hit counter script
Toshiba TOSVERT VF-AS1 Instruction Manual
Toshiba TOSVERT VF-AS1 Instruction Manual

Toshiba TOSVERT VF-AS1 Instruction Manual

The new high-performance inverter tosvert
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

Instruction Manual

T he new
high - performance inverter
TOSVERT
200V class
400V class 0.75 500kW
1.Make sure that this instruction manual is delivered to the end user of
the inverter unit.
2.Read this manual before installing or operating the inverter unit, and
store it in a safe place for reference.
AS1
VF-
TM
0.4 75kW
NOTICE
E6581301
S afety
I
precautions
II II
I ntroduction
C ontents
1
R ead first
C onnection
2
equipment
3
O perations
S earching and
4
setting parameters
B asic
5
parameters
E xtended
6
parameters
O peration with
7
external signal
M onitoring the
8
operation status
T aking measures
9
to satisfy the
CE/UL/CSA standards
S election of
10 10
peripheral
devices
T able of
11 11
parameters
12 12
S pecifications
B efore making a
13 13
service call
I nspection and
14 14
maintenance
15 15
W arranty
D isposal of
16 16
the inverter

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba TOSVERT VF-AS1

  • Page 1: Instruction Manual

    E6581301 S afety precautions II II I ntroduction C ontents R ead first C onnection Instruction Manual equipment O perations T he new S earching and setting parameters high - performance inverter B asic parameters TOSVERT E xtended parameters O peration with external signal M onitoring the operation status...
  • Page 3: Safety Precautions

    E6581301 I. Safety precautions The items described in these instructions and on the inverter itself are very important so that you can use the inverter safely prevent injury to yourself and other people around you as well as prevent damage to property in the area. Thoroughly familiarize yourself with the symbols and indications shown below and then continue to read the manual.
  • Page 4: General Operation

    E6581301 General Operation • @ • @ Danger Reference • E Never disassemble, modify or repair. This can result in electric shock, fire and injury. For repairs, call your sales agency. Disassembly prohibited • E Never remove the front cover when power is on or open door if enclosed in a cabinet. The unit contains many high voltage parts and contact with them will result in electric shock.
  • Page 5: Transportation & Installation

    Operation cannot be stopped immediately by the inverter alone, thus risking an accident or injury. • E All options used must be those specified by Toshiba. 1.4.4 The use of any other option may result in an accident.
  • Page 6 E6581301 Wiring • @ • @ Danger Reference • E Do not connect input power to the output (motor side) terminals (U/T1,V/T2,W/T3). That will destroy the inverter and may result in fire. • E Do not connect resistors to the DC terminals (between PA/+ and PC/-, or between PO and 5.19 PC/-).
  • Page 7 E6581301 Operations • @ • @ Danger Reference • E Do not touch inverter terminals when electrical power is applied to the inverter even if the motor is stopped. Touching the inverter terminals while power is connected to it may result in electric shock. •...
  • Page 8: Maintenance And Inspection

    E6581301 Maintenance and inspection • @ • @ Danger Reference 14.2 • E Never replace any part by yourself. This could be a cause of electric shock, fire and bodily injury. To replace parts, call the local sales agency. Prohibited •...
  • Page 9 E6581301 II. Introduction Thank you for your purchase of the Toshiba “TOSVERT VF-AS1” industrial inverter. The VFAS1-4355KPC, VFAS1-4400KPC and VFAS1-4500KPC are soon to be released. Please note that these models are not referred to in some sections of this manual. (Shaded area (• @ • @ • @...
  • Page 11 Simplified operation of the VF-AS1 ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥...
  • Page 12 E6581301 5.17 PWM carrier frequency ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥...
  • Page 13: Setting Acceleration/Deceleration Patterns And Switching Acceleration/Deceleration

    E6581301 6.23 Increasing the motor output torque further in low speed range ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ F-39 6.24 Torque control ¥...
  • Page 14 E6581301 6.38.1 2-wire RS485/4-wire RS485 ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ F-75 6.38.2 Open network option ¥...
  • Page 15 E6581301 Inspection and maintenance ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥...
  • Page 17: Read First

    L: Built-in EMC filter 004:0.4kW 450:45kW P:Provided TOSVERT 2:200V~240V F:External heat sink • @ • @ • @ 007:0.75kW 550:55kW VF-AS1 series 4:380V~480V Y:Others basic filter Special: 015:1.5kW 750:75kW (non-standard) VFZ1: For explosion- M: Built-in basic filter specification code 022:2.2kW...
  • Page 18: Names And Functions

    E6581301 1. 3 Structure of the main body 1.3.1 Names and functions 1) Outside view Control circuit Operation panel terminal board cover Be sure to close the cover before starting the operation to prevent persons from touching the terminal board in error.
  • Page 19 E6581301 Operation panel Up key RUN lamp EASY key [Note 1] EASY key lamp % lamp Lights when an ON Lights when the unit Press this key to control Lights when the EASY command is issued but no is %. the function assigned key is enabled.
  • Page 20 E6581301 2) Main circuit terminal board VFAS1-2004PL~2015PL VFAS1-4007PL~4022PL Shorting-bar M4 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2022PL• C 2037PL VFAS1-4037 PL Shorting-bar M4 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2055PL VFAS1-4055PL•...
  • Page 21 E6581301 VFAS1-2075PL VFAS1-4110PL Shorting-bar M5 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2110PM, 2150PM VFAS1-4150PL, 4185PL Grounding capacitor switching switch Shorting-bar M6 screw Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2185PM, 2220PM VFAS1-4220PL M8 screw Shorting-bar...
  • Page 22 E6581301 VFAS1-4300PL• C 4370PL Grounding capacitor switching switch M8 screw Shorting-bar Each main circuit terminal has the structure shown in the figure below. Connect a cable to part A if it has a ring terminal, or to part B if it has no terminal (bare wire).
  • Page 23 E6581301 VFAS1-2750P VFAS1-4110KPC M12 screw M10 screw Grounding capacitor switching bar M4 screw M8 screw Grounding terminal(M10 screw) VFAS1-4132KPC Grounding capacitor M12 screw switching screw M10 screw M8 screw M4 screw Grounding terminal(M10 screw) VFAS1-4160KPC Grounding capacitor switching screw M12 screw M12 screw M10 screw M4 screw...
  • Page 24 E6581301 VFAS1-4200KPC~4280KPC M12screw Grounding capacitor switching screw M12screw M4screw Grounding terminal(M12) VFAS1-4355KPC, 4400KPC VFAS1-4500KPC...
  • Page 25: Detaching The Cover

    E6581301 3) Control circuit terminal board The control circuit terminal board is common to all equipment. Serial 4-wire RS485 ST-CC Shorting bar connector Control terminal board screw size: M3 ⇒ For details on all terminal functions, refer to Section 2.3.2. 1.3.2 Detaching the cover Main circuit terminal board cover To wire the main circuit terminal board for models 200V-15kW or smaller and 400V-18.5kW or smaller, remove the...
  • Page 26 E6581301 For 200V/0.4kW to 200V/7.5kW models and 400V/0.75kW to 400V/11kW models, cut off the tabs (part A in the figure below) on the main circuit terminal board if necessary for connecting the cables from the power supply. 200V-0.4kW~3.7/4.0kW 200V-5.5kW~7.5kW 400V-0.75kW~3.7/4.0kW 400V-5.5kW~11kW Front cover To wire the main circuit terminal board for models 200V-18.5kW or more and 400V-22kW or more, remove the front...
  • Page 27 E6581301 Charge lamp This lamp is lit when a high voltage remains in the inverter. When removing the main circuit terminal board cover or opening the front cover, be sure to check that this lamp is off and follow the instructions about wiring on page 4. The mounting position of the charge lamp varies from model to model.
  • Page 28: Grounding Capacitor Switching Method

    E6581301 1.3.3 Grounding capacitor switching method The inverter is grounded through a capacitor. The leakage current from the inverter can be reduced using the selector switch, switching bar or switching screw (depending on the model) on the main circuit terminal board. This switching device is used to detach the capacitor from the grounding circuit or to reduce its capacitance.
  • Page 29 E6581301 200V/55kW models and larger 400V/90kW, 110kW models: Grounding capacitor switching bar Large To change the capacitance from Small to Large, secure the upper end of the grounding capacitor switching bar to the inverter Small chassis, with a screw. To change the capacitance from Large Large to Small, remove the screw that fixes the upper end of the...
  • Page 30: Notes On The Application

    Comparisons with commercial power operation The VF-AS1 Inverter employs the sinusoidal PWM system to supply the motor. This is why compared to operation with a commercial power there will be a slight increase in motor temperature, noise and vibration. The main supply voltage and current will also be distorted due to harmonic distortion while increase the line current.
  • Page 31 E6581301 Braking a motor when power supply is lost A motor with its power cut off goes into freewheel, and does not stop immediately. To stop the motor quickly as soon as the power is cut off install an auxiliary brake. There are different kinds of brake devices, both electrical and mechanical.
  • Page 32 E6581301 1.4.2 Inverters Protecting inverters from overcurrent The inverter has an overcurrent protection function. The programmed current level is set to the inverter's maximum applicable motor. If the motor used has a small capacity, the stall prevention level, overcurrent level and the motor electronic thermal protection must be readjusted.
  • Page 33: What To Do About The Leak Current

    E6581301 1.4.3 What to do about the leak current • @ • @ Warning Current may leak through the inverter's input/output wires because of insufficient electrostatic capacity on the motor with bad effects on peripheral equipment. The leakage current's value is affected by the carrier frequency and the length of the input/output wires.
  • Page 34 E6581301 Remedies: Use the electronic thermal overload built into the inverter. The setting of the electronic thermal overload is done using parameter Reduce the inverter's PWM carrier frequency. However, that will increase the motor's acoustic noise. The setting of PWM carrier frequency is done with the parameter This can be improved by installing 0.1µ~0.5µF-1000V film capacitor to the input/output terminals of each phase in the thermal overload relay.
  • Page 35: Measuring Position

    E6581301 1.4.4 Installation Installation environment The VF-AS1 Inverter is an electronic control instrument. Take full consideration to installing it in the proper operating environment. • @ • @ Danger • E Do not place any inflammable substances near the VF-AS1 Inverter.
  • Page 36: How To Install

    Please consult with your supplier about these measures. • E If the VF-AS1 Inverter is installed near any of the equipment listed below, provide measures to insure against errors in operation. Solenoids: Attach surge suppressor on coil. Brakes: Attach surge suppressor on coil.
  • Page 37 E6581301 Install the inverter in a well-ventilated indoor place and mount it on a flat metal plate in portrait orientation. If you are installing more than one inverter, the separation between inverters should be at least 5cm, and they should be arranged in horizontal rows.
  • Page 38 E6581301 Ambient temperature: Permanently-installed inverters 200V 18.5~45kW (See lines shown in - - - for 22kW) 40°C: (a) 400V 22~75kW When the upper protection cover is removed under condition (a) 100% 50°C: (a) When the upper protection cover is removed under condition (a) 60°C: (a) When the upper protection cover is removed under...
  • Page 39: Calorific Values Of The Inverter And The Required Ventilation

    E6581301 Calorific values of the inverter and the required ventilation The energy loss when the inverter converts power from AC to DC and then back to AC is about 5%. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the interior of the cabinet must be ventilated and cooled.
  • Page 40: Panel Designing Taking Into Consideration The Effects Of Noise

