GRD110 FEATURES APPLICATION Overcurrent protection for phase and earth The GRD110 is a range of fully numeric multi-function faults with IDMTL or DTL. protection relays. GRD110 has five models which differ according to the number and type of current Three instantaneous elements with DTL.
Page 3
GRD110 Table 2 - GRD110 Features GRD110 - Model Number Phase Fault O/C (50/51P) Earth Fault O/C (50/51N) SEF (50/51N) Phase Undercurrent (37P) Thermal Overload (49) NPS Overcurrent (46) Broken Conductor Circuit Breaker Fail (50BF) Inrush current detector Cold Load Protection...
Inrush Current Detector GRD110-500 and -520 provides an inrush current detector against magnetizing inrush currents during transformer energisation. The inrush current detector detects the ratio between second harmonic current and fundamental current.
This feature is not available in GRD110-110. which can be stored is dependent on the recording The operating time monitor records the time time chosen.
Each of the programmable binary GRD110 can be connected to the RSM system via the outputs is driven via a logic gate which can be rear mounted serial communications port, using either programmed for OR gate or AND gate operation.
Page 10
GRD110 PC DISPLAY Setting Event record Metering Data analysis Fault record Figure 5 - Relay Setting and Monitoring System - PC Displays...
GRD110 TECHNICAL DATA Ratings AC current I 1A or 5A Frequency: 50Hz or 60Hz DC auxiliary supply: 110/125Vdc (Operative range: 88 - 150Vdc) 220/250Vdc (Operative range: 176 - 300Vdc) 48/54/60Vdc (Operative range: 38.4 - 72Vdc) Superimposed AC ripple on DC supply:...
Page 12
GRD110 Earth Fault Protection E/F 1 Overcurrent threshold: OFF, 0.02 – 5.00A in 0.01A steps (1A rating) OFF, 0.1 – 25.0A in 0.1A steps (5A rating) Delay type: DTL, IEC NI, IEC VI, IEC EI, UK LTI, IEEE MI, IEEE VI, IEEE EI, US CO8 I, US CO2 STI, user configurable IDMTL Time Multiplier Setting TMS: 0.010 - 1.500 in 0.001 steps...
Page 13
GRD110 Autoreclose ARC Reclaim Time 0.0 - 600.0s in 0.1s steps Close Pulse Width 0.01 - 10.00s in 0.01s steps Lock-out Recovery Time OFF, 0.1 - 600.0s in 0.1s steps Sequences 1 - 5 Shots to Lock-out, each trip programmable for inst or...
GRD110 ENVIRONMENTAL PERFORMANCE Test Standards Details Atmospheric Environment Temperature IEC60068-2-1/2 Operating range: -10 C to +55 C. Storage / Transit: -25 C to +70 C. Humidity IEC60068-2-78 56 days at 40 C and 93% relative humidity. Enclosure Protection IEC60529 IP51 (Rear: IP20)
Page 19
15.6 185.2 Side view Front view 4 holes- 5.5 4 holes- 4.5 Rear view Panel cut-out TB1,TB2,TB3: Screw terminal (M3.5 Ring) TB4: Screw terminal TB4 is provided only for dual RS485 model. Terminal block Figure 9 - GRD110 Outline Diagram...
Page 20
Power Systems Company 1-1,SHIBAURA 1-CHOME,MINATO-KU, TOKYO 105-8001,JAPAN PHONE;+81-3-3457-3644 FAX;+81-3-5444-9168 http://www.toshiba-relays.com...