Commercial Air Conditioning SERVICE MANUAL Models AD182ALERA AD362AHERA Features High energy efficiency PAM control Can be connected with the universal outdoor unit Infrared control type or wired control type Low ambient cooling kit (optional) and low ambient heating kit (optional)
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 1.DESCRIPTION OF PRODUCTS & FEATURES 1.1 Products code explanation D 18 E R A Climate type: T1 (see table 1) Design number (A-G stands for fixed frequency type, R-Z stands for DC inverter frequency type)
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 1.4 Product features Adopt the much friendlier refrigerant R410a The air conditioner system adopts the greatly friendly refrigerant R410a, which is protective for the ozone layer and is good to avoid the earth getting warmer. Benefit for the environment.
Page 5
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 1.5 New friendly refrigerant R410A introduction: ■R410A The working pressure of R410A is approximately 1.6 times higher than R22. Because the oil in the refrigerant is different, please do not mix them. Refrigerant R22 (single)
Page 6
Commercial Air Conditioner Model: AD182ALERA AD362AHERA ■Piping material 1. Use the correct refrigerant piping and materials for R410A 2. For the pipe wall thickness, see the table below: Pipe diameter Φ6.35 Φ9.52 Φ12.7 Φ15.88 Φ19.1 Pipe wall thickness Note: Always observe and comply with the local regulations when installing the refrigerant piping.
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 2. SPECIFICATION item Model AD182ALERA Function cooling heating Capacity 4.8(1.8--5.8) 5.5(2.0---6.8) Total power input 1.65(0.55---2.65) 1.70(0.60---2.65) Max. power input 2650 2650 EER or COP 2.91(C) 3.24(C) Dehumidifying capacity 10‐³×m³/h Running /Max.Running current A / A 7.5(3.0---12.0)/12A 7.5(3.0---12.0)/12A...
Page 8
Commercial Air Conditioner Model: AD182ALERA AD362AHERA Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DB Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 3. Safety precaution 3. Safety precaution Carefully read the following information in order to operate the airconditioner correctly. Below are listed three kinds of Safety Cautions and Suggestions. WARNING! Incorrect operations may result in severe consequences of death or serious injuries.
Page 10
Commercial Air Conditioner Model: AD182ALERA AD362AHERA WARNING! Nothing or nobody is permitted to Installed electrical-leaking circuit placed on or stand on outdoor unit. breaker. It easily cause electrical shock without The falling of goods and people may circuit breaker. cause accidents.
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 7. Controller functions For duct type, the indoor unit can be controlled by wired controller YR-E12 as standard control or by remote controller YR-H71 and remote receiver RE-01 as optional control. As for the connection method, please refer to below figures:...
Page 27
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 8. Electrical Control Functions 1.General features 1.1 Control mode: remotr or wired control + connecting port of long-distance control + passive port control. 1.2 Temperature control: 16-30℃ 1.3 Precise of temperature control: ±1℃ 1.4 Indoor fan speed: AUTO, HIGH, MIDDLE, LOW (no AUTO when in FAN mode);...
Page 28
Commercial Air Conditioner Model: AD182ALERA AD362AHERA conditions, then perform the selected mode. Tr≥Ts-3℃ select COOL mode (includes FAN mode) Tr<Ts-3℃ select HEAT or FAN mode 4.2 After entering the AUTO mode, the mode can change over among COOL, HEAT or FAN...
Page 29
Commercial Air Conditioner Model: AD182ALERA AD362AHERA speed, this area is defined as Area A; 0≤ΔT≤2, the compressor and the outdoor motor will always run for 10 minutes and then stop for 6 minutes, indoor motor will be LOW speed, this area is defined as Area B;...
Page 30
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 7.6 Anti-cold air function in heating mode After entering heating mode, or last defrosting is over, the compressor will start up, if Tg<28℃, indoor motor will stop; if 38℃>Tg≥28℃, indoor motor will run at low speed; if Tg≥38℃ or the compressor has run for over 4 minutes, indoor motor will run at the set speed;...
Page 31
Commercial Air Conditioner Model: AD182ALERA AD362AHERA receiving the timer signal for the last time. The SLEEP function only can be set before the TIMER ON begins. TIMER OFF: the unit running, the timer LED on, while the timer is over, timer LED off, the unit will stop, the sleep can be set, the sleep time will replace the original time of TIMER ON/OFF.
Page 32
Commercial Air Conditioner Model: AD182ALERA AD362AHERA pressure is too low and low pressure switch is running for 30 senconds, compressor and outdoor fan motor will stop and will send failure 13. Trouble code The remote receiver, wired controller and indoor PCB indicator all can indicate the failure code.
Page 33
Commercial Air Conditioner Model: AD182ALERA AD362AHERA temp. sensor-multi) 20(32D) Module failure Module overheat, overcurrent, due to the signal, short-circuit resumable 36(54D) Fault in zero-load Current sensor failure or due to the signal, resumable compressor is not started 14 Jumper selection (√shows jumper connected, ON; ×shows jumper disconnected, OFF; *...
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 10. Troubleshooting 1) Pressure protection Confirm the fault according to the fault code list Does system have Are CN17 and CN18 Replace PCB pressure switch? in PCB cut off? Make them in short circuit...
Page 38
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 3) Low pressure protection Confirm the fault according to the fault code list Are connectors of pressure switch in good Check and reconnect condition? Is low side pressure switch Replace PCB activated? (If not, DC voltage is 0V.)
Page 39
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 4) High pressure protection Confirm the fault according to the fault code list Are connectors of pressure switch in good Check and reconnect condition? Is high side pressure switch Replace PCB activated? (If not, DC voltage is 0V.)
Page 40
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 5) Communication error between indoor and outdoor units Confirm commumication failure according to the fault code list Confirm the fault indicator is communication failure Are communication wire Does indoor communication S and supply wires L and...
Page 41
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 7) High current protection in 3-phase fixed frequency models Is three-phase circuit not balanced? Is supply voltage too Modify power supply circuit low? Is supply voltage too low at compressor start-up? Is power cable or compressor wire...
Page 42
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 9) Overcurrent protection for single-phase fixed frequency models Is supply voltage too low? Especially modify power supply circuit when compressor starts up? Is supply wire securely re-wiring connected? Is compressor current more than overcurrent...
Page 43
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 10) Temperature cutoff protection confirm the malfunction according to the fault code list Does small relay coil Is outdoor four-way valve Relay is broken. of four-way valve have in good condition during Replace PCB...
Page 44
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 11) Fault in drain system confirm the malfunction according to the fault code list Unclog pipe and Is drain pipe clogged? water pump Is pump motor in Replace water good condition? pump Is drain pan dirty and...
Page 45
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 13) Fault in indoor fan motor confirm the malfunction according to the fault code list Is indoor status Is output voltage of indication good? fan motor good? Is power supply good? Is fan capacitor...
Page 46
Commercial Air Conditioner Model: AD182ALERA AD362AHERA 14) Troubleshooting (before replacement of PCB) Service call Fault confirmation For example: no cooling, etc. 1.Is supply voltage acceptable? Confirm operating 2.Is temperature setting correct? (e.g. too high) conditions 3.Is system in TIMER mode? 4.Is user aware of product features, etc.