    E6581301 Panel designing taking into consideration the effects of noise The inverter generates high frequency noise. When designing the control panel setup, consideration must be given to that noise. Examples of measures are given below. • E Wire so that the main circuit wires and the control circuit wires are separated. Do not place them in the same conduit, do not run them parallel, and do not bundle them.
  • Page 41: Connection Equipment

    E6581301 2. Connection equipment • @ • @ Danger • E Never disassemble, modify or repair. This can result in electric shock, fire and injury. For repairs, call your sales agency. Disassembly prohibited • E Don't stick your fingers into openings such as cable wiring hole and cooling fan covers. This can result in electric shock or other injury.
  • Page 42 Control and main power supply The control power supply and the main circuit power supply for the VF-AS1 are the same. If a malfunction or trip causes the main circuit to be shut off, control power will also be shut off.
  • Page 43: Standard Connections

    E6581301 Standard connections • @ • @ Danger • E Do not connect input power to the output (motor side) terminals (U/T1, V/T2, W/T3). Connecting input power to the output could destroy the inverter or cause a fire. • E Do not connect a regenerative braking resistor to any DC terminal (between PA/+ and PC/-, or between PO and PC/-).
  • Page 44 E6581301 [Standard connection diagram - sink] The figure below shows an example of typical wiring in the main circuit of a 200V 0.4-45kW/400V 0.75-75kW inverter. Main circuit power source 200V class: 0.4~45kW Three-phase 200~240V-50/60Hz 400V class: 0.75~75kW Three-phase 380~480V-50/60Hz Motor Main Noise circuit...
  • Page 45 E6581301 [Standard connection diagram - sink] The figure below shows an example of typical wiring in the main circuit of a 200V 55, 75kW/400V 90-500kW inverter. Main circuit power source 200V class: 55kW, 75kW Three-phase 300~220V-50Hz Three-phase 200~240V-60Hz 400V class: 90kW Three-phase 380~480V-50/60Hz 110kW~500kW Three-phase 380~440V-50Hz...
  • Page 46 E6581301 [Standard connection diagram - source] The figure below shows an example of typical wiring in the main circuit of a 200V 0.4-45kW/400V 0.75-75kW inverter. Main circuit power source 200V class: 0.4~45kW Three-phase 200~240V-50/60Hz 400V class: 0.75~75kW Three-phase 380~480V-50/60Hz Motor Main Noise circuit...
  • Page 47 E6581301 [Standard connection diagram - source] The figure below shows an example of typical wiring in the main circuit of a 200V 55, 75kW/400V 90-500kW inverter. Main circuit power source 200V class: 55kW, 75kW Three-phase 300~220V-50Hz Three-phase 200~240V-60Hz 400V class: 90kW Three-phase 380~480V-50/60Hz 110kW~500kW Three-phase 380~440V-50Hz...
  • Page 48: Description Of Terminals

    Description of terminals 2.3.1 Main circuit terminals This diagram shows an example of wiring of the main circuit. Use options if necessary. Power supply and motor connections • @ VF-AS1• @ Connect the power Connect the motor Power supply cables to RL1, S/L2, interconnect cables to and T/L3.
  • Page 49: Control Circuit Terminals

    E6581301 2.3.2 Control circuit terminals The control circuit terminal board is common to all equipment. Shorting bar between ST-CC (VFAS1- * * * * * -WN) ⇒ How to set input terminal function, refer to section 7. Terminal Input/ Electrical Function Inverter internal circuits symbol...
  • Page 50 E6581301 Terminal Input/ Electrical Function Inverter internal circuits symbol output specifications Constant 10Vdc voltage circuit Output Analog input setting power output (Permissible load current:10mAdc) SW3: Multifunction programmable analog input 2.2k 12.7k terminal when SW3 is in the RR position. 10Vdc RR/S4 Input Standard default setting:0~10Vdc input and...
  • Page 51 E6581301 Default setting (Settings marked SW settings Function with • œ ) SOURCE SINK Setting for using the inverter’s internal power supply in sink logic • œ mode INT/PLC SOURCE SINK Setting for using the inverter’s external power supply in sink logic mode INT/PLC SOURCE...
  • Page 52 E6581301 Sink logic/source logic (When inverter's internal power supply is used) Current flowing out turns control input terminals on. These are called sink logic terminals. The method generally used in Europe is source logic in which current flowing into the input terminal turns it on. Sink logic terminals and source logic terminals are sometimes referred to as negative logic terminals and positive logic terminals, respectively.
  • Page 53 E6581301 Sink logic/source logic (When an external power supply is used) The P24/PLC terminal is used to connect to an external power supply or to insulate a terminal from other input or output terminals. Use the slide switch SW1 to switch between sink logic and source logic configurations. <Examples of connections when an external power supply is used>...
  • Page 54: Serial Rs485 Communication Connector

    When connecting a communications device via the two-wire connector, carefully read the precautions for use in the operating manual for the communications device. * When connecting the VF-AS1 to other inverters, you do not need to connect the master receive lines (pins 4 and 5) or the slave send lines (pins 3 and 6).
  • Page 55 E6581301 3. Operations This section explains the basics of operation of the inverter. Check the following again before starting operation. 1) Are all wires and cables connected correctly? 2) Does the supply voltage agree with the rated input voltage? • @ • @ Danger •...
  • Page 56: Setting/Monitor Modes

    E6581301 Setting/monitor modes The VF-AS1 has the following three setting/monitor modes. Standard monitor mode The standard inverter mode. This mode is enabled when inverter power goes on. This mode is for monitoring the output frequency and setting the frequency reference value. If also displays information about status alarms during running and trips.
  • Page 57: Simplified Operation Of The Vf-As1

    E6581301 Simplified operation of the VF-AS1 On of three operation modes can be selected: terminal board operation, operation panel and combination of both. ⇒ For other operation modes, refer to Section 5.5. Terminal board mode :Operation by means of external signals...
  • Page 58: Frequency Setting

    E6581301 Frequency setting 1) Setting the frequency using potentiometer Potentiometer The operation frequency by potentiometer (1~10kƒ ¶ - 1/4W ) for setting ⇒ Refer to Section 7.3 for details of adjustment. :Frequency settings RR/S4 60Hz With potentiometer Frequency [Parameter setting] Set the “basic parameter frequency setting mode selection 1”...
  • Page 59 E6581301 4) Setting the frequency using input voltage (0~10Vdc) Voltage signal Voltage signal (0~10V) for setting the operation frequency ⇒ Refer to Section 7.3 for details of adjustment. VI/II :Voltage signal 0-10Vdc 60Hz Frequency 10Vdc 0Vdc [Parameter setting] Set the “extended parameter analog input VI/II voltage/current switching” parameter In addition, set the “basic parameter frequency setting mode selection 1”...
  • Page 60 E6581301 Key operated LED display Operation Press either the key or the key to change to the parameter group Press the ENTER key to display the first extended parameter Press the key to change to Pressing the ENTER key allows the reading of parameter setting. (Default setting: ) Press the key to change the parameter to...
  • Page 61: Panel Operation

    E6581301 3.2.2 Panel operation This section describes how to start/stop the motor, and set the operation frequency with the operating panel. :Set frequency Example of basic connection MCCB :Motor starts Motor R/L1 U/T1 Power S/L2 V/T2 :Stop the motor supply STOP T/L3 W/T3...
  • Page 62 E6581301 Example of operation panel control Key operated LED display Operation The running frequency is displayed. (When standard monitor display selection [Output frequency]) Set the operation frequency. Press the ENTER key to save the operation frequency. and the ⇔ frequency are displayed alternately. Pressing the RUN key causes the motor to accelerate to the set ⇒...
  • Page 63: Searching And Setting Parameters

    E6581301 4. Searching and setting parameters There are two types of setting mode quick mode and standard setting mode. Quick mode : EASY Key: ON Eight frequently used basic parameters are just displayed (Factory default position). Quick mode (EASY) Title Function Automatic function setting V/f control mode selection...
  • Page 64: How To Set Parameters

    E6581301 How to set parameters This section explains how to set parameters, while showing how parameters are organized in each setting monitor mode. 4.1.1 Setting parameters in the selected quick mode To place the inverter in this mode, press the key (the LED lights up), and then press the key.
  • Page 65: Setting Parameters In The Standard Setting Mode

    E6581301 4.1.2 Setting parameters in the standard setting mode Press the key to place the inverter in this mode. MODE How to set basic parameters Selects parameter to be changed. (Press the key.) Reads the programmed parameter setting. (Press the key.) Change the parameter value.
  • Page 66: Functions Useful In Searching For A Parameter Or Changing A Parameter Setting

    E6581301 Adjustment range and display of parameters : An attempt has been made to assign a value that is higher than the programmable range. Or, as a result of changing other parameters, the programmed value of the parameter that is now selected exceeds the upper limit.
  • Page 67: Basic Parameters

    E6581301 5. Basic parameters This parameter is a basic parameter for the operation of the inverter. ⇒ Refer to Section 11, Table of parameters. History function : History function • Function Automatically searches for 5 latest parameters that are programmed with values different from the standard default setting and displays them in the .
  • Page 68: Setting Acceleration/Deceleration Time

    E6581301 Setting acceleration/deceleration time : Automatic acceleration/deceleration : Acceleration time 1 : Deceleration time 1 • Function 1) For acceleration time 1 programs the time that it takes for the inverter output frequency to go from 0Hz to maximum frequency 2) For deceleration time 1 programs the time that it takes for the inverter output frequency to got from maximum frequency...
  • Page 69: Manually Setting Acceleration/Deceleration Time

    E6581301 5.2.2 Manually setting acceleration/deceleration time Set acceleration time from 0 (Hz) operation frequency to maximum frequency and deceleration time as the time when operation frequency goes from maximum frequency to 0 (Hz). Output frequency [Hz] (Manual setting) Time [s] [Parameter setting] Title Function...
  • Page 70 3) Increasing torque manually (V/f constant control) The VF-AS1 inverter is set to this control mode by factory default. This is the setting of constant torque characteristics that are suited for such things as conveyors. It can also be used to manually increase starting torque.
  • Page 71: Setting Parameters By Operating Method

    E6581301 Setting parameters by operating method : Automatic function setting • Function Automatically programs all parameters (parameters described below) related to the functions by selecting the inverter's operating method. The major functions can be programmed simply. [Parameter setting] Title Function Adjustment range Default setting :Disabled...
  • Page 72: Selection Of Operation Mode

    E6581301 Voltage/current switching by means of an external terminal ( Switching between remote and local (different frequency commands) can be performed by turning on or off the S3 terminal. In that case, apply a voltage via the RR/S4 terminal and a current via the VI/II terminal. S3-CC OFF: The frequency is set according to the voltage applied to the RR/S4 terminal.
  • Page 73 E6581301 <Frequency setting mode selection> [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage input) :RX (voltage input) :Operation panel input enabled (including LED/LCD option input) :2-wire RS485 communication input Frequency setting mode :4-wire RS485 communication input selection 1 :Communication option input :Optional AI1 (differential current input)
  • Page 74: Preset Speed Operation

