10.10. Replacing components in WCU (Swedewater)
10.10.1. Replacing or cleaning conductivity meter
Service MTTR 4 - 8 h
Figure 10–67 Conductivity meter
1) Coupling ring
1. Shut down the PCS6000 according to the "PCS6000 Lockout/tagout procedure",
3BHS600000 E22.
2. Empty water circuit of the cooling system according to section 10.5.2, Emptying the
cooling liquid circuit, page 139.
3. Disconnect the electrical connection.