Page 1
R410A INDOOR UNIT 1. MULTI TYPE : 3-4ROOMS TYPE ASU9RMLQ AUU9RML ASU12RMLQ AUU12RML ASU18RMLQ AUU18RML ARU9RML ARU12RML ARU18RML D2D_MU016E/04 2009.05.07...
Page 2
1. FEATURE 1-1. MODEL INDOOR UNIT ASU9RMLQ AUU9RML ARU12RML ARU9RML ASU12RMLQ AUU12RML ARU18RML ASU18RMLQ AUU18RML Concealed Ceiling Concealed Ceiling Wall Mounted Type Cassette Type type (small) type (Compact) OUTDOOR UNIT AOU36RML1 - (01 - 01) -...
Page 3
INDOOR UNIT CONNECTION PATTERNS MODEL : AOU36RML1 When 3 and 4 indoor units are connected ( Btu/h ) CONNECTION PATTERN NO.1 NO.2 NO.3 NO.4 Indoor unit Indoor unit Indoor unit Indoor unit 9,000 9,000 9,000 9,000 9,000 12,000 9,000 12,000 12,000 12,000 12,000...
1-2. SELECT FUNCTION WALL MOUNTED TYPE Auto restart When the air conditioner power was temporarily turned off by a power failure etc. It restarts automatically after the power recovers. (Operated by setting before the power failure.) Clean room conditioning is realized by equipping the plasma air cleaner Plasma air cleaner quickly removes small dust particles and odors.
2. REMOTE CONTROLLER 2-1. WIRELESS REMOTE CONTROLLER (FOR WALL MOUNTED TYPE) Wireless remote controller is an accessory of all indoor units. FEATURES Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. Four kinds of timers. Easy operation. Can be used jointly with Wired remote controllers.
Page 6
FUNCTIONS MASTER CONTROL button SET TEMP. buttons( Signal Transmitter TIMER MODE button FAN CONTROL button START/STOP button AIR CLEAN button AIR FLOW DIRECTION SET button AIR FLOW DIRECTION SWING button RESET button CLOCK ADJUST button TEST RUN button Perform a test run only when installing the air conditioner .If the signal to perform a test run is received during normal operation, the air conditioner's thermostat will malfunction.
2-2. WIRED REMOTE CONTROLLER (FOR CONCEALED CEILING TYPE and OPTIONAL PART FOR WALL MOUNTED TYPE) FEATURES Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function. SU MO TU WE TH FR SA (2 times Start / Stop per day for a week) 15 18 21 When setting up a timer, operation mode and a temperature...
Page 8
FUNCTIONS START/STOP button Pressed to start and stop operation. Set Temperature button Display Selects the setting temperature. SU MO TU WE TH FR SA Master control button Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY). 3 6 9 12 15 18 21 Fan control button Selects the fan speed (AUTO, LOW, MED, HIGH).
Page 9
2-3. WIRED REMOTE CONTROLLER (FOR CASSETTE TYPE) FEATURES Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function. (2 times Start / Stop per day for a week) When setting up a timer, operation mode and a temperature setup can be changed.
Page 10
FUNCTIONS START/STOP button Pressed to start and stop operation. Set temperature button Selects the setting temperature. Master control button Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY). Fan control button Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH). Economy button Turns the economy efficient mode on and off.
2-4. WIRELESS REMOTE CONTROLLER (OPTIONAL PART FOR CASSETTE TYPE) FEATURES Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. Four kinds of timers. Easy operation. Easy to change transmission code (4 patterns) by button operation. Simple function setting Setting of the air conditioner selection function is performed by remote controller.
Page 12
FUNCTIONS MODE button Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). /Start / end R.C. custom code change. (Max 4 types) Economy button Set temp. button ( Set remote controller custom code buttons Sets the indoor temp./ Sets R.C. custom code. Filter reset button Sleep button Pressed to select sleep timer.
3. SPECIFICATIONS 3-1. WALL MOUNTED TYPE WALL MOUNTED MODELS TYPE INVERTER HEAT PUMP TYPE MODEL NAME ASU9RMLQ ASU12RMLQ ASU18RMLQ POWER SOURCE 230/208V ~ 60Hz AVAILABLE VOLTAGE RANGE 187-253V ~ 60Hz 2.80 3.50 5.20 RATED BTU/h 9500 12000 17800 COOLING 1.50-3.30 1.50-4.00...