    E6581301 The functions assigned to the following control input terminals (contact input: ⇒ Refer to Section 7.2) are always activated regardless of the settings of the command mode selection and frequency setting mode selection 1 • Reset terminal (default setting: RES, valid only for tripping) •...
  • Page 75 E6581301 2) Setting the run and stop frequencies (forward run, reverse run and coast stop) by means of external signals and setting the operation frequency with the operation panel Title Function Example of setting Run/stop : ON/OFF of terminals F-CC/R-CC Command mode selection (Terminal (Standby: connection of terminals...
  • Page 76 E6581301 4) Setting the run, stop and operation frequencies (forward run, reverse run and coast stop) by means of external signals (default setting) Title Function Example of setting Run/stop :ON/OFF of terminals F-CC/R-CC Command mode Speed command :External signal input :(Terminal input) selection (1) VI/II terminal: 0~+10Vdc...
  • Page 77: Selecting Control Mode

    E6581301 Selecting control mode : V/f control mode selection • Function With “VF-AS1,” the V/f controls shown below can be selected. 0: Constant torque characteristics 1: Voltage decrease curve 2: Automatic torque boost *1 3: Sensorless vector control 1 *1...
  • Page 78: Automatic Torque Boost

    (Constant torque characteristics) and increase torque manually. Motor constant must be set. If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter, there is basically no need to set the motor constant.
  • Page 79 (4) Effective in producing high motor torque at low speed. Motor constant must be set. If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter, there is basically no need to set the motor constant.
  • Page 80 Motor constant must be set. If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter, there is basically no need to set the motor constant.
  • Page 81: Manual Torque Boost-Increasing Torque Boost At Low Speeds

    E6581301 Manual torque boost–increasing torque boost at low speeds : Manual torque boost 1 • Function If torque is inadequate at low speeds, increase torque by raising the torque boost rate with this parameter. Base frequency voltage 1 [V]/[%] Output frequency [Hz] Base frequency [Parameter setting] Title...
  • Page 82: Maximum Frequency

    E6581301 Maximum frequency : Maximum frequency • Function 1) Programs the range of frequencies output by the inverter (maximum output values). 2) This frequency is used as the reference for acceleration/deceleration time. Output frequency [Hz] In case of =80Hz • This function determines the 80Hz maximum value in line with the ratings of the motor and load.
  • Page 83: Setting Frequency Command Characteristics

    E6581301 5.11 Setting frequency command characteristics : VI/II point setting : RR/S4 point setting : RX point setting It sets up, when using the optional circuit board. : Point 1, 2 setting/ frequency ⇒ For details, refer to Section 7.3. •...
  • Page 84 E6581301 : ON –: OFF (Speed commands other than preset speed commands are valid when all are OFF) Preset speed Terminal S1-CC – – – – – – – S2-CC – – – – – – – S3-CC – – –...
  • Page 85 E6581301 Below is an example of 7-step speed operation. Output frequency [Hz] Time ST-CC F-CC S1-CC S2-CC S3-CC Example of 7-step speed operation 4)Setting the operation mode An operation mode can be selected for each preset speed. Operation mode setting Title Function Adjustment range...
  • Page 86: Selecting Forward And Reverse Runs (Operation Panel Only)

    E6581301 5.13 Selecting forward and reverse runs (operation panel only) : Forward/reverse run selection • Function Program the direction of rotation of the motor when the running and stopping are made using the RUN key and STOP key on the operation panel. Valid when (command mode selection) = (operation panel input).
  • Page 87: Setting The Electronic Thermal

    E6581301 5.14 Setting the electronic thermal : Motor electronic thermal protection level 1 : Electronic thermal protection characteristic selection : Overload reduction starting frequency : Motor 150%-overload time limit : Inverter overload selection • Function This parameter allows selection of the appropriate electronic thermal protection characteristics according to the particular rating and characteristics of the motor.
  • Page 88 E6581301 Setting of motor electronic thermal protection level 1 If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1 so that it fits the motor's rated current.
  • Page 89 E6581301 Setting of motor electronic thermal protection level 1 If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1 so that it fits the motor's rated current.
  • Page 90: Inverter Overload

    E6581301 3) Inverter overload characteristics Set to protect the inverter unit. Cannot be turned off by parameter setting. The inverter has two overload detecting functions, which can be switched from one to another using parameter (inverter overload detection mode selection). [Parameter setting] Title Function...
  • Page 91: Output Current

    E6581301 5.15 Changing the display unit % to A (ampere)/V (volt) : Current/voltage display mode • Function These parameters are used to change the unit of monitor display. % ⇔A (ampere)/V (volt) Current 100% = Inverter’s rated current 200V-class voltage 100% = 200Vac 400V-class voltage 100% = 400Vac Example of setting During the operation of the VFAS1-2037PL (rated current 16.6A) at the rated load (100% load), units are displayed...
  • Page 92: Meter Setting And Adjustment

    Connect meters as shown below. <Connection to terminal FM> Meter: Frequency meter (default setting) VF-AS1 The reading of the frequency meter fluctuates during calibration. A frequency meter QS60T is optionally available. Output modes of the FM terminal When used with a 0~1mAdc ammeter...
  • Page 93 E6581301 [Terminal FM-related parameters] Adjustment Title Function Adjustment range Default setting level : Output frequency : Frequency command value : Output current : Input voltage (DC detection) : Output voltage : Compensated frequency *2 : Speed feedback (real-time value) : Speed feedback (1 second filter) : Torque : Torque command : Torque current...
  • Page 94 MODE (When standard monitor display selection [Output frequency]) For meter connection, the VF-AS1 inverter has two output terminals; FM and AM, which can be used simultaneously. Meter adjustment 1 when the inverter is at rest (adjustment by setting ) to...
  • Page 95 E6581301 Meter adjustment Fixed output 1 Fixed output 2 Fixed output 3 Adjustment level ) • • ) • • ) • • 185% 100% 150% 250% 135% 100% Note: The 100% value of input/output power is the product of • ã 3×200V (400V) × inverter’s rated current. [Example: Procedure of calibrating the meter connected to the terminal AM to which “output current”...
  • Page 96: Pwm Carrier Frequency

    E6581301 Gradient bias adjustment of analog monitor output Here is an example of the adjustment of output from 0-20mA → 20-0mA, 4-20mA using the FM terminal. (mA) (mA) 100% 100% (mA) (mA) small large 100% 100% The analog output inclination can be adjusted using the parameter 5.17 PWM carrier frequency : PWM carrier frequency...
  • Page 97: Trip-Less Intensification

    E6581301 5.18 Trip-less intensification 5.18.1 Auto-restart (Restart during coasting) : Auto-restart control selection Warning • Do not go near motors and equipment. Motors and equipment that have stopped temporarily after momentary power failure will restart suddenly after recovery. This could result in unexpected injury. Mandatory •...
  • Page 98 E6581301 2) Restarting motor during coasting (Motor speed search function) Motor speed F-CC ST-CC = : This function operates after the ST-CC terminal connection has been opened first and then connected again. Title Function Adjustment range Default setting Example of setting :Disabled :At auto-restart after momentary stop Auto-restart control...
  • Page 99 E6581301 5.18.2 Regenerative power ride-through control/Deceleration stop during power failure/Synchronized acceleration/deceleration : Regenerative power ride-through control : Non-stop control time/Deceleration time during power failure : Synchronized deceleration time : Synchronized acceleration time : Regenerative power ride-through control level • Function 1) Regenerative power ride-through control: When momentary power failure occurs during operation, this function makes operation continue using the regeneration energy from a motor.
  • Page 100 E6581301 An example of setting when Input voltage Motor speed Time Deceleration stop • E Even after the recovery from an input power failure, the motor continues slowing down to a stop. If the voltage in the inverter main circuit falls below a certain level, however, control will be stopped and the motor will coast. •...
  • Page 101: Dynamic (Regenerative) Braking - For Abrupt Motor Stop

    (Enter the time elapsed before the inverter trips if a load 10 times as large as the allowable continuous braking resistance specified using is applied.) There is no need to change resistance settings recommended by Toshiba (except DGB resistance setting). Note 2: If...
  • Page 102 E6581301 All 200V VF-AS1 and 400V VF-AS1 with ratings of up to 160kW have built-in dynamic braking resistors as standard equipment. If the rating of your inverter falls within this range, connect the resistor, as shown in Figure a) below or Figure b) on the next page.
  • Page 103 E6581301 b) When a using braking resistor without thermal fuse An external braking resistor (optional) * If no power supply is provided TH - Ry for the control circuit MCCB PA/+ Motor Three-phase R/L1 main circuit S/L2 power supply T/L3 Depression transformer Inverter...
  • Page 104 E6581301 c) Capacities of 400V-200kW or more TH - Ry An external braking resistor (optional) * If no power supply is provided Dynamic braking unit (optional) for the control circuit MCCB PA/+ Motor R/L1 Three-phase S/L2 main circuit T/L3 power supply Depression transformer Forward run/stop...
  • Page 105 E6581301 Selection of braking resistor option and braking unit Standard braking resistors are listed in the table below. The usage rate is 3%. (Except for type DGP***) Braking resistor Continuous regenerative Inverter type Model number Rating braking allowable capacity [Note 2] [Note 1] VFAS1-2004PL, PBR-2007...
  • Page 106 E6581301 Minimum resistance of connectable braking resistors The minimum allowable resistance values of the externally connectable braking resistors are listed in the table below. Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance values. (For 200kW or greater models, a dynamic braking resistor drive unit (optional separate unit) is needed.) 200V Class 400V Class...
  • Page 107: Standard Default Setting

    E6581301 5.20 Standard default setting : Default setting • Function This parameter is to set two or more parameters at a time for different commands. Using this parameter, all parameters can be also return to their respective default settings by one operation, and save or set specific parameters individually.
  • Page 108 E6581301 Default setting ( Setting parameter resets all parameters except the following to their default settings. When this parameter is set to 3, is displayed for a while, then switches back to the original display ( ). Note that this setting also clears all trip history records. Trip history data will be cleared at this time. Following parameters are designed considering maintenance that they cannot be reset to the factory default setting even if you set the parameter .
  • Page 109: Searching For All Reset Parameters And Changing Their Settings

    E6581301 5.21 Searching for all reset parameters and changing their settings : Automatic edit function • Function Automatically searches for only those parameters that are programmed with values different from the standard default setting and displays them in the user parameter group .
  • Page 110: Easy Key Function

    E6581301 5.22 EASY key function : Registered parameter display selection Quick registration parameter 1~32 : EASY key function selection • Function The following three functions can be assigned to the EASY key for easy operation by means of a single key. •...
  • Page 111 E6581301 [How to select parameters] Select the desired parameters as parameters 1 to 32 ( ). Note that parameters should be specified by communication number. For communication numbers, refer to Table of parameters. In the quick mode, only parameters registered as parameters 1 to 32 are displayed in order of registration. By default, parameters are set as shown in the table below.
  • Page 113: Extended Parameters

    E6581301 6. Extended parameters Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. ⇒ Refer to Section 11, Table of parameters. Input/output parameters 6.1.1 Low-speed signal : Low-speed signal output frequency • Function When the output frequency exceeds the setting of an ON signal will be generated.
  • Page 114: Putting Out Signals Of Arbitrary Frequencies

    E6581301 6.1.2 Putting out signals of arbitrary frequencies : Speed reach setting frequency : Speed reach detection band • Function When the output frequency becomes equal to the frequency set by ± , an ON or OFF is generated. [Parameter setting of frequency and detection band] Title Function Adjustment range...
  • Page 115: Input Signal Selection

    E6581301 Input signal selection 6.2.1 Priority when forward/reverse run commands are entered simultaneously : Priority when forward/reverse run commands are entered simultaneously • Function This parameter allows you to select the direction in which the motor runs when a forward run (F) command and a reverse run (R) command are entered simultaneously.
  • Page 116: Assigning Priority To The Terminal Board In The Operation Panel And Operation Mode

