5 SETTINGS
l) PMU RECORDING
PATH: SETTINGS
PRODUCT SETUP
RECORDING PMU1(4)
PMU 1
RECORDING
MESSAGE
MESSAGE
MESSAGE
•
PMU 1 FUNCTION: This setting enables or disables the recorder for PMU 1(4). The rate is fixed at the reporting rate
set within the aggregator (i.e., Aggregator 1(2)).
•
PMU 1 NO OF TIMED RECORDS: This setting specifies the number of timed records that are available for a given log-
ical PMU 1(4). The length of each record is equal to the available memory divided by the content size and number of
records. As the number of records is increased the available storage for each record is reduced. The relay supports a
maximum of 128 records in either timed or forced mode.
•
PMU 1 TRIGGER MODE: This setting specifies what happens when the recorder uses its entire available memory
storage. Under the "Automatic Overwrite", the last record is erased to facilitate new recording, when triggered. Under
the "Protected" selection, the recorder stops creating new records when the entire memory is used up by the old un-
cleared records.
•
PMU 1 TIMED TRIGGER POSITION: This setting specifies the amount of pre-trigger data as a percent of the entire
record. This setting applies only to the timed mode of recording.
m) NETWORK CONNECTION
PATH: SETTINGS
SYSTEM SETUP
REPORTING OVER
NETWORK
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The Ethernet connection works simultaneously with other communication means working over the Ethernet and is config-
ured as follows. Up to three clients can be simultaneously supported.
GE Multilin
SYSTEM SETUP
PHASOR MEASUREMENT
PMU 1 FUNCTION
DISABLE
PMU 1 NO OF TIMED
RECORDS: 10
PMU 1 TRIGGER MODE:
AUTOMATIC OVERWRITE
PMU 1 TIMED TRIGGER
POSITION: 10%
PHASOR...
PHASOR MEASUREMENT UNIT 1(4)
NETWORK REPORTING
FUNCTION: Disabled
NETWORK REPORTING
IDCODE: 1
NETWORK REPORTING
RATE: 10 per sec
NETWORK REPORTING
STYLE: Polar
NETWORK REPORTING
FORMAT: Integer
NETWORK PDC CONTROL:
Disabled
NETWORK TCP PORT:
4712
NETWORK UDP PORT 1:
4713
NETWORK UDP PORT 2:
4714
G60 Generator Protection System
5.4 SYSTEM SETUP
PHASOR MEASUREMENT UNIT1(4)
Range: Enable, Disable
Range: 2 to 128 in steps of 1
Range: Automatic Overwrite, Protected
Range: 1 to 50% in steps of 1
REPORTING OVER NETWORK
Range: Enabled, Disabled
Range: 1 to 65534 in steps of 1
Range: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times per
second
Range: Polar, Rectangular
Range: Integer, Floating
Range: Enabled, Disabled
Range: 1 to 65535 in steps of 1
Range: 1 to 65535 in steps of 1
Range: 1 to 65535 in steps of 1
5
5-105