SPA-ZC 400 Ethernet Adapter 1MRS756014 Modbus/TCP Brigde Installation and Commissioning Manual 7.1. Interfaces................37 7.2. Test and conditions............38 8. Maintenance and service..........41 8.1. LED indicators..............41 8.2. Communication settings............. 41 8.3. IP Query................43 8.4.
Copyrights The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document. In no event shall ABB Oy be liable for direct, indirect, special, incidental or...
This manual This manual provides thorough information on the SPA-ZC 400 Ethernet Adapter and the central concepts related to it. SPA-ZC 400 Ethernet Adapter is used for connecting REF 541/3/5, REM 543/5 and RET 541/3/5 Intelligent Electronic Devices (IED) to the Modbus/TCP Bridge. In the manual you find information on SPA-ZC 400 and its components, an introduction to engineering tasks and a description of the basic operations.
1MRS756014 Modbus/TCP Brigde Installation and Commissioning Manual 1.4. Product documentation Name of the manual Document ID SPA-ZC 400 configuration CD 1MRS151048 CAP 505 User's Guide 1MRS752292-MUM SPA-ZF Optical glass fibres, multimode 1MRS755371 granded index type Plastic-core fibre-optic cables, Features and...
1MRS756014 Ethernet Adapter SPA-ZC 400 Modbus/TCP Brigde Installation and Commissioning Manual Example: MIF349 Variables are shown using lowercase letters: sequence name 1.6. Revision history Version Date History 30.06.2006 Document created...
1MRS756014 Ethernet Adapter SPA-ZC 400 Modbus/TCP Brigde Installation and Commissioning Manual Safety information Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed.
Modbus/TCP Brigde Installation and Commissioning Manual Product overview SPA-ZC 400 is used to connect one REF 541/3/5, REM 543/5 or RET 541/3/5 device with the Modbus protocol over the TCP/IP network using the same Ethernet link. SPA-ZC400MMP and SPA-ZC400MMG versions provide simultaneous dual port communication for fibre-optic SPA and LON.
Installation and Commissioning Manual Media converters: RuggedCom RMC-100-MM IMC McBasic MM1300 Allied Telesyn AT-MC302-20 More tested devices can be found on the ABB web site (http://www.abb.com/substationautomation). 3.1. SPA-ZC400MMP and SPA-ZC400MMG The optional interface provides a connection between the REF 541/3/5, REM 543/5 or RET 541/3/5 device and the fibre-optic SPA and LON.
Ethernet Adapter SPA-ZC 400 Modbus/TCP Brigde Installation and Commissioning Manual 3.2. Features SPA-ZC 400 has the following features: Simultaneous dual port communication (SPA-ZC400MMP and SPA- ZC400MMG versions) for Modbus and LON/SPA (excluding event polling) Support of Modbus communication over TCP/IP A040138B Fig.
Page 16
SPA-ZC 400 Ethernet Adapter 1MRS756014 Modbus/TCP Brigde Installation and Commissioning Manual A data message sent as a TCP/IP message means that the higher layer Transmission Control Protocol assembles the message or file into smaller packets. These are then transmitted over the Internet and received by a TCP...
Connect the SPA-ZC 400 module to REF 541/3/5, REM 543/5 or RET 541/3/5 and screw SPA-ZC 400 to the 9-pin type D-connectors. Connect the LAN cable to the LAN connector of SPA-ZC 400. The other end of the cable is connected to the Modbus protocol over TCP/IP through the Ethernet switch.
SPA-ZC 400 Ethernet Adapter 1MRS756014 Modbus/TCP Brigde Installation and Commissioning Manual 5. The CET for SPA-ZC 40x Installation program starts. In this dialog, click Next. With the Back button you can return to the previous dialog, and with the Cancel button, exit the installation wizard. This applies to all the dialogs in the installation wizard.
To connect SPA-ZC 400, the used computer and SPA-ZC 400 must use the same address space. To change the computer's IP address space to be the same as in SPA-ZC 400: 1. Open the Network Connections in Control Panel. 2. Type, for example, the following IP address to the IP address box: 192.168.2.1.
Fig. 4.3.1.-1 Changing IP address 4.3.2. Checking connection to SPA-ZC 400 Check the connection to SPA-ZC 400 by using the ping command: 1. Open the Run dialog. 2. Type cmd to the Open box, see Fig. 4.3.2.-1. A060242 Fig. 4.3.2.-1 Starting command prompt 3.
Page 21
Pinging SPA-ZC 400 SPA-ZC 400 responds to the ping command if the computer and SPA-ZC 400 are on the same network. 5. If SPA-ZC 400 responds with the IP address, the connection is established between the computer and SPA-ZC 400.
5.1. Overview of engineering The engineering and maintenance of SPA-ZC 400 is done by using CET for SPA-ZC 40x functions or by importing the existing SPA-ZC 40x CID file. The device's communication structure is described in the Project Explorer dialog.
Creating a new project 5.3. Restarting Use this function to restart the SPA-ZC 400 at runtime. 1. Select IED and Tools > Reset Tool to open the restart pane, see Fig. 5.3.-1 2. Click Reset. The results are reported to the UI text box.
Fig. 5.4.-1 shows an example of the object tree when it has been built. In the example tree you can see the SPA-ZC 400 object and its child objects as devices and data objects. Indentation is used to indicate the parent-child...
Page 26
SPA-ZC 400 Ethernet Adapter 1MRS756014 Modbus/TCP Brigde Installation and Commissioning Manual A051858 Fig. 5.4.-1 Example view of the SPA-ZC 40x Communication Engineering Tool You have several possible ways to add objects to the object tree in the communication structure: You can use the right mouse button (right-click) to select the object to which you want to add a child object.