    E6581301 6.2.2 Assigning priority to the terminal board in the operation panel and operation mode : Input terminal priority selection • Function This parameter is used to give priority to certain external commands entered from the terminal board in operation panel and operation mode. For example, when jogging the motor by giving signals externally.
  • Page 117: Binary/Bcd Signal Selection (Expansion Tb Option Unit)

    E6581301 Output frequency [Hz] Forward run Set frequency Forward run ‚ O Panel key STOP STOP STOP ST-CC ‚ r 3-CC (Jog run) 6.2.3 Binary/BCD signal selection (Expansion TB option unit) : 16-bit binary/BCD input selection (Expansion TB option unit) To be released soon.
  • Page 118: Modifying Input Terminal Functions

    E6581301 Terminal function selection 6.3.1 Keeping an input terminal function always active (ON) : Always ON function selection 1~3 • Function This parameter specifies an input terminal function that is always kept active (ON). (Only one function selectable) [Parameter setting] Title Function Adjustment range...
  • Page 119: Programmable Controller

    E6581301 Connection method 1) a-contact input Inverter a-contact switch Sink setting Input This function is activated when the input terminal and CC terminal (common) are short-circuited. Use this function to specify forward/reverse run or a preset speed operation. 2) Connection with transistor output Inverter Programmable controller Input...
  • Page 120: Using The Servo Lock Function

    E6581301 6.3.3 Using the servo lock function : Input terminal function selection 3 (ST) : Starting frequency setting • Function As with the operation of a server motor, these parameters allow you to operate the motor at 0Hz by simply issuing an operation signal.
  • Page 121 E6581301 6.3.5 Response time of input/output terminals : Input terminal 1 response time selection : Input terminal 2 response time selection : Input terminal 3 response time selection : Input terminal 4 response time selection : Input terminal 5~12 response time selection : Input terminal 13~20 response time selection ⇒...
  • Page 122 E6581301 Setting of switching terminals The V/f1, V/f2, V/f3 and V/f4 switching function is not yet assigned to any terminal. Therefore, it is necessary to assign them to unused terminals. Ex.) Assigning the V/f switching 1 function to S1 and the V/f switching 2 function to S2. Title Function Adjustment range...
  • Page 123: V/F 5-Point Setting

    E6581301 V/f 5-point setting : V/f 5-point setting VF1 frequency : V/f 5-point setting VF4 frequency : V/f 5-point setting VF1 voltage : V/f 5-point setting VF4 voltage : V/f 5-point setting VF2 frequency : V/f 5-point setting VF5 frequency : V/f 5-point setting VF2 voltage : V/f 5-point setting VF5 voltage : V/f 5-point setting VF3 frequency...
  • Page 124 E6581301 2) Automatic switching by means of switching frequencies ( Command selected Operation frequency with command Command selected with A: If the frequency set with is higher than that set with ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ Priority is given to the command set with B: If the frequency set with...
  • Page 125: Operation Frequency

    E6581301 Operation frequency 6.7.1 Start frequency/Stop frequency : Start frequency setting : Stop frequency setting • Function The frequency set with the parameter is put out as soon as operation is started. Use the parameter when a delay in response of starting torque according to the acceleration/deceleration time is probably affecting operation.
  • Page 126: Frequency Setting Signal 0Hz Dead Zone Handling Function

    E6581301 Output frequency [Hz] The inverter begins accelerating after the frequency command value has reached point B. Deceleration stop begins when the frequency command value decreases below point A. – 100% Operation frequency command value 6.7.3. Frequency setting signal 0Hz dead zone handling function : Frequency command dead band •...
  • Page 127 E6581301 Note:During DC braking, the DC braking current may be adjusted Output frequency [Hz] automatically to prevent the overload LED display protection function from being activated and causing the inverter to displayed Set frequency trip. DC braking The DC braking current may be adjusted automatically to prevent tripping.
  • Page 128: Motor Shaft Fixing Control

    E6581301 [Priority to DC braking during forward/reverse operation] (Forward/reverse run DC braking priority control = [ON]) • @ • @ Output frequency [Hz] : DC braking Set frequency Time [s] Reference frequency Forward run signal (F-CC) Reverse run signal (R-CC) (4) During normal forward/reverse run ( : Not recognized as a stop command, so that the DC braking is not active.
  • Page 129: Function Of Issuing A 0Hz Command During A Halt

    E6581301 LED display Output frequency [Hz] is displayed. is displayed. Set frequency DC braking start frequency Time [s] Output current [A] Operation signal (F-CC) Operation standby signal (ST-CC) Note 1: If the motor shaft fixing control parameter is set at (enabled) when the output frequency is below the DC braking start frequency and terminals ST-CC are closed (ON), the DC braking function is...
  • Page 130: Auto-Stop In Case Of Lower-Limit Frequency Continuous Operation

    E6581301 Auto-stop in case of lower-limit frequency continuous operation : Time limit for lower-limit frequency operation • Function If operation is carried out continuously at a frequency below the lower-limit frequency ( ) for the period time set , theinverter will automatically slow down the motor to a stop. “...
  • Page 131: Jog Run Mode

    E6581301 6.10 Jog run mode : Jog run frequency : Jog run stop pattern : Operation panel jog run mode • Function Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal generates a jog run frequency output at once, irrespective of the designated acceleration time.
  • Page 132: Setting Frequency Via External Contact Input (Up/Down Frequency Setting)

    E6581301 [Setting of jog run setting terminal (S3-CC)] Assign control terminal S3 ([ : preset speed 3] in default setting) as the jog run setting terminal. Title Function Adjustment range Example of setting Input terminal function selection 7 (S3) (Jog run setting terminal) Note:During the jog run mode, there is LOW (low speed detection signal) output but no RCH (designated frequency reach signal) output, and PID control does not work.
  • Page 133 E6581301 Adjustment with continuous signals (Parameter setting example 1) Set parameters as follows to adjust the output frequency up or down in proportion to the frequency adjustment signal input time: Panel frequency incremental gradient = setting time Panel frequency decremental gradient = setting time Set parameters as follows to adjust the output frequency up or down almost in synchronization with the adjustment by the panel frequency command:...
  • Page 134: Jump Frequency - Jumping Resonant Frequencies

    E6581301 If two signals are input simultaneously • If a clear single and an up or down signal are input simultaneously, priority will be given to the clear signal. • If up and down signals are input simultaneously, the frequency will be increased or reduced by the difference between the settings of .
  • Page 135: Preset Speed Operation Frequencies

    E6581301 [Parameter setting] Title Function Adjustment range Default setting Jump frequency 1 Jumping width 1 Jump frequency 2 Jumping width 2 Jump frequency 3 Jumping width 3 If the upper limit frequency ( ) is within jump frequency range, it is limited to the lowest frequency in the jump frequency range. If the lower limit frequency ( ) is within jump frequency range, it is limited to the highest frequency in the jump frequency range.
  • Page 136: Retry Function

    E6581301 6.14 Trip-less intensification 6.14.1 Retry function : Retry selection (selecting the no. of times) Warning • Stand clear of motors and equipment. The motor and equipment stop when the alarm is given, selection of the retry function will restart them suddenly after the specified time has elapsed.
  • Page 137: Avoiding Overvoltage Tripping

    E6581301 Even when trip retention selection parameter ( ) is set to , the retry function is enabled by setting. During retry the blinking display will alternate between and the monitor display specified by parameter monitor display selection parameter The number of retries will be cleared if the inverter is not tripped for the specified period of time after a successful retry.
  • Page 138 E6581301 [Parameter setting] Title Function Adjustment range Default setting 200V models: Base frequency voltage 1 V class: (output voltage V class: 400V models: adjustment) Base frequency voltage :Supply voltage uncorrected, output voltage unlimited selection :Supply voltage corrected, output voltage unlimited (correction of supply :Supply voltage uncorrected, output voltage limited voltage)
  • Page 139: Drooping Control

    E6581301 6.14.4 Reverse run prohibition : Reverse run prohibition selection • Function This function prevents the motor from running in the forward or reverse direction when it receives the wrong operation signal. [Parameter setting] Title Function Adjustment range Default setting :Permit all, :Prohibit reverse run Reverse-run prohibition selection...
  • Page 140: Light-Load High-Speed Operation Function

    E6581301 The change in frequency at the time of drooping can be calculated, as described below: a) Gain by internal torque reference (Gain1) If internal torque reference (%) ≧ 0 Gain1 = (internal torque reference - dead band ) / 100 Gain1 needs to be set at 0 or a positive number.
  • Page 141: Braking Function

    E6581301 6. 17 Braking function : Braking mode selection : Brake release time : Load portion torque input : Creeping frequency selection : Creeping time : Hoisting torque bias input : Braking time learning function : Lowering torque bias multiplier •...
  • Page 142 For the braking functions, the pre-excitation time is automatically determined by the inverter from motor- related constants. When the VFAS1-2037PL is used in combination with a Toshiba 4P-3.7kW-60Hz-200V standard motor, the preliminary excitation time is approximately 0.1 to 0.2 seconds.
  • Page 143: Acceleration/Deceleration Suspend Function

    E6581301 6.18 Acceleration/deceleration suspend function : Acceleration/deceleration : Deceleration suspend frequency suspend function : Deceleration suspend time : Acceleration suspend frequency : Acceleration suspend time • Function Using these parameters, acceleration or deceleration can be suspended to let the motor run at a constant speed.
  • Page 144: Commercial Power/Inverter Switching

    E6581301 If the stall control function is activated during constant-speed rotation The frequency drops momentarily as a result of stall control, but the time for which the frequency drops is included in the suspend time. Output frequency [Hz] Time [s] Stall (Momentary acceleration (deceleration) suspend time) = (t1 + t2 + ts) Stall control...
  • Page 145: Pid Control

    E6581301 [Timing chart (example)] Commercial power switching frequency holding time Detection time Commercial power/inverter switching frequency Set frequency Inverter-side switching waiting time MC output for inverter operation Commercial power/inverter switching output 1 (P24-OUT1) Commercial power-side switching waiting time MC output for commercial power operation Commercial power/inverter switching output 2 (P24-OUT2) Commercial power switching signal (S3-CC)
  • Page 146: Stop Position Control Function

    E6581301 6.21 Stop position control function : V/f control mode selection : Number of PG input pulses : PID control switching : Selection of number of PG : PID control feedback control input phases signal selection : Simple positioning : Proportional (P) gain completion range •...
  • Page 147 E6581301 Preset speed operation frequency 2 Preset-speed operation frequency 1 Output frequency [Hz] Stop position control mode Preset speed operation frequency 2 Time [s] Run command (F) Preset speed 1 (S1) Preset speed 2 (S2) Stop position command signal (RR/S4) Positioning completion range If the stop position control command is entered during high-speed operation, a trip may occur because of overcurrent or overvoltage.
  • Page 148: Setting Motor Constants

