10.1 SETTING EXAMPLE
10 APPLICATION OF SETTINGS

10.1.14 FREQUENCY

The pickup and delay settings are dependent on operating practices and system characteristics. In this example, two over-
frequency and two underfrequency elements will be used. The elements will be blocked when offline. Underfrequency will
initiate a trip. Overfrequency will alarm only. Either source may be assigned.
Make the following changes in EnerVista UR Setup or through the


SETTINGS
CONTROL ELEMENTS
UNDERFRE-
and the


QUENCY
UNDERFREQUENCY 1(2)
SETTINGS
CONTROL ELEMENTS
OVERFREQUENCY
OVERFREQUENCY
menus:
1(2)
10.1.15 ACCIDENTAL ENERGIZATION
In this example, the
is selected as "UV and Offline". The
setting
ACCDNT ENRG ARMING MODE
ACCDNT ENRG OC PICKUP
should be set at ½ the minimum expected fault current. In this case, 1.0 pu (8000 A primary) is selected. In cases where it
is possible to re-energize the machine through its auxiliary transformer, a lower setting may be required. The undervoltage
pickup setting must be set above the maximum expected fault voltage.
Make the following changes in EnerVista UR Setup or through the


SETTINGS
GROUPED ELEMENTS
SETTING GROUP

menu:
1
ACCIDENTAL ENERGIZATION
10
10-12
G60 Generator Protection System
GE Multilin