1MRK 511 365-UUS A
Name
Values (Range)
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Pickup1
5 - 2500
t1
0.000 - 60.000
TD1
0.05 - 999.00
IMin1
1 - 10000
t1Min
0.000 - 60.000
MultPU1
1.0 - 10.0
DirModeSel2
Disabled
Non-directional
Forward
Reverse
Characterist2
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Table continues on next page
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Unit
Step
Default
-
-
ANSI Def. Time
%IB
1
1000
s
0.001
0.000
-
0.01
0.05
%IB
1
100
s
0.001
0.000
-
0.1
2.0
-
-
Non-directional
-
-
ANSI Def. Time
Current protection
Description
Selection of time delay curve type for step 1
Operating phase current level for step 1 in % of
IBase
Def time delay or add time delay for inverse
char of step 1
Time dial multiplier for the inverse time delay
for step 1
Minimum operate current for step1 in % of
IBase
Minimum operate time for inverse curves for
step 1
Multiplier for current operate level for step 1
Directional mode of step 2 (Disabled, Nondir,
Forward, Reverse)
Selection of time delay curve type for step 2
Section 8
173