    E6581301 6.22 Setting motor constants : Auto-tuning 1 : Motor rated rotational speed (motor nameplate) : Slip frequency gain : Motor constant 1 (torque boost) : Auto-tuning 2 : Motor constant 2 (no-load current) : Motor rated capacity (motor nameplate) : Motor constant 3 (leak inductance) : Motor rated current (motor nameplate) : Motor constant 4 (rated slip)
  • Page 149 Different from the inverter capacity Others * When using a long cable (guide: 30m or over), be sure to make auto-tuning 1 ( = ). Toshiba standard 4P motor Is motor capacity same Set the following parameters, as specified on with inverter capacity? the motor nameplate.
  • Page 150 E6581301 Precautions on auto-tuning 1 (1) The inverter is tuned automatically (auto-tuning 1 = ) when the inverter is started for the first time after setup. During auto-tuning 1, which takes several seconds, the motor is energized, although it is standing still. Noise may be produced by the motor during auto-tuning 1, which, however, does not indicate that something is wrong with the inverter or the motor.
  • Page 151: Increasing The Motor Output Torque Further In Low Speed Range

    Examples of setting the motor constants Here are setting examples for each of the selections 1, 2 and 3 described in Section 6.22. a) Combination with a Toshiba standard motor (4P motor with the same capacity as the inverter) Inverter : VFAS1-2037PL Motor : 3.7kW-4P-60Hz...
  • Page 152: Speed Limits In Torque Control Mode

    E6581301 6.24 Torque control ⇒ For details, refer to Instruction Manual (E6581331) specified in Section 6.41. 6.24.1 Torque command : V/f control mode selection : Torque command selection : VI/II input point 1 setting : VI/II input point 1 rate : VI/II input point 2 setting : VI/II input point 2 rate : RR/S4 input point 1 setting...
  • Page 153: Selection Of Tension Torque Bias Input And Load Sharing Gain Input

    E6581301 For a crane/hoist, an elevator application, as lifted Reverse run up and down at controlled speeds, the direction of rotation is frequently reversed. In such cases, the Forward run load can be started smoothly, by adding load torque into the torque reference equivalent to the additional torque, when starting acceleration after releasing the brake.
  • Page 154: Torque Limit

    E6581301 6.25 Torque limit 6.25.1 Torque limit switching : Power running torque limit 1 : Power running torque limit 3 selection level : Power running torque limit 1 : Regenerative braking torque level limit 3 level : Regenerative braking torque : Power running torque limit 4 limit 1 selection level...
  • Page 155 E6581301 [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage Power running torque limit 1 selection input) :RX (voltage input) Power running torque limit 1 level %:Disabled :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage Regenerative braking torque limit 1 input) selection :RX (voltage input)
  • Page 156 E6581301 RX-CC RR/S4 -CC, VI-CC 100% +100% Torque produced Torque produced by motor by motor -10V +10V II-CC -100% 100% Torque produced by motor 20mA [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage Power running torque limit 1 selection input) :RX (voltage input) :VI/II (voltage/current input)
  • Page 157 E6581301 Operation frequency Frequency [Hz] If the torque limit function is not activated Actual speed Time [s] Torque [N·m] Torque limit level Time [s] Mechanical brake (released) Time [s] = (In sync with min. time) The operation frequency keeps increasing, even if the torque limit function is activated. In this control mode, the actual speed is kept in sync with the operation frequency, while torque is held at a limit level when it decreases as a result of the release of the mechanical brake.
  • Page 158: Current And Speed Control Gain

    E6581301 6.26 Stall prevention function 6.26.1 Power running stall continuous trip detection time : Power running stall continuous trip detection time • Function A function for preventing lifting gear from failing accidentally. If the stall prevention function is activated in succession, the inverter judges that the motor has stalled and trips.
  • Page 159: Fine Adjustment Of Frequency Setting Signal

    E6581301 6.28 Fine adjustment of frequency setting signal : VI/II input bias : RX input gain : VI/II input gain : Optional AI1 input bias : RR/S4 input bias : Optional AI1 input gain : RR/S4 input gain : Optional AI2 input bias : RX input bias : Optional AI2 input gain •...
  • Page 160 E6581301 6.30 Acceleration/deceleration 2 6.30.1 Setting acceleration/deceleration patterns and switching acceleration/deceleration patterns 1, 2, 3 and 4 : Acceleration time 2 : Deceleration S-pattern upper limit adjustment : Deceleration time 2 : Acceleration time 3 : Acceleration/deceleration 1 pattern : Deceleration time 3 : Acceleration/deceleration 2 pattern : Acceleration/deceleration 3 pattern : Acceleration/deceleration time 1, 2, 3, 4 selection...
  • Page 161 E6581301 2) Switching by frequencies - Automatically switching acc/dec times at certain frequencies Title Function Adjustment range Default setting Acceleration/deceleration switching frequency 1 Acceleration/deceleration switching frequency 2 Acceleration/deceleration switching frequency 3 Note:Regardless of the sequence of input of frequencies, acc/dec times are switched from 1 to 2 at the lowest frequency, from 2 to 3 at the middle frequency and from 3 to 4 at the highest frequency.
  • Page 162 E6581301 Setting parameters a) Operating method: Terminal input Set the command mode selection b) Use the S2 and S3 terminals for switching. (Instead, other terminals may be used.) S2: Acceleration/deceleration switching signal 1 S3: Acceleration/deceleration switching signal 2 Title Function Adjustment range Example of setting (Acceleration/deceleration...
  • Page 163: Pattern Operation

    E6581301 3) S-pattern acceleration/deceleration 2 Select this pattern to obtain slow acceleration in a demagnetizing region with a small motor acceleration torque. This pattern is suitable for high-speed spindle operation. Output frequency [Hz] Output frequency [Hz] Maximum frequency Maximum frequency Set frequency Set frequency Base frequency...
  • Page 164 E6581301 <Basic operating> Step Setting Parameter Set the pattern operation selection (Deselect) parameter at “Enabled.” (Pattern operation enabled, setting in seconds) (Pattern operation enabled, setting in minutes) Set all necessary operation frequencies. (Preset speed operation frequencies 1~7) In addition, set frequencies for preset (Preset speed operation frequencies 8~15) speed operation.
  • Page 165: Preset Speed Mode

    E6581301 Pattern operation switching output (output terminal function: If the pattern operation switching output function is selected (activated), a signal is put out on completion of all the predetermined patterns of operation. When there is no operation command left to be entered or the pattern operation selection signal changes, the output terminals are turned off.
  • Page 166: Protection Functions

    E6581301 6.33 Protection functions 6.33.1 Setting of stall prevention level : Stall prevention level Warning • Do not set the stall prevention level ( ) extremely low. If the stall prevention level parameter ( ) is set at or below the no-load current of the motor, the stall preventive function will be always active and increase the frequency when it judges that regenerative Prohibited braking is taking place.
  • Page 167: Emergency Stop

    E6581301 6.33.3 Emergency stop : Emergency stop : Emergency DC braking control time • Function Emergency stop mode can be selected. At emergency stop, a trip message (“ ”) is displayed. FL relay can be deactivated using the output function selection. 1) Emergency stop by terminal operation Emergency stop can be performed with the a or b-contact.
  • Page 168: Output Phase Failure Detection

    E6581301 6.33.4 Output phase failure detection : Output phase failure detection selection • Function This parameter detects inverter output phase failure. If the inverter detects an open phase failure, the tripping function and the FL relay will be activated. At the same time, the trip information will also be displayed.
  • Page 169: Control Mode For Low Current

    E6581301 6.33.8 Control mode for low current : Low current detection hysteresis width : Low current trip selection : Low current detection current : Low current detection time • Function If the current is lower than level and passes for a time longer than , the inverter trips.
  • Page 170: Overtorque Trip

    E6581301 6.33.10 Overtorque trip : Overtorque trip selection : Overtorque detection level during power running : Overtorque detection level during regenerative braking : Overtorque detection time : Overtorque detection hysteresis • Function Trips the inverter or issues an alarm if the total time for which torque is above the level set with reaches the time set with .
  • Page 171: Cooling Fan Control Selection

    E6581301 6.33.11 Cooling fan control selection : Cooling fan control selection • Function With this parameter, you can set the condition of cooling fan so that it operates only when the inverter requires cooling, and thus it can be used for a longer period. = : Automatic control of cooling fan, enabled.
  • Page 172: Abnormal Speed Detection

    E6581301 6.33.13 Abnormal speed detection : Abnormal speed detection time : Overspeed detection frequency upper band : Overspeed detection frequency lower band • Function These parameters allow you to set the inverter so that, when it is in sensor speed control mode ( ), it always monitors the rotational speed of the motor, even when the motor is at rest, and if the speed remains out of the specified limits for the specified length of time, it outputs an error signal.
  • Page 173: Braking Answer Waiting Time

    E6581301 6.33.16 Regenerative power ride-through control level : Regenerative power ride-through control level • Function This parameter is used to set the operation level of the regenerative power ride-through control and the deceleration stop. (Refer to Section 5.18.2.) Title Function Adjustment range Default setting Regenerative power ride-through control level...
  • Page 174: Guide To Time Of Replacement

    E6581301 6.33.19 Guide to time of replacement : Annual average ambient temperature • Function You can set the inverter so that it will calculate the remaining useful life of the cooling fan, main circuit capacitor and on-board capacitor from the ON time of the inverter, the operating time of the motor, the output current (load factor) and the setting of and that it will display and send out an alarm through output terminals when each component is approaching the end of its useful life.
  • Page 175 E6581301 6.34 Override : Override addition input selection : Override multiplication input selection • Function These parameters are used to adjust reference frequencies by means of external input. Title Function Adjustment range Default setting :Disabled :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage input) :RX (voltage input) :Operation panel input enabled (including LED/LCD option input)
  • Page 176 E6581301 Ex.1: (VI/II input), (disabled) Output frequency = Reference frequency + Override (VI/II input [Hz]) Ex.2: (VI/II input), (disabled) Output frequency = Reference frequency + Override (VI/II input [Hz]) 2) Multiplicative override In this mode, each output frequency is multiplied by an externally override frequency. [Ex.1: RR/S4 (Reference frequency), VI/II (Override input)] [Ex.2: RX (Reference frequency), VI/II (Override input)] Output frequency...
  • Page 177: Adjustment Parameters

    E6581301 6.35 Adjustment parameters 6.35.1 Pulse train output for meters : Logic output/pulse output selection (OUT1) : Pulse output function selection : Selection of number of pulses : Constant at the time of filtering : FM output filter • Function Pulse trains can be sent out through the OUT1-NO output terminals.
  • Page 178: Setting Of Optional Meter Outputs

    E6581301 6.35.2 Setting of optional meter outputs : Meter output settings ⇒ For details, refer to Instruction Manual (E6581341) specified in Section 6.41. 6.35.3 Calibration of analog outputs : FM voltage/current output switching : FM output gradient characteristic and bias adjustment : AM output gradient characteristic and bias adjustment •Function Output signals from FM/AM terminals are analog voltage signals.
  • Page 179: Operation Panel Parameter

    E6581301 6.36 Operation panel parameter 6.36.1 Prohibition of key operations and parameter settings : Parameter write protect selection : Operation panel frequency setting prohibition selection : Operation panel emergency stop operation prohibition selection : Operation panel reset operation prohibition selection : Prohibition of change of during operation : All key operation prohibition...
  • Page 180: Displaying The Rotational Speed Of The Motor Or The Line Speed

    E6581301 6.36.2 Displaying the rotational speed of the motor or the line speed : Frequency free unit display magnification : Frequency free unit conversion selection : Free unit display gradient characteristic : Free unit display bias • Function The frequency or any other item displayed on the monitor can be converted freely into the rotational speed of the motor, the operating speed of the load, and so on.
  • Page 181: Changing The Steps In Which The Value Displayed Changes

