-
Line distance protection REL650 2.2 IEC
1MRK 506 382-UEN A
GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6
Accuracy
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
ANSI/IEEE C37.2
device number
63
GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6
Technical manual