5 SETTINGS
An example user display setup and result is shown below:
USER DISPLAY 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
USER DISPLAYS
If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the
bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items
NOTE
are different.
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
DIRECT I/O
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
DISP 1 TOP LINE:
Current X
~
DISP 1 BOTTOM LINE:
Current Y
~
DISP 1 ITEM 1:
6016
DISP 1 ITEM 2:
6357
DISP 1 ITEM 3:
0
DISP 1 ITEM 4:
0
DISP 1 ITEM 5:
0
Current X
0.850
Current Y
0.327 A
DIRECT I/O
DIRECT OUTPUT
DEVICE ID: 1
DIRECT I/O CH1 RING
CONFIGURATION: Yes
DIRECT I/O CH2 RING
CONFIGURATION: Yes
DIRECT I/O DATA
RATE: 64 kbps
DIRECT I/O CHANNEL
CROSSOVER: Disabled
CRC ALARM CH1
CRC ALARM CH2
UNRETURNED
MESSAGES ALARM CH1
UNRETURNED
MESSAGES ALARM CH2
G60 Generator Protection System
Shows user-defined text with first tilde marker.
A
Shows user-defined text with second tilde marker.
A
Shows decimal form of user-selected Modbus register
address, corresponding to first tilde marker.
Shows decimal form of user-selected Modbus register
address, corresponding to second tilde marker.
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
This item is not being used. There is no corresponding
tilde marker in top or bottom lines.
Shows the resultant display content.
5.2.16 DIRECT INPUTS/OUTPUTS
Range: 1 to 16
Range: Yes, No
Range: Yes, No
Range: 64 kbps, 128 kbps
Range: Disabled, Enabled
See page 5–65.
See page 5–65.
See page 5–66.
See page 5–66.
5.2 PRODUCT SETUP
5
5-59