Function Block - ABB Relion 670 Series RES670 Technical Manual

Phasor measurement unit 2.1 ansi
Table of Contents

Advertisement

1MRK 511 365-UUS A
18.4.6.1
18.4.6.2
Table 473:
MVGAPC Non group settings (basic)
Name
Values (Range)
BasePrefix
micro
milli
unit
kilo
Mega
Giga
Tera
MV db
1 - 300
MV zeroDb
0 - 100000
MV hhLim
-5000.00 - 5000.00
MV hLim
-5000.00 - 5000.00
MV lLim
-5000.00 - 5000.00
MV llLim
-5000.00 - 5000.00
MV min
-5000.00 - 5000.00
MV max
-5000.00 - 5000.00
MV dbType
Cyclic
Dead band
Int deadband
MV limHys
0.000 - 100.000
Phasor measurement unit RES670 2.1 ANSI
Technical manual

Function block

MVGAPC
BLOCK
^VALUE
^IN
RANGE
IEC14000022-1-en.vsd
IEC14000022 V1 EN
Figure 236:
MVGAPC function block
Settings
Unit
Step
-
-
Type
1
m%
1
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
-
-
%
0.001
Station communication
Default
Description
unit
Base prefix (multiplication factor)
10
Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
500
Zero point clamping in 0.001% of range
900.00
High High limit multiplied with the base prefix
(multiplication factor)
800.00
High limit multiplied with the base prefix
(multiplication factor)
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
-900.00
Low Low limit multiplied with the base prefix
(multiplication factor)
-1000.00
Minimum value multiplied with the base prefix
(multiplication factor)
1000.00
Maximum value multiplied with the base prefix
(multiplication factor)
Dead band
Reporting type
5.000
Hysteresis value in % of range (common for all
limits)
Section 18
605