4.2.2.3 Oil Trap and Inverted Trap

Table 4-13 Refrigerant pipe components
Item
Liquid pipe
Gas pipe
Thermal
insulation
foam
Oil trap
and
inverted
trap
Figure 4-22 Oil trap and inverted trap (unit: mm)
Issue 08 (2021-09-17)
Specifications
L ≤ 60 m: R410A copper pipe; outer diameter of 5/8 inch (15.88
mm); wall thickness of 1.0 mm; operating pressure > 4.5 MPa
60 m < L ≤ 100 m: R410A copper pipe; outer diameter of 3/4 inch
(19.05 mm); wall thickness of 1.0 mm; operating pressure > 4.5
MPa
R410A copper pipe; outer diameter of 7/8 inch; thickness of 1.2
mm; operating pressure ≥ 4.5 MPa
Thickness: ≥ 9.2 mm
When the outdoor unit is installed at a position higher than the
indoor unit, install an oil trap every five to six meters in the
vertical direction along the gas pipe and an inverted trap for the
inlet and outlet of the outdoor unit to ensure system reliability