hit counter script

echoflex Elaho Installation Manual

Dual tech switch-mount occupancy
Hide thumbs Also See for Elaho:

Advertisement

Quick Links

Echoflex Installation Guide
Elaho Dual Tech Switch-mount Occupancy
Overview
The Elaho Dual Tech Switch-mount Occupancy Sensor is a switch station
with a built-in sensor that uses passive infrared (PIR) and acoustic
detection to provide reliable occupancy and vacancy sensing for lighting
control.
Each button is back lit by both blue and amber LEDs to show changes in
status. The sensor provides a 180 degree field of view with up to 13.7 m
(45 ft) radius for large motion detection.
This document guides you through the installation and local
configuration of the Dual Tech Switch-mount Occupancy Sensor.
Custom Configuration
For more information about the custom configuration options available
using ElahoAccess, reference the ElahoAccess Mobile App integrated help
system.
Note:
the function selection switch is set to Custom (middle position).
Reference
Corporate Headquarters n Middleton, WI, USA | +1 608 831 4116
© 2023 Echoflex Solutions, Inc. | Trademark and patent info:
Web
echoflexsolutions.com
Third-party license agreement
change. Echoflex intends this document to be provided in its entirety.
8186M2187 Rev C Released 2023-06
Settings made using ElahoAccess are applied only when
Function Switch on
| Email
info@echoflexsolutions.com
info: etcconnect.com/licenses
The Dual Tech Switch-mount
Occupancy Sensor is available in
1–button and 2–button models, and
is available with white, black, cream,
or gray wall plate.
page 11.
echoflexsolutions.com/ip
| Support
service@echoflexsolutions.com
| Product information and specifications subject to

Advertisement

Table of Contents
loading

Summary of Contents for echoflex Elaho

  • Page 1 Echoflex Installation Guide Elaho Dual Tech Switch-mount Occupancy Overview The Elaho Dual Tech Switch-mount Occupancy Sensor is a switch station with a built-in sensor that uses passive infrared (PIR) and acoustic detection to provide reliable occupancy and vacancy sensing for lighting control.
  • Page 2: Prepare For Installation

    Dual Tech Switch-mount Occupancy Sensor Prepare for Installation Elaho Dual Tech Switch-mount Occupancy Sensors ship with electronics, a decorator style wall plate, and a termination kit. The sensor may be installed into an industry-standard back box (provided by others) or surface-mounted back box (sold separately and available from Echoflex).
  • Page 3: Wire Specification

    EchoConnect communication bus. EchoConnect is a bi-directional protocol that uses one pair of wires (data+ and data–) for both data and power. Echoflex recommends using Belden 8471 Class 2 wire (or approved equal – see the Echoflex cable cross database echoflexsolutions.com/files/Elaho_Data_Cable_Wire_Specs...
  • Page 4: Installation

    Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Installation Installation should follow all local codes and standard electrical practices. Note: NEC Class 2 product to be wired in accordance to NEC Article 725 and local jurisdiction requirements. The back box should be installed plumb and square for best results.
  • Page 5 Rotary and DIP switch settings are accessible on the rear of the station. Set Space and Address The Dual Tech Switch-mount Occupancy Sensor participates in an Elaho system using the configured Space and Address, which are provided on the selectable using the two rotary switches on the back of the sensor.
  • Page 6 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Switch # Vacancy Timeout • 5 min = Switches 3 and 4 are Off 3 and 4 • 15 min = Switch 3 is Off and Switch 4 is On (default) • 30 min = Switch 3 is On and Switch 4 is Off •...
  • Page 7 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Install Button Legends Elaho Dual Tech Switch-mount Occupancy Sensors ship with standard button legends installed beneath a clear lens. Note: Customize and print your own button legends on standard transparency. Download the button legend template provided on the Echoflex website echoflexsolutions.com.
  • Page 8 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Install the Station Receptacle spacers are provided for use in flush mount applications to help align the station and cover flush against the wall. 1. Insert the station electronics and wiring into the back box.
  • Page 9: Power Up And Test

    Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Install the Wall Plate The wall plate is secured to the station with built-in magnets. 1. Align the top of the wall plate to the station and angle the bottom approximately 20 degrees.
  • Page 10 1. Prepare the site for configuration. a. Make certain the sensor and lighting loads are powered and connected for control by the Elaho control system. b. You will need direct access to the sensor in order to place it into Walk Test mode.
  • Page 11: Station Configuration

    Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Station Configuration The Dual Tech Switch-mount Occupancy Sensor has on-board switch and button settings that are available from the front of the station when it is installed and the wall plate is removed.
  • Page 12 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor When a preset is active, the button LED lights blue to indicate its active state. If preset levels are altered while the preset is still active, the related button LED will return to its default state, either off or amber. Reference DIP Switch Settings on page 5...
  • Page 13 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Zone Toggle Functionality While the Function switch is set to Zone, the station allows you to toggle the zone on and off. The controlled zone level raises to full or toggles off using a 1/2 or two second fade time, depending on the station type.
  • Page 14 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Program Zone Start Note: The zone that is configured to the button controls is also the zone that will be activated at full with occupancy detection and deactivated with vacancy detection. 1. Set the station Function switch to Zone (the lowest switch position).
  • Page 15 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Station Functionality 1–Button Switch-mount Sensor The 1–button Switch-mount Sensor offers control of a single preset or zone as determined by the Function switch setting. Factory Defaults The 1–button Switch-mount Sensor ships from the factory in the following default settings: •...
  • Page 16 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Zone In Zone mode, an occupancy detection event activates the zone that is configured to button 1 at full, and the vacancy detection event deactivates the Zone (set to 0%). The 1–button sensor supports the following button actions:...
  • Page 17 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor 2–Button Switch-mount Sensor The 2–Button Switch-mount Sensor offers control of two presets or zones as determined by the Function and DIP switch settings. Factory Defaults The 2–Button Switch-mount Sensor ships from the factory in the...
  • Page 18 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Zone In Zone mode, an occupancy detection event activates the zone that is configured to button 1 at full, and the vacancy detection event deactivates the Zone (set to 0%). The 2–Button sensor supports the following button actions:...
  • Page 19 Echoflex Installation Guide Dual Tech Switch-mount Occupancy Sensor Custom While the 2–Button Switch-mount Sensor supports the following default button actions in Custom mode, complete customization is available when using ElahoAccess. In Custom mode using default behaviors, an occupancy event activates the zone that is configured to button 1 at full, and the vacancy detection event deactivates the Zone (set to 0%).
  • Page 20 15° 14 m (45 ft) Compliance The Dual Tech Switch-mount Occupancy Sensor is for use with Echoflex dimming and relay products. For current and complete compliance information, view the product datasheet at echoflexsolutions.com. For complete product documentation, including compliance documentation, visit echoflexsolutions.com/products.

Table of Contents