106 Electrical installation
Note: For information of parameter indexes marked in this diagram, see chapter
Parameters in the firmware manual

Terminal sizes

(frames R0...R8): 0.14...1.5 mm
tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)

Notes:

1)
Current [0(4)...20 mA, R
input as selected with parameter 12.15 AI1 unit selection .
2)
Current [0(4)...20 mA, R
input as selected with parameter 12.25AI2 unit selection .
3)
Total load capacity of the auxiliary voltage output+24V (X2:10) = 6.0 W (250 mA
/ 24 V) - User can use this source for either of theI/O connections (DI1... DI2- RO1
or DI3...DI6 - RO2~RO3).
4)
The constant speed are set based on the combination of sources as follows:
Source defined by parameter
28.22
0
1
0
5)
The speed reference ramp is set based on the combination of sources as follows:
DI5
parameter 28.71
0
1
6)
Connected with jumpers at the factory.
7)
Applicable for R0~R2 frames only.
8)
Use shielded twisted-pair cables for digital signals.
9)
Ground the outer shield of the cable 360° under the grounding clamp on the
grounding shelf for the control cables.
2
(all terminals)
< 500 ohm] or voltage [ 0(2)...10 V, R
in
= 100 ohm] or voltage[ 0(2)...10 V, R
in
Source defined by parameter
28.23
0
0
1
Ramp set
Acc/Dec time 1
Acc/Dec time 2
> 200 kohm]
in
> 200 kohm]
in
Constant speed active
Set speed through AI1
Constant frequency 1
Constant frequency 2
Parameters
Scalar control (default)
28.72 time 1
28.73 Freq deceleration time 1
28.74 time 2
28.75 time 2