    E6581301 An example of setting: When , and Panel indication Panel indication 1000 80(Hz) 80(Hz) Output frequency Output frequency Panel indication Output frequency 80 (Hz) 6.36.3 Changing the steps in which the value displayed changes : Changing step selection 1 (pressing a panel key once) : Change step selection 2 (panel display) •...
  • Page 182: Canceling The Operation Command

    E6581301 6.36.4 Changing the standard monitor display : Standard monitor display selection : Status monitor 1~8 display selection These parameters are used to select the item to be displayed when the power turned on and also to change items displayed in status monitor mode. ⇒...
  • Page 183: Tracing Functions

    E6581301 6.36.8 Torque-related parameters for panel operation : Operation panel tension torque bias : Operation panel load sharing gain These parameters are used to specify the torque bias and how to share the load. ⇒ For details, refer to Instruction Manual (E6581331) specified in Section 6.41. 6.37 Tracing functions : Trace selection...
  • Page 184 E6581301 1) To acquire trace data at the occurrence of tripping: (Examples of current waveforms output) Trip Current waveforms output Failure FL signal :Trace data Trace data 1 2) To acquire trace data at the time of triggering: Trigger input Trace data 1 Ex.) When using the RR/S4 terminal as the tracing back trigger signal terminal Title...
  • Page 185 FE63 My function monitor 4 Acquisition of trace data Trace data is acquired through a communication device. The VF-AS1 supports the communication standards and protocols listed below. (Built-in option) • RS485 (MODBUS-RTU) …TOSHIBA protocol • USB…TOSHIBA protocol • CC-Link • PROFIBUS •...
  • Page 186 E6581301 Trace data communication number Communication Minimum setting Function Setting/readout range Default setting /readout unit Trace data 1 pointer (correspond to E100 E000 (For to E199) Trace data 2 pointer (correspond to E200 E001 (For to E299) Trace data 3 pointer (correspond to E300 E002 (For...
  • Page 187: Communication Function

    E6581301 6.38 Communication function 6.38.1 2-wire RS485/4-wire RS485 : Baud rate (2-wire RS485) : Parity (common to 2-wire RS485 and 4-wire RS485) : Inverter number (common) : Communications time-out time (common to 2-wire RS485 and 4-wire RS485) : Communications time-out action (common to 2-wire RS485 and 4-wire RS485) : Send waiting time (2-wire RS485) : Master/slave setting for Inverter-to-inverter communications (common to 2-wire RS485)
  • Page 188 :Slave (trips for emergency stop if communications something goes wrong with the (common to 2-wire RS485) master) :Master (sends a frequency command) :Master (sends an output frequency) :Master (sends a torque command) :Master (sends an output torque command) Protocol selection (2-wire RS485) :TOSHIBA, :MODBUS F-76...
  • Page 189 E6581301 Title Function Adjustment range Default setting :Disabled :2-wire RS485 Frequency point selection :4-wire RS485 :Communication add option Point 1 setting Point 1 frequency Point 2 setting Inverter with a model number ending with Point 2 frequency -WN: -WP: :Deselect :Command information 1 :Command information 2 Block write data 1...
  • Page 190: Host Computer

    E6581301 2) 4-wire RS485 The 4-wire RS485 device included as standard equipment, allows you to connect the inverter to a higher-level system (host) and to set up a network for data communications between inverters. It makes it possible for the inverter to be linked to a computer and to carry out data communications with other inverters.
  • Page 191 E6581301 <Broadcast> When an operation frequency command is broadcasted from the host computer to inverters : Wiring Host computer : Data (host → INV) No.00 No.01 No.02 No.03 No.29 No.30 : Use the terminal board to branch the cable. (1) Data is sent from the host computer. (2) Data from the computer is received at each inverter and the inverter numbers are checked.
  • Page 192 :Master (sends a frequency command) :Master (sends an output frequency) :Master (sends a torque command) :Master (sends an output torque command) :TOSHIBA Protocol selection (4-wire RS485) :MODBUS :Deselect :Command information 1 :Command information 2 Block write data 1 :Frequency command...
  • Page 193: Open Network Option

    E6581301 Title Function Adjustment range Default setting :Deselect :Status information :Output frequency :Output current :Output voltage :Alarm information :PID feedback value :Input terminal board monitor :Output terminal board monitor :VI/II terminal board monitor Block read data 1 :RR/S4 terminal board monitor :RX terminal board monitor :Input voltage (DC detection) :Speed feedback frequency...
  • Page 194: Traverse Function

    E6581301 6.40 Traverse function : Traverse selection : Traverse step : Traverse acceleration time : Traverse jump step : Traverse deceleration time ⇒ For details, refer to Instruction Manual (E6581337) specified in Section 6.41. Instruction manuals for optionally available devices and special functions 6.41 For details, refer to the instruction manual for each optional device or function.
  • Page 195: Operation With External Signal

    E6581301 7. Operation with external signal External operation The inverter can be freely controlled externally. Parameters must be differently set depending on the operation method. Make sure of the operation method before setting parameters, and set parameters properly to the operation mode according to the procedure mentioned below. [Steps in setting parameters] Check of external signal conditions Operation signal:...
  • Page 196 E6581301 Applied operation with input and output signals (operation by terminal board) 7.2.1 Functions of input terminals (in case of sink logic) Use the above parameters to send signals from an external programmable controller to various control input terminals to operate and/or set the inverter. The desired contact input terminal functions can be selected from 120 types.
  • Page 197 E6581301 3) Connection with transistor output Inverter Programmable controller Input terminal The inverter can be controlled by connecting the input terminal with output (contactless switch) of a programmable controller. Use this function to specify forward/reverse run or a preset speed operation. Use a transistor that operates on 24Vdc, 5mA power.
  • Page 198 E6581301 Table of setting of contact input terminal function Parameter setting Parameter setting Function Function Positive Negative Positive Negative logic logic logic logic • @ • @ No function is assigned • @ Servo lock signal • @ • @ F: Forward run command •...
  • Page 199: Functions Of Output Terminals (Incase Of Sink Logic)

    E6581301 Sink logic/source logic Switching between sink logic and source logic (input/output terminal logic) is possible. ⇒ For details, refer to the Section 2.3.2. 7.2.2 Functions of output terminals (incase of sink logic) Use the above parameters to send various signals from the inverter to external equipment. By setting parameters for the OUT1, OUT2 and FL (FLA, FLB and FLC) terminals on the terminal board, you can use 0~255 functions and functions obtained by combining them.
  • Page 200 E6581301 Output terminal function (open collector, relay outputs) setting and detection levels For the open connector output terminals (OUT1, OUT2) and the relay output terminals (FLA, FLB and FLC), functions can be selected from 120 functions (functions 0 to 255). The selectable functions and detection levels are listed in the table below.
  • Page 201 E6581301 Parameter setting Function Operation output specifications (in case of positive logic) Positive Negative logic logic ON:The state that torque component is Over-torque detection value or larger continued more than set value. ON:A certain rate of braking resister overload trip ( Braking resistor detection time is over.
  • Page 202 E6581301 Parameter setting Function Operation output specifications (in case of positive logic) Positive Negative logic logic Specified data output Specified data output Specified data output Specified data output Output of the designated data in 7-bit. Specified data output Specified data output Specified data output Light load output ON:Load is equal to...
  • Page 203: Setup Of Input Terminal Operation Time

    E6581301 7.2.3 Setup of input terminal operation time •Function The input/output terminal operation time setup function is used to extend response time if there is something malfunctioning because of noise or chattering of input relay. Setup of response time Title Function Adjustment range Default setting...
  • Page 204: Setup Of External Speed Command (Analog Signal)

    E6581301 Setup of external speed command (analog signal) Function of analog input terminals can be selected from four functions (external potentiometer, 0 to 10Vdc, 4 (0) to 20mAdc, -10 to +10Vdc). The selective function of analog input terminals gives system design flexibility. ⇒...
  • Page 205: Setup By Analog Input Signals (Rr/S4 Terminal)

    *1: Inverter with a model number ending with -WN: 60.0 -WP: 50.0 ■Run/stop setup To control switching between forward run CHARGE MCCB Motor (F) and reverse run (R), and stop by U/T1 R/L1 VF-AS1 Power external commands. V/T2 S/L2 supply • ¡ Setup of frequency setting signal and W/T3 T/L3...
  • Page 206: Setup By Analog Input Signals (Vi/Ii Terminal)

    *1: Inverter with a model number ending with -WN: 60.0 -WP: 50.0 ■Run/stop setup To control switching between forward run CHARGE MCCB Motor (F) and reverse run (R), run and stop by U/T1 R/L1 VF-AS1 Power external commands. V/T2 S/L2 supply • ¡ Setup of frequency setting signal and W/T3 T/L3...
  • Page 207: Setup By Analog Input Signals (Rx Terminal)

    *1: Inverter with a model number ending with -WN: 60.0 -WP: 50.0 ■Run/stop setup CHARGE Run/stop operation by means of external MCCB Motor commands. U/T1 VF-AS1 R/L1 Power • ¡ Setup of frequency setting signal and V/T2 S/L2 supply W/T3...
  • Page 209: Monitoring The Operation Status

    E6581301 8. Monitoring the operation status Screen composition in the status monitor mode The status monitor mode is used to monitor the operation status of the inverter. ⇒ For modes available and instructions about how to switch them, refer to section 3.1. Here is the screen composition in the status monitor mode.
  • Page 210: Monitoring The Status

    E6581301 Monitoring the status 8.2.1 Status monitor under normal conditions In this mode, you can monitor the operation status of the inverter. twice To monitor the inverter when it is normally running, press the • @ • @ • @ and the current status is indicated MODE on the LED display.
  • Page 211 E6581301 (Continued) Commun ication Item displayed Description operated display [Note 5] FE10 Past trip 1 Past trip 1 (displayed alternately at 0.5-sec. intervals) [Note 5] FE11 Past trip 2 Past trip 2 (displayed alternately at 0.5-sec. intervals) [Note 5] FE12 Past trip 3 Past trip 3 (displayed alternately at 0.5-sec.
  • Page 212 E6581301 Input terminal information Data bit of communication No. F E 06 Input terminal 1 (F) : F111 : 0 Input terminal 2 (R) : F112 : 1 When there is signal input Input terminal 3 (ST) : F113 : 2 Input terminal 4 (RES) : F 114 : 3 When there is no signal input...
  • Page 213: Display Of Detailed Information On A Past Trip

    E6581301 8.2.2 Display of detailed information on a past trip Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the • @ • @ • @ key when the trip record is selected in the status monitor mode.
  • Page 214: Changing Status Monitor Function

    E6581301 Changing status monitor function Changing the display format while power is on The item displayed in the standard monitor mode (*1 on the left side of table on page H-2), for example, operation frequency which is displayed by default in this way: “= ”...
  • Page 215 E6581301 [Setup values of monitor indication parameters ( Communication Default Unit Item displayed Marking Unit (Panel) setting (Communication) FD00 Output frequency Depends on 0.01Hz FE02 Frequency command value Depends on 0.01Hz FE03 Output current 1% or 0.01% FE04 Input voltage (DC detection) 1% or 0.01% FE05...
  • Page 216: Display Of Trip Information