5.5. Configuring by using imported CID file If you have to configure several SPA-ZC 400 with the similar settings, it is possible to import a previously generated CID file and change the communication addresses, typically by changing the IP address.
Configuring communication parameters SPA-ZC 400 communication parameters are located in the device properties. SPA-ZC 400 uses static IP addresses, which have to be defined in the planned network structure. For uplink network settings, see Sections 5.6.1. Uplink network settings and 5.6.2.
Page 29
SNTP Servers SPA-ZC 400 uses SNTP as its own real-time clock. The time is used to synchronize an IED with Modbus. The secondary SNTP server is used if the primary SNTP server for some reason drops off the network.
The possible communication speed settings of the Modbus bus are: 1200 bps 2400 bps 4800 bps 9600 bps 19200 bps 38400 bps Receive Timeout Receive Timeout defines how long SPA-ZC 400 waits for the slave’s respond before it considers the slave to be non-responding. The unit is milliseconds.
1. Select the SPAZC40x_MODBUS Device object and right-click to select the CID Export. 2. If you download configuration to SPA-ZC 400 the first time, change the IP address from default address (192.168.2.10) to new IP address according to the planned network structure.
Page 32
Fig. 5.7.-1 Downloading the device's configuration If SPA-ZC 400 is connected to a system where the connection to it can be obtained, the Export function tries to determine the SPA-ZC 400 version and exports the export file accordingly. If the connection is disabled, prompt the correct version to be exported, see Fig.
Page 33
1MRS756014 Ethernet Adapter SPA-ZC 400 Modbus/TCP Brigde Installation and Commissioning Manual You can export a configuration in CID format from CID Export tool to hard drive. This SCL is usually used by System Configuration tool. It is possible to export a dataset in SCL files in different levels. If you select to export a dataset in FCD level, for example an information report from SPA-ZC 40x contains always value quality and time in one structure.
LEDs. When the SPA-ZC 400 configuration is completed, the green LED is If the configuration fails, check the error log files from the SPA-ZC 400 file system. The status and error logs are located in the /log directory. For more information about maintenance, refer to Chapter 8.
Installation and Commissioning Manual Technical data 7.1. Interfaces SPA-ZC 400 - IED interfaces Fixed mechanics and fixed connectors for REF 541/3/5, REM 543/5 and RET 541/3/5 protection relays D-type subminiature connector for simultaneous dual port communication (optional, see Table 3.1.-1).
MODBUS / TCP SPA / TCP 00-0C-02-B0-CC-00 POWER LINK DIAG SERVICE ETHERNET A040130B Fig. 7.1.-1 Dimensions of the SPA-ZC 400 module Table 7.1.-1 Dimensions and weight Type Dimensions [mm] Weight [g] SPA-ZC 400 195 x 50 x 26 7.2. Test and conditions...
Page 39
1MRS756014 Ethernet Adapter SPA-ZC 400 Modbus/TCP Brigde Installation and Commissioning Manual Table 7.2.- 1 Envi ronmen tal test and cond itions Recommended service temperature -10...+55˚C range (continuous) Transport and storage temperature -40...+70˚C according to the IEC 60068-2- range Dry heat test...
Page 40
SPA-ZC 400 Ethernet Adapter 1MRS756014 Modbus/TCP Brigde Installation and Commissioning Manual Table 7.2.-4 Standard tests Supply current consumption Running 340 mA Start up 430 mA...
Modbus/TCP Brigde Installation and Commissioning Manual Maintenance and service If the SPA-ZC 400 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. For more details, refer to Table 9.-1.
Page 42
Installation and Commissioning Manual The following IED-specific settings have to be checked when setting up REF 541/3/5, REM 543/5 or RET 541/3/5: Protocol selection for SPA-ZC 400 Table 8.2.-1 explains the possible port configurations of REF 541/3/5, REM 543/5 or RET 541/3/5.
SPA command timeout should be < 1 second when LON interlocking is not in use. SPA baud rate and SPA slave number in IED Baud rate and slave number have to be according to the SPA-ZC 400 configuration in X3.2/Communication 2. 8.3.
Identification If contacting the Customer Service, it is necessary to send the following information by request: Version information of Communication Engineering Tool (CET) for SPA- ZC 40x Select Help > About to view the version information. SPA-ZC 400 version information...
1MRS756014 Ethernet Adapter SPA-ZC 400 Modbus/TCP Brigde Installation and Commissioning Manual The version information can be read from the device's label. If the device is updated afterwards, use CET's IP query to get the correct version information from the device memory. For more information about IP query, refer to Section 8.3.
SPA-ZC 400 configuration CD Engineering tool, Communication Engineering Tool (CET) for SPA-ZC 40x Order at least one SPA-ZC 400 configuration CD with your delivery to get the Communication Engineering Tool. The SPA-ZC 400 package does not include the configuration CD by default.
Intelligent Electronic Device Also known as IED. Devices containing advanced logics such as meters, protection and control relays and trip units. Modbus By extension, communication board implementing the Modbus protocol for REF542plus. Data communication protocol developed by ABB Connector type for glass fibre cable...
IED Capability Description Intelligent Electronic Device Internet Protocol Local Area Network Logical Device Light-Emitting Diode Logical Node Local Operating Network SNTP Simple Network Time Protocol Data communication protocol developed by ABB</ para> Structured Query Language Transmission Control Protocol Universal Time Clock...
Page 56
ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa FINLAND +358 10 2211 +358 10 224 1080 www.abb.com/substationautomation...