(Consists of One PUHY-P120TKMU-A, One PUHY-P72TKMU-A and One CMY-Y100CBK3 Twinning Kit)
Job Name:
Engineer Name:
System No.:
OUTDOOR VRF HEAT PUMP SYSTEM FEATURES
•
3-phase, 208/230V
•
Modular variable refrigerant flow (VRF) systems;
smaller capacity units can be piped together to form a single,
large-capacity two-pipe system
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static pressure;
factory set to 0"WG
• Connects to CITY MULTI indoor units; controlled via
CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating Temperature Range
Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB
Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
Specifications
Unit Type
Nominal Cooling Capacity
Nominal Heating Capacity
External Dimensions (H x W x D)
Net Weight
Electrical Power Requirements
Cooling Power Input
Heating Power Input
Cooling Current (208/230V)
Heating Current (208/230V)
Minimum Circuit Ampacity
(MCA)**
Maximum Breaker Size**
Maximum Overcurrent Protection**
Piping Diameter
From Twinning Kit to Indoor Units
(Brazed) (In. / mm)
From Modules to Twinning Kit
(Brazed) (In. / mm)
Indoor Unit
Sound Pressure Levels
Fan
Type x Quantity
Airflow Rate
Direct-drive Inverter Motor Output
Compressor Operating Range
Compressor Type x Quantity
Compressor Motor Output
Compressor Crankcase Heater
Refrigerant
Lubricant
High-pressure Protection Device
Compressor / Fan Protection Device
Inverter Protection Device
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
PUHY-P192TSKMU-A
Model:
System
PUHY-P192TSKMU-A
Btu/h
192,000
Btu/h
215,000
In. / mm
Refer to Module Data
Lbs. / kg
1,127 / 511
Voltage, Phase, Hertz
Refer to Module Data**
kW
kW
R.L.A.
45.6 / 41.3
R.L.A.
52.1 / 47.1
A
Refer to Module Data**
A
Refer to Module Data**
A
Refer to Module Data**
Liquid (High Pressure)
5/8 / 15.88
Gas (Low Pressure)
1-1/8 / 28.58
Liquid (High Pressure)
Refer to Module Data
Gas (Low Pressure)
Total Capacity
50 to 130% of ODUs
Model / Quantity
P06 ~ P96 / 2 to 41
dB(A)
Refer to Module Data
CFM
kW
6% to 100%
Refer to Module Data
kW
kW
Refer to Module Data
Refer to Module Data
Location:
Contractor:
Date:
PUHY-P120TKMU-A
OPTIONAL PARTS
□ Twinning Kit*..................................................CMY-Y100CBK3
□ T-Branch Joint (≤ 72,000 Btu/h)............................CMY-Y102SS-G2
□ T-Branch Joint (≤ 144,000 Btu/h)..........................CMY-Y102LS-G2
□ T-Branch Joint (≤ 234,000 Btu/h)...........................CMY-Y202S-G2
□ Header (4-Branch; ≤ 72,000 Btu/h)..........................CMY-Y104C-G
□ Header (8-Branch; ≤ 144,000 Btu/h)........................CMY-Y108C-G
□ Header (10-Branch; ≤ 234,000 Btu/h)......................CMY-Y1010C-G
* Twinning Kit is necessary to combine the refrigerant flows of the
modules and is sold separately.
Module 1
PUHY-P120TKMU-A
120,000
135,000
65 x 68-29/32 x 29-5/23 /
1,650 x 1,750 x 740
697 / 316
14.81
16.91
45 / 42**
50**
73 / 67**
1/2 / 12.7
1-1/8 / 28.58
62.5
60.0
Propeller Fan x 2
11,300
0.92 + 0.92
Inverter-driven Scroll Hermetic x 1
8.1
-
601 psi / 4.15 MPa
Overheat Protection / Thermal Switch
Overheat / Overcurrent Protection
PUHY-P72TKMU-A
Module 2
PUHY-P72TKMU-A
72,000
80,000
65 x 36-1/4 x 29-5/32 /
1,650 x 920 x 740
430 / 195
208 / 230V, 3-phase, 60Hz**
Refer to System Data
Refer to System Data
25 / 23**
30**
42 / 38**
Refer to System Data
3/8 / 9.52
7/8 x 22.2
Refer to System Data
58.0
Propeller Fan x 1
6,200
0.92
Refer to System Data
Inverter-driven Scroll Hermetic x 1
5.5
-
R410A
MEL32
601 psi / 4.15 MPa
Overheat Protection / Thermal Switch
Overheat / Overcurrent Protection