    E6581301 Display of trip information 8.4.1 Trip code display If the inverter trips, an error code is displayed to suggest the cause. In the status monitor mode, the status when the inverter trip is held. Display of trip information Communication/Error code Error code Description Communication No.:FC90...
  • Page 217 E6581301 (Continued) Communication/Error code Error code Description Communication No.:FC90 Speed error (Over speed) Analog input disconnection Abnormal CPU2 communication V/f control error CPU1 fault Abnormal logic input voltage Add-on option 1 error Add-on option 2 error Stop position retaining error CPU2 fault Step-out (for PM motors only) No error...
  • Page 218: Monitor Display At Tripping

    E6581301 8.4.2 Monitor display at tripping At the occurrence of a trip, the same information as that displayed in the mode described in 8.2.1, “Status monitor under normal conditions,” can be displayed, as shown in the table below, if the inverter is not turned off or reset. To display trip information after turning off or resetting the inverter, follow the steps described in 8.2.2, “Display of detailed information a past trip.”...
  • Page 219 E6581301 (Continued) Commun ication Item displayed Description operated display [Note 7] FE10 Past trip 1 Past trip 1 (displayed alternately at 0.5-sec. intervals) FE11 Past trip 2 Past trip 2 (displayed alternately at 0.5-sec. intervals) [Note 7] FE12 Past trip 3 Past trip 3 (displayed alternately at 0.5-sec.
  • Page 220: Display Of Alarm, Pre-Alarm, Etc

    E6581301 Display of alarm, pre-alarm, etc. When the inverter alarm, pre-alarm, etc. occurred, the contents are displayed. (Some are not displayed.) Listed below ones can be monitored via communication (FC91). Refer to 13.1 for the other alarms. Description Panel indication Overcurrent pre-alarm Inverter overload pre-alarm Motor overload pre-alarm...
  • Page 221: Taking Measures To Satisfy The Ce/Ul/Csa Standards

    Inverters themselves are not subject to approval for CE marking. The CE mark must be put on every final product that includes an inverter(s) and a motor(s). The VF-AS1 series of inverters complies with the EMC directive if an EMC filter recommended by Toshiba is connected to it and wiring is carried out correctly.
  • Page 222: Measures To Satisfy The Emc Directive

    E6581301 9.1.2 Measures to satisfy the EMC directive Concrete measures for EMC directive of CE markings are shown below. Models with a built-in EMC filter (1) 200V class: VFAS1-2004PL~2075PL 400V class: VFAS1-4007PL~4500KPC The above mentioned models install EMC noise filter inside. So the conducted and radiated noise can be reduced, optional EMI noise filters are not needed.
  • Page 223 E6581301 (2) Use shielded power cables and control signal cables for the input and output lines of the inverter. Route the cables and wires so as to minimize their lengths. Keep a distance between the power cable and the control cable and between the input and output wires of the power cable.
  • Page 224 E6581301 When an external EMC filter is added (1) Additional external EMC filters have the further effect of suppressing conduction and radiation noises. Use the recommended EMC noise filter specified in Table 3. This combination of inverter and filter was used when examining the inverter for compliance with the EMC directive.
  • Page 225 E6581301 (Continued) Requirements Length of Transmission noise Transmission noise PWM carrier motor frequency Inverter type EN55011 Class A Group 1 Class B Group 1 connecting Applicable filters Applicable filters cable (kHz) EMF3-4090F EMF3-4090F EMF3-4090F VFAS1-4220PL EMF3-4090F EMF3-4090F EMF3-4090F EMF3-4092G EMF3-4092G EMF3-4092G VFAS1-4300PL EMF3-4092G...
  • Page 226: Emc Filter

    E6581301 [Ex. Countermeasure - inverter wiring] Strip and earth the shielded cable, following the example shown in Fig. Peel off the outer sheath of the cable and fix the shielded part with a metal saddle. Noise cut plate PG feedback signal line (Shielded cabless) Control wiring (Shielded cabless) Relay contact output FLA, FLB, FLC 4-wire RS485 communication line...
  • Page 227: Measures To Be Taken To Satisfy The Low-Voltage Directive

    Type : NF series 9.1.3 Low-voltage directive The low-voltage directive provides for the safety of machines and systems. All Toshiba inverters are CE-marked in accordance with the standard EN 50178 specified by the low-voltage directive, and can therefore be installed in machines or systems and imported without a problem to European countries.
  • Page 228: Caution In Installing The Inverter

    Fig. 4 Measures to be taken to satisfy the UL/CSA standards All VF-AS1 series inverters are certified by UL and CSA, and have nameplates with UL and CSA markings. 9.2.1 Caution in installing the inverter A UL certificate was granted on the assumption that the inverter would be installed in a cabinet. Therefore, install the inverter in a cabinet and if necessary, take measures to maintain the ambient temperature (temperature in the cabinet) within the specified temperature range.
  • Page 229: Caution As To The Protection Of Motors From Overload

    E6581301 Table 5 AIC, Fuse and Wire sizes AIC (A) Fuse class and Voltage Applicable Wire sizes of Inverter model output current (Interrupting current class motor [kW] power circuit (A) *2, *3 capacity) VFAS1-2004PL 2.5 ( AIC 5000A AWG 14 CC 7Amax.
  • Page 231: Selection Of Peripheral Devices

    E6581301 10. Selection of peripheral devices • @ • @ Danger • When using the inverter without the front cover, be sure to place the inverter unit inside a cabinet. If they are used outside the cabinet, it may cause electric shock. Mandatory •...
  • Page 232: Selection Of Wiring Equipment

    VFAS1-4500KPC (*1): Type forms of Toshiba Schneider Electric Ltd. products. (*2): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz. (*3): Choose the MCCB according to the power supply capacity. For comply with UL and CSA standard, use the fuse certified by UL and CSA.
  • Page 233: Installation Of A Magnetic Contactor

    E6581301 10. 2 Installation of a magnetic contactor If using the inverter without installing a magnetic contactor (MC) in the primary circuit, use an MCCB (with a power cutoff device) to open the primary circuit when the inverter protective circuit is activated. If using a braking resistor or braking resistor unit, install a magnetic contactor (MC) or no-fuse breaker with a power cutoff device to the power supply of the inverter, so that the power circuit opens when the failure detection relay (FL) in the inverter or the external overload relay is activated.
  • Page 234: Installation Of An Overload Relay

    When operating multiple motors at a time, be sure to install an overload relay for each individual motor. When using the VF-AS1 inverter to operate a constant-torque motor, such as the Toshiba VF motor, adjust the protection characteristic of the electronic thermal protection unit ( ) to the VF motor use.
  • Page 235: Application And Functions Of Options

    E6581301 10. 4 Application and functions of options Separate type options shown below are prepared for the inverter VF-AS1 (2) DC reactor (200kW models and larger) (3) High attention radio (DCL) noise filter (5) Zero-phase reactor ferrite core type radio...
  • Page 236 Note) Set the carrier frequency to 2.2kHz when sine wave filter is used. Control power supply The VF-AS1 supplies control power from the main circuit power supply in it. The optional (10) backup option backup unit is designed to supply control power in the event the main circuit power supply shuts down.
  • Page 237 E6581301 Selection table of separate-type options Radio noise reduction filter Motor end Motor Applicable Input AC DC reactor Voltage Inverter Braking resistor surge voltage noise High Core motor reactor (DCL) Simple class model (*2, 3) suppression reduction type attenuation [kW] (ACL) (*7) type...
  • Page 239: Table Of Parameters

    11. Table of parameters 1. Basic parameter [1/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during cation Title Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) History function ●/●...
  • Page 240 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) 1. Basic parameter [2/4] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) ● 0:Constant torque characteristics ● 1:Voltage decrease curve 2:Automatic torque boost ●/- 3:Sensorless vector control 1 (speed)
  • Page 241 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) 1. Basic parameter [3/4] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Motor overload protection 0600 10~100% Enabled ●/●...
  • Page 242 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) 1. Basic parameter [4/4] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0: - 1:50 Hz default setting 2:60 Hz default setting 3:Factory default setting 4:Trip cleared...
  • Page 243 2. Extended parameters Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [1] Frequency signal Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) Low-speed signal output 0100 0.0~ 0.1/0.01 Enabled...
  • Page 244 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [3] Terminal function selection Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0110 Always ON function selection 1 0~135 *1 Disabled ●/●...
  • Page 245 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [4] Terminal response time setup Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Input terminal 1 response time 0140 2~200ms Disabled...
  • Page 246 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [5] V/f 5-point setting Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) V/f 5-point setting VF1 0190 0.0~ 0.1/0.01 Disabled ●...
  • Page 247 [6] Speed/torque reference gain/bias setup [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque (Panel/Communi setting running control control control cation) 0212 RR/S4 input point 2 setting 0~100% Enabled ●/●...
  • Page 248 [7] Operation frequency Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0240 Starting frequency setting 0.0~10.0Hz 0.1/0.01 Enabled ●/●...
  • Page 249 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [10] Jump frequency Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0270 Jump frequency 1 0.0~ 0.1/0.01 Enabled ●/●...
  • Page 250 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [12] Tripless intensification setup [2/2] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0303 Retry selection 0:Deselect, 1-10 times Enabled ●/●...
  • Page 251 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [14] Functions for lift [1/2] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0324 Drooping output filter 0.1~200.0 rad/s (Enabled if =3, 4, 7 or 8) 0.1/0.1 100.0...
  • Page 252 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [14] Functions for lift [2/2] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Acceleration/deceleration 0349 0:Deselect, 1:Parameter setting, 2:Terminal input Disabled ●/●...
  • Page 253 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [16] PID control [2/2] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0363 Integral (I) gain 0.01~100.0 0.01/0.01 0.10 Enabled ●/●...
  • Page 254 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [18] Motor constant [2/2] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0401 Slip frequency gain 0~150% Enabled ●/●...
  • Page 255 [19] Torque control [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Disabled 1:VI/II (voltage/current input) Forward speed limit input 0425 2:RR/S4 (potentiometer/voltage input)
  • Page 256 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [20] Torque limit [2/2] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Regenerative braking torque 0443 0.0~249.9%, 250.0:Disabled 0.1/0.01 250.0...
  • Page 257 [21] Adjustment parameters [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0478 Optional AI2 input bias 0~255 Enabled ●/●...
  • Page 258 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [22] Acceleration/deceleration 2 [2/2] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0514 Acceleration time 4 0.1~6000 sec.
  • Page 259 [23] Pattern operation [2/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0.1~6000 (The unit depends on the setting of 0540 Speed 1 operation time 0.1/0.1...
  • Page 260 [23] Pattern operation [3/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Preset speed operation frequency 0570 Ditto Disabled...
  • Page 261 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [24] Protection functions [2/3] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Each time (standard pulse) Selection of short circuit 1:Only one time after power is turned on 0613...
  • Page 262 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [24] Protection functions [3/3] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Deselect 0637 PTC1 thermal selection Disabled ●/●...
  • Page 263 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [26] Meter output Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0671 AM terminal meter adjustment Enabled ●/●...
  • Page 264 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [27] Operation panel parameters [1/3] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Parameter write protect 0700 0:Permit, 1:Prohibit Enabled...
  • Page 265 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [27] Operation panel parameters [2/3] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Operation panel emergency stop 0:Permit 0734 Enabled...
  • Page 266 [27] Operation panel parameters [3/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0757 Quick registration parameter 7 0~999 *1 Disabled ●/●...
  • Page 267 RS485) 3:Master (sends a frequency command) 4:Master (sends an output frequency) 5.Master (sends a torque command) 6.Master (sends an output torque command) Protocol selection (2-wire 0:TOSHIBA 0807 Enabled ●/● ●/● ● ● 6. 38. 1...
  • Page 268 RS485) 3:Master (sends a frequency command) 4:Master (sends an output frequency) 5:Master (sends a torque command) 6:Master (sends an output torque command) Protocol selection (4-wire 0:TOSHIBA 0829 Enabled ●/● ●/● ● ● 6. 38. 1...
  • Page 269 [28] Communication function [3/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Communication option (DeviceNet/ 0845 0000~ 0000 Enabled...
  • Page 270 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [28] Communication function [4/4] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Deselect 1:Status information 2:Output frequency 3:Output current 4:Output voltage 5:Alarm information...
  • Page 271 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [29] My function [1/5] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Input terminal function number 0:Deselect 1:F terminal 2:R terminal...
  • Page 272 [29] My function [2/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:NOP (not operation) 1:ST (move) 2:STN 3:AND (logical product) 4:ANDN...
  • Page 273 Sensorless vector/vector with sensor (●:Effective, -:Ineffective) [29] My function [3/5] Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0915 Input function command 32 Same as Disabled ●/●...
  • Page 274 [29] My function [4/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0948 Input function command 61 Same as Enabled ●/●...
  • Page 275 [29] My function [5/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Deselect 1:VI/II 2:RR/S4 0962 Analog input function target 21 Enabled ●/●...
  • Page 276 [Contents of monitor displays] Sensorless vector/vector with sensor (●: valid, -: invalid) Unit Meter Communi Monitor output Trip Speed Torque Function (Commun output PM control Reference cation No. selection retention control control ication) selection Standard monitor FE00 Trip frequency monitor 0.01Hz when tripped when tripped...
  • Page 277 [Monitor FM/AM/pulse output function selection (1/2)] Sensorless vector/vector with sensor ●: valid, -: invalid) FM/AM/pulse output Monitor output Unit Speed Torque Function (Communicat Trip retention PM control Reference Communicati Communicati control control Option No. Option No. ion) on No. on No. FD00 FE00 Output frequency...
  • Page 278 [Monitor FM/AM/pulse output function selection (2/2)] Sensorless vector/vector with sensor (●: valid, -: invalid) FM/AM/pulse output Monitor output Unit Function (Communicat Trip retention Speed control Torque control PM control Reference Communicati Communicati Option No. Option No. ion) on No. on No. Attached to expansion I/O card 2 CPU FE67 ×...
  • Page 279 [Input terminal function setting (1/2)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Speed Torque Function PM control Reference logic logic control control No function is assigned ●/● ●/● ● ● F: Forward run command ●/● ●/● ● ●...
  • Page 280 [Input terminal function setting (2/2)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Speed Torque Function PM control Reference logic logic control control Servo lock signal ●/● ● ● ● Simple positioning (positioning loop) ●/● ● ● ● Integrating wattmeter display clear ●/●...
  • Page 281 [Output terminal function setting (1/3)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic ●/● ●/● ● ● ●/● ●/● ● ● ●/● ●/● ● ● Acceleration/deceleration completion ●/● ●...
  • Page 282 [Output terminal function setting (2/3)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic Inverter healthy output ●/● ●/● ● ● RS485 communication error ●/● ●/● ● ● Error code output 1 (6-bit output) ●/●...
  • Page 283 [Output terminal function setting 3/3] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic My function output 10 ●/● ●/● ● ● My function output 11 ●/● ●/● ● ●...
  • Page 284 Standard default settings classified by inverter model (capacity) Torque Base Acc/dec boost frequency Allowable Motor Motor Motor time Dynamic Inverter side Motor rated Motor voltage PWM Carrier continuous Motor rated Motor rated constant 1 constant 2 constant 3 braking switching revolutions constant 4 Inverter type...
  • Page 285: Models And Their Standard Specifications

