Figure 4-55 Removing the low temperature component
4.6.3 Securing a Low temperature Component
Place the low temperature component on a concrete platform, and align the
mounting holes with the holes in the concrete platform. Secure the low
temperature component to the concrete platform using four M12 x 60 stainless
steel expansion bolts to a torque of 45 N·m, as shown in
Figure 4-56 Securing a low temperature component
4.7 Installing the Water Cooling Module
4.7.1 Checking the Nitrogen Pressure
Check whether any of the two needle valve bonnets is missing by turns.
●