Page 14
3-2. CONCEALED CEILING TYPE CONCEALED CEILING MODELS TYPE INVERTER HEAT PUMP TYPE MODEL NAME ARU9RML ARU12RML ARU18RML POWER SOURCE 230/208V ~ 60Hz AVAILABLE VOLTAGE RANGE 187-253V ~ 60Hz 2.80 3.50 5.20 RATED BTU/h 9500 12000 17800 COOLING 1.50-3.30 1.50-4.00 1.80-5.60 MIN.-MAX.
3-3. CASSETTE TYPE CASSETTE MODELS TYPE INVERTER HEAT PUMP TYPE Model name AUU9RML AUU12RML AUU18RML Power source 230 / 208V ~ 60Hz Available voltage range 187-253V ~ 60Hz 2.60 3.50 5.20 RATED BTU/h 8800 12000 17800 COOLING 1.5-3.3 1.5-4.0 1.8-5.6 MIN.
4. DIMENSIONS 4-1. WALL MOUNTED TYPE MODEL : ASU9R, ASU12R, ASU18R [Unit : Inch (mm)] 31-3/32 9-1/16 (790) (230) Front view Side view 14-7/8 16-7/32 (378) (412) 6-3/16 x 3/4 (hole) Wall hook 9-31/32 9-7/16 (5 x 19 (hole)) 60-ø3/16 (5) (hole) brackel (253) (240)
Page 17
4-2. CONCEALED CEILING TYPE MODEL : ARU9R [Unit : Inch (mm)] View A Rear view Bolt Pitch Outlet 5-5/16 (135) 5-5/16 (135) 4-23/32 (120) 4-23/32 (120) 4-23/32 (120) 13/64 22-5/64 (560) Side view (R) (ø5 hole) Top view Front view Bottom view Refrigerant pipe flare connection (Liquid) Refrigerant pipe flare connection (Gas)
Page 18
BRACKETS BRACKETS CONTROL BOX AIR FLOW OUTLET [Unit : Inch (mm)] Strong and durable ceiling Indoor Unit Left Right side side [Unit : Inch (mm)] Unit Control box Maintenance hole - (01 - 17) -...
Page 19
MODEL : ARU12R, ARU18R [Unit : Inch (mm)] Rear view View A Bolt Pitch 25/64 (10) Outlet 2-63/64 (76) 6-9/64 (156) 6-9/64 (156) 6-9/64 (156) 5-29/32 (150) 5-33/64 (140) 5-33/64 (140) 5-33/64 (140) 5-33/64 (140) Side view (R) Top view Front view Bottom view Refrigerant pipe flare connection (Liquid)
Page 20
BRACKETS BRACKETS AIR FLOW OUTLET CONTROL BOX [Unit : Inch (mm)] Strong and durable ceiling Indoor Unit Left Right side side [Unit : Inch (mm)] Unit Control box Maintenance hole - (01 - 19) -...
INSTALLATION PLACE [Unit : Inch (mm)] Strong and durable ceiling 47-1/4 (1,200) 39-3/8 (1,000) or more 94-1/2 (2,400)~106-1/4 (2,700) or more Obstruction Floor 3-WAY DIRECTIONS SETTINGS [Unit : Inch (mm)] 4 (100) or more To set “3-way directions”, the air outlet shutter plate (UTR-YDZB) sold separately must be installed and “outlet-direction”...
Page 23
MAINTENANCE SPACE [Unit : Inch (mm)] Control box Maintenance space 18 (450) or more Be sure to leave the maintenance space follow as above sketch area for future service. - (01 - 22) -...
Page 24
5. WIRING DIAGRAMS 5-1. WALL MOUNTED TYPE MODEL : ASU9R, ASU12R, ASU18R TO OUTDOOR UNIT - (01 - 23) -...
Page 25
5-2. CONCEALED CEILING TYPE MODEL : ARU9R, ARU12R, ARU18R - (01 - 24) -...
Page 26
5-3. CASSETTE TYPE MODEL : AUU9R, AUU12R, AUU18R - (01 - 25) -...