    E6581301 12. Specifications 12.1 Models and their standard specifications 1) Standard specifications (small/medium capacity types) Item Specification Voltage class 200V class Applicable motor (kW) 0.75 3.7/4.0 18.5 Type VFAS1- Form 2004PL 2007PL 2015PL 2022PL 2037PL 2055PL 2075PL 2110PM 2150PM 2185PM 2220PM 2300PM 2370PM 2450PM Output capacity (kVA) Note 1: Output current...
  • Page 286 E6581301 2) Standard specifications (large capacity types) Note 4 Item Specification Voltage class 200V class Applicable motor (kW) Type VFAS1- Form 2550P 2750P Output capacity (kVA) Note 1: Output current Output voltage Three-phase 200V~230V (The maximum output voltage is equal to the input supply voltage.) Overload 150%-1 minute, 165%-2 sec.
  • Page 287 E6581301 4) Common specification Item Specification Control system Sinusoidal PWM control Output voltage adjustment Main circuit voltage feedback control. (Switchable between automatic adjustment/fix/control off) Setting between 0.01 to 500Hz. Default max. frequency is set to 0.01 to 60Hz. Output frequency range Maximum frequency adjustment (30 to 500Hz) Minimum setting steps of 0.01Hz: operation panel input (60Hz base),...
  • Page 288 E6581301 (Continued) Item Specification Stall prevention during operation, overload limit, overload, undervoltage on power source side, DC circuit Alarms undervoltage, setting error, in retry, upper limit, lower limit. Overcurrent, overvoltage, fin overheat, short circuit on the load side, ground fault on the load side, inverter overload, arm overcurrent at starting, overcurrent on the load side at starting, EEPROM error, RAM error, Causes of ROM error, transmission error, (dynamic braking resistor overcurrent/overload), (emergency stop),...
  • Page 289: Inverter Type

    E6581301 12.2 Outside dimensions and mass Outside dimensions and mass Voltage Applicable Dimensions (mm) Approx. Inverter type Drawing class motor (kW) weight (kg) VFAS1-2004PL 0.75 VFAS1-2007PL VFAS1-2015PL VFAS1-2022PL 3.7/4.0 VFAS1-2037PL VFAS1-2055PL VFAS1-2075PL VFAS1-2110PM VFAS1-2150PM 200V 18.5 VFAS1-2185PM VFAS1-2220PM VFAS1-2300PM VFAS1-2370PM VFAS1-2450PM VFAS1-2550P 84 (59)
  • Page 290: Outline Drawing

    E6581301 Outline drawing (Instal l ation di m ension) (Installation dimension) Fig. A Fig. B (Installation dimension) (Installation dimension) Fig. C Fig.D (Installation dimension) (Installation dimension) Fig. E Fig. F...
  • Page 291 E6581301 (Installation dimension) (Installation dimension) Fig. G Fig. H (Installation dimension) (Instal l ation di m ension) Fig. I Fig. J...
  • Page 292 E6581301 (Installation dimension) (Installation dimension) Fig. K Fig. L (Installation dimension) (Installation dimension) Fig. M Fig. N...
  • Page 293 E6581301 Fig. O Fig. P...
  • Page 295: Before Making A Service Call

    E6581301 13. Before making a service call - Trip information and remedies 13.1 Trip causes/warnings and remedies When a problem arises, diagnose it in accordance with the following table. If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table, contact your supplier.
  • Page 296 E6581301 (Continued) Error Description Possible causes Remedies code •The V/f parameter is improperly set. •Check the V/f parameter setting. •The motor is locked up. •Check the load (operated machine). •Low-speed operation is performed •Adjust to the overload that the motor can Motor overload continuously.
  • Page 297 E6581301 (Continued) Error Description Possible causes Remedies code •A data writing error occurs. •Turn off the inverter, then turn it again. If it does not EEPROM error recover from the error, make a service call. Initial read error •Some internal data is corrupted. •Make a service call.
  • Page 298 E6581301 (Continued) Error Description Possible causes Remedies code •Is circuit board (or main •When board has been replaced, input Inverter type circuit/drive circuit board) error replaced? Analog input • Overrated voltage is applied to • Apply voltage within the rated voltage. terminal analog input.
  • Page 299 E6581301 (Continued) Error Problem Possible causes Remedies code •This message is displayed when •Press the STOP key again to clear the trip. pressing the STOP key while an Clear enabling error code is displayed. indication • Input terminal RES signal is ON •Turn off the input terminal RES signal.
  • Page 300: Method Of Resetting Causes Of Trip

    E6581301 [Pre-alarm display] Error Description Possible causes Remedies code Overcurrent pre-alarm Same as (Overcurrent) Same as (Overcurrent) Overvoltage pre-alarm Same as (Overvoltage) Same as (Overvoltage) Achieving PBR operation blink while PBR is operating is not an blink while PBR is operating is not an level error.
  • Page 301: If The Motor Does Not Run While No Trip Message Is Displayed

    E6581301 13.3 If the motor does not run while no trip message is displayed... If the motor does not run while no trip message is displayed, follow these steps to track down the cause. YES : The motor does not run. NO : Is power being Supply the power...
  • Page 302: How To Check Other Troubles

    E6581301 13.4 How to check other troubles The following table provides a listing of other troubles, their possible causes and remedies. Troubles Causes and remedies The motor runs in the wrong •Invert the phases of the output terminals U, V and W. direction.
  • Page 303: Inspection And Maintenance

    E6581301 14. Inspection and maintenance Danger • E The equipment must be inspected every day. If the equipment is not inspected and maintained, errors and malfunctions may not be discovered which could lead to accidents. Mandatory • E Before inspection, perform the following steps. (1) Shut off all input power to the inverter.
  • Page 304: Periodical Inspection

    E6581301 14.2 Periodical inspection Make a periodical inspection at intervals of 3 or 6 months depending on the operating conditions. Danger • E Before inspection, perform the following steps. (1) Shut off all input power to the inverter. (2) Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit. Mandatory (3) Use a tester that can measure DC voltages (800VDC or more), and check that the voltage to the DC main circuits (between PA/+ and PC/-) does not exceed 45V.
  • Page 305: Replacement Of Expendable Parts

    E6581301 Replacement of expendable parts The inverter is composed of a large number of electronic parts including semiconductor devices. The following parts deteriorate with the passage of time because of their composition or physical properties. The use of aged or deteriorated parts leads to degradation in the performance or a breakdown of the inverter.
  • Page 306: Making A Call For Servicing

    14.3 Making a call for servicing For the Toshiba service network, refer to the back cover of this instruction manual. If defective conditions are encountered, please contact the Toshiba service section in charge via your Toshiba dealer. When making a call for servicing, please inform us of the contents of the rating label on the right panel of the inverter, the presence or absence of optional devices, etc., in addition to the details of the failure.
  • Page 307: Warranty

    • E Failure or damage caused by the use of the inverter for any purpose or application other than the intended one 4. All expenses incurred by Toshiba for on-site services shall be charged to the customer, unless a service contract is signed beforehand between the customer and Toshiba, in which case the service contract has priority over this warranty.
  • Page 309: Disposal Of The Inverter

    E6581301 16. Disposal of the inverter   Warning • E For safety's sake, do not dispose of the disused inverter yourself but ask an industrial waste disposal agent (*). If the collection, transport and disposal of industrial waste is done by someone who is not Mandatory licensed for that job, it is a punishable violation of the law.
  • Page 312 200120, The People's Republic of China FAX: +81-(0)3-5444-9268 TEL: +86-(0)21-6841-5666 FAX: +86-(0)21-6841-1161 For further information, please contact your nearest Toshiba Liaison Representative or International Operations - Producer Goods. The data given in this manual are subject to change without notice. 2005-10...

Table of Contents