Dead Line Detection - ABB Relion 670 Series RES670 Technical Manual

Phasor measurement unit 2.1 ansi
Table of Contents

Advertisement

1MRK 511 365-UUS A
13.2.7.3
Phasor measurement unit RES670 2.1 ANSI
Technical manual
DeltaIA
0
20 ms
DeltaIB
0
20 ms
DeltaIC
0
20 ms
DeltaVA
0
20 ms
DeltaVB
0
20 ms
DeltaVC
0
20 ms
ANSI12000165 V2 EN
Figure 129:
Internal signals DeltaV or DeltaI and the corresponding output signals

Dead line detection

A simplified diagram for the functionality is found in figure 130. A dead phase condition
is indicated if both the voltage and the current in one phase is below their respective setting
values VDLDPU and IDLDPU. If at least one phase is considered to be dead the output
DLD1PH and the internal signal DeadLineDet1Ph is activated. If all three phases are
considered to be dead the output DLD3PH is activated