7-2. AIR VELOCITY DISTRIBUTION 7-2-1. WALL MOUNTED TYPE MODEL : ASU9R (ft.) Unit : ft./s(m/s) 6.56 TOP VIEW Note : VERTICAL FLAP : Upward Condition HORIZONTAL FLAP : Center 3.28 Fan speed : High Operation mode :FAN 6.6(2.0) 3.3(1.0) 1.6(0.5) 3.28 6.56 5 (m)
Page 43
MODEL : ASU12R (ft.) Unit : ft./s(m/s) 6.56 TOP VIEW Note : VERTICAL FLAP : Upward Condition HORIZONTAL FLAP : Center 3.28 Fan speed : High Operation mode :FAN 6.6(2.0) 3.3(1.0) 1.6(0.5) 3.28 6.56 5 (m) 3.28 6.56 9.84 13.1 16.4 (ft.) (ft.) Unit : ft./s(m/s)
Page 44
MODEL : ASU18R (ft.) Unit : ft./s(m/s) 6.56 TOP VIEW Note : VERTICAL FLAP : Upward Condition HORIZONTAL FLAP : Center 3.28 Fan speed : High Operation mode :FAN 6.6(2.0) 3.3(1.0) 1.6(0.5) 3.28 6.56 5 (m) 3.28 6.56 9.84 13.1 16.4 (ft.) (ft.) Unit : ft./s(m/s)
Page 45
7-2-2. CASSETTE TYPE MODEL : AUU9R HEATING AIR VELOCITY DISTRIBUTION Note : Reference data Condition Fan speed : High Ceiling height Vertical flap : Downward (4WAY) Operation mode : Heating (ft.) 8.86 8.20 6.6ft/s (2.0m/s) 6.56 4.9ft/s (1.5m/s) 3.3ft/s (1.0m/s) 1.6ft/s (0.5m/s) 0.8ft/s (0.25m/s) 3.28...
Page 46
MODEL : AUU12R HEATING AIR VELOCITY DISTRIBUTION Note : Reference data Condition Fan speed : High Ceiling height Vertical flap : Downward (4WAY) Operation mode : Heating (ft.) 8.86 8.20 6.56 4.9ft/s (1.5m/s) 3.3ft/s (1.0m/s) 1.6ft/s (0.5m/s) 3.28 0.8ft/s (0.25m/s) Distance 3.28 6.56...
Page 47
MODEL : AUU18R HEATING AIR VELOCITY DISTRIBUTION Note : Reference data Condition Fan speed : High Ceiling height Vertical flap : Downward (4WAY) Operation mode : Heating (ft.) 8.86 8.20 6.6ft/s (2.0m/s) 6.56 4.9ft/s (1.5m/s) 3.3t/s (1.0m/s) 1.6ft/s (0.5m/s) 3.28 0.8ft/s (0.25m/s) Distance 3.28...
Page 48
7-3. AIR FLOW 7-3-1. WALL MOUNTED TYPE MODEL : ASU9R, ASU12R, ASU18R Number of Model Fan speed rotations Air flow (r.p.m) HIGH 1200 1070 ASU9R QUIET HIGH 1380 1230 Indoor unit ASU12R 1050 QUIET HIGH 1480 1380 ASU18R 1200 QUIET 1060 *The values in this table are values when the operation mode is "FAN".
Page 49
7-3-2. CASSETTE TYPE MODEL : AUU9R COOLING Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET HEATING Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 48) -...
Page 50
MODEL : AUU12R COOLING Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET HEATING Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 49) -...
Page 51
MODEL : AUU18R COOLING Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET HEATING Number of Fan speed rotations Airflow (r.p.m) HIGH QUIET - (01 - 50) -...
9. ELECTRIC CHARACTERISTICS 9-1. WALL MOUNTED TYPE Model name ASU9R ASU12R ASU18R 230 / 208 ~ Voltage Power supply Frequency Max. operating current ( Indoor unit ) 0.20 / 0.20 0.25 / 0.25 0.30 / 0.30 Connection cable Wiring spec. (Indoor unit to outdoor unit ) Limited wiring length 9-2.
10. SAFETY DEVICES Model Protection ASU9R ARU9R AUU9R form ASU12R ARU12R AUU12R ASU18R ARU18R AUU18R Current fuse 3.15A 250V 3.15A 250V 3.15A 250V (PCB) Circuit protection ±4 ±2 Thermal fuse °F OFF °C OFF ±9 ±5 (Terminal) °F ON °C ON ±9 ±5 ±36...
