Cable/Terminal/Torque Specifications
Installation should conform to the NEC Article 110
of the Occupational Safety and Health Administration, and any other applicable national, regional, or
industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the H9 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the H9 ASD.
Note:
Cable/Terminal specifications are based on the rated current of the H9 ASD and Do
Not include the 10% Service Factor.
Note:
Use only 75° C copper wire/cable for motor and power connections.
For further installation information see the section titled
Table 11. 230-Volt H9 ASD Cable/Terminal/Torque Specifications.
Model
MCP Rating
Number
(Amps)
VT130H9U
2010
15
2015
2025
2035
30
2055
2080
50
2110
75
2160
100
2220
125
2270
150
2330
175
2400
200
2500
250
2600
300
2750
400
210K
500
212K
Note:
(*) Indicates that the item is one of a set of two parallel cables.
84
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Wire/Cable Size
AWG or kcmil
Wire-Size/Lug-Capacity for
Input/Output Power
Recommended Maximum
14
10
10
8
8
6
4
3
3
2
2
1/0
2/0
4/0
3/0
4/0
*3/0
*1/0
*250
*250
(Requirements for Electrical Installations), all regulations
Installation and Connections on pg.
Lug Size Range
Input/Output Power
3Ø-Input
3Ø-Output
14 to 8
12 to 8
(3-core shield)
8 to 3
Torque to 5.3/0.6
12 to 1/0
4 to 1/0
6 to 250
2 to 300
6 to 250
H9 ASD Installation and Operation Manual
14.
Terminal
Board
Torque
TB1 – 4
3Ø-Input 3Ø-Output
Terminals
In-Lbs./Nm
11.5/1.3
17.7/2.0
20
21/2.4
50/5.7
53/6
275/31
168/19
275/31