Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Page 11
Table of contents LD0.RESVMMXU1 Residual voltage (1)........45 LD0.SECRSYN1 Synchrocheck line and bus state....45 LD0.T1PTTR1 Temperature protection values (1)....45 LD0.VMMXU1 Voltage measurement ........45 LD0.VSMSQI1 Sequence of voltage measurement....46 Section 3 DNP3 protocol implementation........47 DNP3 device profile................47 DNP3 implementation table..............49 Section 4 Glossary.................53 REF615 Point List Manual...
Section 1 1MRS756711 D Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
C/2010-06-11 Content updated to correspond to the product version D/2012-05-11 Content updated to correspond to the product version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual...
Section 1 1MRS756711 D Introduction Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Section 2 1MRS756711 D DNP3 data mappings Section 2 DNP3 data mappings Overview This document describes the DNP3 data points and structures available in REF615 Ver.4.0. The data points are unmapped as a default on the DNP3 level. The point lists describe a superset of all DNP3 data available through the standard configurations A, B, C, D, E, F, G, H and I including the optional functionalities.
Section 2 1MRS756711 D DNP3 data mappings IEC 61850 name SA name Description Values .Op.general OPR_OFRQ -Operate 1=Operate LD0.FRPTUF1 Underfrequency .Op.general OPR_UFRQ -Operate 1=Operate LD0.FRPFRC1 Frequency gradient .Op.general OPR_FRG -Operate 1=Operate 2.3.1.26 LD0.FRPFRQ2 Frequency protection (2) Table 29: LD0.FRPFRQ2 Frequency protection (2) IEC 61850 name SA name Description...
Section 2 1MRS756711 D DNP3 data mappings 2.3.1.67 LD0.TRPPTRC2 Global conditioning (2) Table 70: LD0.TRPPTRC2 Global conditioning (2) IEC 61850 name SA name Description Values .Op.general Operate input signal 1=Operate .Tr.general Trip output signal 1=Trip 2.3.1.68 LD0.VMHAI1 PQ - Voltage total harmonic distortion Table 71: LD0.VMHAI1 PQ - Voltage total harmonic distortion IEC 61850 name...
Section 2 1MRS756711 D DNP3 data mappings 2.3.2 Binary outputs Table 81: Explanations of the binary output table columns Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as name Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the same as the application function block name.
Section 2 1MRS756711 D DNP3 data mappings 2.3.2.5 LD0.DARREC1 Autoreclosing reset signals Table 86: LD0.DARREC1 Autoreclosing reset signals IEC 61850 name SA name Description Type LD0.DARREC1 .RsCnt.Oper.ctlVal AR reset all counters .RsRec.Oper.ctlVal AR reset 2.3.2.6 LD0.DNPGGIO1 Parameter setting group control Table 87: LD0.DNPGGIO1 Parameter setting group control IEC 61850 name...
Section 2 1MRS756711 D DNP3 data mappings 2.3.2.9 DR.RDRE1 Disturbance recorder Table 90: DR.RDRE1 Disturbance recorder IEC 61850 name SA name Description Type DR.RDRE1 .MemClr.Oper.ctlVal Clear all records .RcdTrg.Oper.ctlVal Trig recording 2.3.2.10 LD0.SPCGGIO1 Multipurpose binary outputs (1) The binary outputs may be configured either as pulse- or persistent-type outputs. Pulse-type outputs are triggered with the write value "1".
Section 2 1MRS756711 D DNP3 data mappings Table 92: LD0.SPCGGIO2 Multipurpose binary outputs (2) IEC 61850 name SA name Description Type LD0.SPCGGIO2 .SPCS01.ctlVal Output 1 control On/Off .SPCS02.ctlVal Output 2 control On/Off .SPCS03.ctlVal Output 3 control On/Off .SPCS04.ctlVal Output 4 control On/Off .SPCS05.ctlVal Output 5 control...
Section 2 1MRS756711 D DNP3 data mappings 2.3.3.1 CTRL.CBCSWI1 CB 4-pole (2 bit) position value Table 97: CTRL.CBCSWI1 CB 4-pole (2 bit) position value IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.CBCSWI1 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 2.3.3.2...
Section 2 1MRS756711 D DNP3 data mappings 2.3.3.16 CTRL.LLN0 Local remote station off Table 112: CTRL.LLN0 Local remote station off IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.LLN0 Off=0; Loc=1; Rem=2; .LocRem.stVal Station=3 0…3 0,3,0,3 2.3.3.17 LD0.LPHD1 System values Table 113: LD0.LPHD1 System values IEC 61850 name...
Section 2 1MRS756711 D DNP3 data mappings 2.3.3.20 LD0.RESCMMXU1 Residual current (1) Table 116: LD0.RESCMMXU1 Residual current (1) IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.RESCMMXU1 .A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] 0,40,0,4000 2.3.3.21 LD0.RESVMMXU1 Residual voltage (1) Table 117: LD0.RESVMMXU1 Residual voltage (1) IEC 61850 name...
Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 122: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: REF615 Highest DNP level supported: Device function: For requests: Level 2+ ○...
Page 54
Section 3 1MRS756711 D DNP3 protocol implementation DNP3 device profile document ○ Sometimes ● Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages" Timeouts while waiting for: Data link ○ None ○ Fixed at ____ ○...
Section 3 1MRS756711 D DNP3 protocol implementation DNP3 device profile document ○ Configurable ○ When device restarts ○ Only certain objects ○ When status flags change ○ Sometimes (attach explanation) ○ ENABLE/DISABLE UNSOLICITED No other options are permitted. function codes supported Default counter object/variation: Counters roll over at: ●...
Page 56
Section 3 1MRS756711 D DNP3 protocol implementation Table 123: Implementation table OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Object Variation Function codes Qualifier codes number number Description Function codes (dec) Qualifier codes (hex) (dec) (hex) Binary 1 (read) 00, 01 (start-stop) input –...
Page 57
Section 3 1MRS756711 D DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) 16-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 2 (default) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) 32-bit...
Page 58
Section 3 1MRS756711 D DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Time delay 129 (response) 07 (limited qty) fine (qty = 1) Not defined Class 0 1 (read) 06 (no range, or all) data Class 1 1 (read) 06 (no range, or all)
Section 4 1MRS756711 D Glossary Section 4 Glossary 615 series Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment CROB Control relay output block Common time of occurrence. The time and date CTO object is an information object that represents the absolute time of day.
Page 64
Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...