SMU11B Site Monitoring Unit
V500R003C00
User Manual
Issue
03
Date
2022-06-06
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei SMU11B

  • Page 1 SMU11B Site Monitoring Unit V500R003C00 User Manual Issue Date 2022-06-06 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 4 Issue 03 (2022-06-06) Updated Figure 1-2, Table 1-4. Issue 02 (2020-08-12) Updated Table 1-3 Issue 01 (2020-02-28) This is the first official release. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 5: Table Of Contents

    User Manual Contents Contents About This Document........................ ii 1 Description of Components....................1 1.1 Monitoring Module SMU11B.............................. 1 1.2 Expansion Box MUE03A................................ 6 2 User Interface......................... 10 2.1 Installing a Communications Cable..........................10 2.2 Logging In to the WebUI..............................10 3 NMS Management........................ 12 3.1 NetEco Management................................
  • Page 6 A.19 Yada2060 Ammeter Alarm Table..........................48 A.20 Rectifier Alarm Table................................ 48 A.21 Rectifier Group Alarm Table............................49 A.22 DC Energy Meter Alarm Table............................50 A.23 Int. AirCon Alarm Table..............................50 B Acronyms and Abbreviations....................52 Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 7: Description Of Components

    Figure 1-1 SMU11B appearance (1) Running indicator (2) Minor alarm indicator (3) Major alarm indicator (4) Wiring terminals (5) Communications port COM (6) Handle (7) Position of the SN code (8) Communications port FE Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 8 Steady on A minor or warning alarm is generated. Major alarm Steady off No critical or indicator major alarm is generated. Steady on A critical or major alarm is generated. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 9 DI4+ Dry contact input DI4- DI5+ DI5- Table 1-3 Pin definitions for SIG2 wiring terminals Signal Description Battery midpoint voltage detection port 1 Battery midpoint voltage detection port 2 Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 10 HTTPS protocols Connects to a PC and manages the SMU through the WebUI. NOTE All these ports are protected by a security mechanism. Figure 1-3 Pins in the COM port Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 11 Grounding Figure 1-4 Pins in the FE port Table 1-6 Pin definitions for the FE port Signal Description Transmits data over FE. Receives data over FE. 4, 5, 7 and 8 Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 12: Expansion Box Mue03A

    19200 bit/s, Modbus protocols monitoring or 115200 bit/s module. COM_OUT1 Baud rate: 9600 Master-slave and Connects to an bit/s, 19200 bit/s, Modbus protocols intelligent device. COM_OUT2 or 115200 bit/s COM_OUT3 Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 13 Table 1-10 Pin definitions for the COM_OUT1, COM_OUT2, and COM_OUT3 ports Signal Description RS485+ RS485 data + RS485- RS485 data - 12 V Power supply RS485+ RS485 data + RS485- RS485 data - 6, 7 – Grounding (PE) Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 14 Signal Description DIN6–DIN9 12 V 12 V output 12 V 12 V output DIN N Dry contact input Grounding (PE) WATER 12 V 12 V output WATER Water sensor signal input Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 15 SMOKE Smoke sensor signal input 12 V 12 V output Figure 1-10 J7 pins Table 1-13 J7 pin definitions Terminal Signal Description 12 V 12 V output Grounding (PE) – – Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 16: User Interface

    Step 1 Set the PC IP address in the same network segment as the SMU IP address. For example, if the SMU has an IP address of 192.168.0.10, a subnet mask of 255.255.255.0, and a default gateway of 192.168.0.1, set the IP address to Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 17 192.168.0.10) in the address box of the browser, and then press Enter to access the WebUI login page. Figure 2-2 WebUI login page NO TE The initial user name is admin, and the initial password is Changeme. ----End Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 18: Nms Management

    Step 3 Set the IP type, IP address, subnet mask, and gateway address on the WebUI. NO TICE If the IP address of the SMU11B is changed on the WebUI, record the IP address for future login. Issue 03 (2022-06-06)
  • Page 19: Logging In To The Neteco

    Procedure Step 1 Enter https://NetEco IP address: port number for NetEco login (for example, https://10.10.10.1:31943) in the address box of the browser and press Enter. The NetEco login page is displayed. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 20: Nms Management Over Snmp

    3.2 NMS Management over SNMP 3.2.1 Connecting a Communications Cable Procedure Step 1 Connect the FE port on the SMU by using a network cable. Figure 3-3 Connecting a communications cable (1) FE port ----End Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 21: Setting Snmp Parameters

