Section 19
Basic IED functions
Table 591:
TIMESYNCHGEN Non group settings (basic)
Name
CoarseSyncSrc
FineSyncSource
SyncMaster
TimeAdjustRate
HWSyncSrc
SyncLostMode
SyncAccLevel
CurrentSyncSource
PTPGMId
PTPGMClass
PTPGMPriority1
PTPGMPriority2
PTPGMAccuracy
PTPParentId
PTPSteps
SNTPSource
SNTPMaster
GPSNumberOfSats
PTPOwnId
796
Values (Range)
Unit
Off
-
SPA
LON
DNP
IEC103
Off
-
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
Off
-
SNTP-Server
Slow
-
Fast
Off
-
GPS
IRIG-B
PPS
NoBlock
-
Block
BlockOnLostUTC
Class T5 (1us)
-
Class T4 (4us)
Unspecified
0 - 16
-
0 - 16
-
0 - 16
-
0 - 16
-
0 - 16
-
0 - 16
-
0 - 16
-
0 - 16
-
0 - 16
-
0 - 16
-
-1 - 12
-
0 - 16
-
Step
Default
-
Off
-
Off
-
Off
-
Fast
-
Off
-
NoBlock
-
Unspecified
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
0
1
-
1MRK 506 382-UEN A
Description
Coarse time synchronization source
Fine time synchronization source
Activate IEDas synchronization master
Adjust rate for time synchronization
Hardware time synchronization source
Behavior of dependent protection
functions when time synchronization
quality is inadequate
Wanted time synchronization accuracy
Current synchronization source
PTP Grand Master Id
PTP Grand Master Class
PTP Grand Master Prio 1
PTP Grand Master Prio 2
PTP Grand Master Accuracy
PTP Id of closest parent
PTP number of stepsto Grand master
The source of the SNTP time
The IP-adress of the SNTP master
GPS satellites used in calculation of time
PTP own clock identity
Line distance protection REL650 2.2 IEC
Technical manual
PID-6638-SETTINGS v3