11. OPTIONAL PARTS Exterior Parts name Model No. Summary For wall mounted type The optional wired remote control unit can Wired remote be used. When you use remote control unit , UTB-UUB control unit there are following different points as compared with using wireless remote control unit.
R410A OUTDOOR UNIT 2. MULTI TYPE : 3-4ROOMS TYPE AOU36RML1 D2D_AO016E/03 2009.04.24...
Page 67
1. SPECIFICATIONS 1-1. COMBINATIONS 9000+9000+9000, 12000+9000+9000, 12000+12000+9000 Btu/h INVERTER MULTI MODELS TYPE HEAT PUMP TYPE MODEL NAME AOU36RML1 INDOOR UNIT COMBINATION 9+9+9 12+9+9 12+12+9 CONNECTION PATTERN OF INDOOR UNIT Wall Mounted Ducted Cassette Wall Mounted Ducted Cassette Wall Mounted Ducted Cassette POWER SOURCE 230/208V ~ 60Hz...
Page 68
1-2. COMBINATIONS 12000+12000+12000, 18000+9000+9000, 9000×4 Btu/h INVERTER MULTI MODELS TYPE HEAT PUMP TYPE MODEL NAME AOU36RML1 INDOOR UNIT COMBINATION 12+12+12 18+9+9 9+9+9+9 CONNECTION PATTERN OF INDOOR UNIT Wall Mounted Ducted Cassette Wall Mounted Ducted Cassette Wall Mounted Ducted Cassette POWER SOURCE 230/208V ~ 60Hz AVAILABLE VOLTAGE RANGE 187-253V ~...
Page 69
2. DIMENSIONS MODEL : AOU36R [Unit : Inch (mm)] Top view 1-7/32 15/32 1-11/16 (43) (31) (12) 35-7/16 (900) 13 (330) Front view 15-3/4 (400) 25-19/32 (650) Side view Bottom view 15/32 4- 15/32 ( 12) (12) 1-5/8 (41) MOUNTING POSITION [Unit : Inch (mm)] When there are obstacles at the When there are obstacles at the...
5. COEFFICIENT OF COMPENSATION FOR PIPE LENGTH AND HEIGHT DIFFERENCE This table is created using the maximum capacity. INDOOR UNIT 9000BTU (AOU36R) COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE Pipe length COOLING 7.5m 16ft. 25ft. 33ft. 49ft. 66ft. 82ft. 15m 49ft. 0.968 0.956 0.940 10m 33ft.
Page 73
This table is created using the maximum capacity. INDOOR UNIT 12000BTU (AOU36R) COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE Pipe length COOLING 7.5m 16ft. 25ft. 33ft. 49ft. 66ft. 82ft. 15m 49ft. 0.959 0.943 0.924 10m 33ft. 0.979 0.967 0.950 0.931 Indoor unit is upper 7.5m 25ft.
Page 74
This table is created using the maximum capacity. INDOOR UNIT 18000BTU (AOU36R) COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE Pipe length COOLING 7.5m 16ft. 25ft. 33ft. 49ft. 66ft. 82ft. 15m 49ft. 0.968 0.961 0.954 10m 33ft. 0.982 0.976 0.969 0.962 Indoor unit is upper 7.5m 25ft.
7. AIR FLOW MODEL : AOU36R COOLING Number of rotations Air flow (r.p.m) 3600 1000 2119 HEATING Number of rotations Air flow (r.p.m) 3800 1056 2237 - (02 - 10) -...
Page 79
9. ELECTRIC CHARACTERISTICS Model name AOU36R Voltage 230 / 208 Power supply Frequency Max. operating current 19.8 / 19.8 Starting current 15.0 Main fuse (Circuit breaker) 30.0 current *1) Wiring spec. Power cable *2)Limited wiring length 55 / 49 *1) Wiring spec. Selected sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) *2) Limited wiring length :...
Page 80
10. SAFETY DEVICES Model Protection form AOU36R 3.15A 250V Current fuse (MAIN PCB) 5A 250V Circuit protection Current fuse 10A 250V (NEAR THE TERMINAL) °F OFF °C OFF Fan motor protection Temperature Thermistor °F ON °C ON ±4 ±2 °F OFF °C OFF Compressor protection Temperature Thermistor...