    Step 1 Log in to the WebUI. NO TE The initial user name is admin, and the initial password is Changeme. Step 2 Access the System Settings page and set SNMP. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 22 User Name, MD5/SHA Password, and DES/AES Password. Then click Confirm. Step 3 In SNMP Trap, click Add. ● If the SNMP version is SNMPv1 or SNMPv2c, set Trap Target Address, Trap Port, and Trap Community. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 23: Nms Commissioning

    You can query the power system on the network management system (NMS) that is connected over the Simple Network Management Protocol (SNMP). For details, see the related documents of the NMS. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 24: Common Operations

    When importing the backup configuration file, ensure that the system type of the exported configuration file is the same as that of the configuration file to be imported. Figure 4-1 Backing up current settings Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 25: Importing A Configuration File

    After factory defaults are restored, all parameter values change to their default factory values. You are advised to back up the current settings before restoring factory defaults. CA UTION After factory defaults are restored, the monitoring unit restarts. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 26: Upgrading Software

    ● Exercise caution to choose the version rollback function during software upgrade. After version rollback, the user accounts created are deleted, and the initial user name and password are required for login. Figure 4-4 Upgrading software Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 27: Importing An Individual File

    Only the system administrator can change user passwords. Changing a User Password Step 1 Log in to the WebUI and choose Maintenance > User Management. The user management page is displayed. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 28 Confirm. The Recertification dialog box is displayed. CA UTION The administrator needs to set Old Password only when changing the administrator's own password. Change the password in compliance with the following rules: Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 29: Viewing Active Alarms

    ● You are advised to periodically change the WiFi password to improve account security and prevent unauthorized network attacks, such as data tampering. ● Huawei will not be liable for any loss caused by your failure to change the password in time or to keep the new password properly.
  • Page 30: Viewing Version Information

    Figure 4-9 Filtering out historical alarms Step 2 View historical alarms. Figure 4-10 Viewing historical alarms ----End 4.9 Viewing Version Information Querying the monitoring version number helps you locate fault causes and verify upgrades. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 31: Collecting Fault Information

    Figure 4-11 Viewing version information 4.10 Collecting Fault Information The SMU11B collects fault information about lithium batteries and rectifiers. The fault information records the running information about the lithium battery and rectifier module for a specified period of time. The information can be used to locate faults.
  • Page 32: Exporting Maintenance Information

    WebUI to quickly collect information and identify system faults. Procedure Step 1 Export historical data. Figure 4-14 Exporting historical data Step 2 Export e-label information. Figure 4-15 Exporting e-label information Step 3 Export fault information. Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 33 SMU11B Site Monitoring Unit User Manual 4 Common Operations Figure 4-16 Exporting fault information ----End Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 34: Installing A Cable For The Expansion Box

    COM port on the SMU. Figure 5-1 Installing a cable for the expansion box NO TE Ensure that the expansion box side with holes does not face downwards. ----End Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 35: Replacing An Smu11B

    COM communications cables, and remove the signal cable terminals. Step 3 Pull out the handle of the monitoring module to remove it from the subrack. Figure 6-1 Removing the old monitoring module Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 36 Step 8 Set the IP address of the new monitoring module to the IP address of the old one. Log in to the WebUI, import the individual file, and set parameters as required. ----End Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 37: A Alarm List

    Overvoltage AC Phase Enable Minor Undervoltage AC Phase Failure Enable Minor A.2 ibox Alarm Table Table A-2 ibox Alarm Settings WebUI Alarm Alarm Enabled Alarm Severity Relay Communication Enable Minor Failure Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 38: Tcuc Alarm Table

    Warning Undertemperature Alarm TEC Cooler Fault Enable Major Door Open Alarm Enable Minor Smoke Alarm Enable Critical Water Alarm Enable Critical Reserved IN0 Enable Minor Alarm Reserved IN1 Enable Minor Alarm Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 39 Battery String 4 Enable Warning Cell2 Imbalance Battery String 4 Enable Warning Cell3 Imbalance Battery String 4 Enable Warning Cell4 Imbalance Communication Enable Minor Failure Battery String 1 Enable Warning Mid-Point Imbalance Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 40 Major Missing Infra Sensor Alm Enable Major Heater Fault Alm Enable Major Equip Fault Enable Minor Emergency Enable Warning Ventilation Start Motor1 Abnormal Enable Major Alarm Motor2 Abnormal Enable Major Alarm Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 41: Battery String Alarm Table

    Minor AC Phase L1 Enable Minor Overvoltage AC Phase L2 Enable Minor Overvoltage AC Phase L3 Enable Minor Overvoltage AC Phase L1 Enable Minor Undervoltage AC Phase L2 Enable Minor Undervoltage Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 42 Bus Bar Ultra UV Disable Critical Bus Bar Undervolt. Enable Major SEB Comm. Failed Enable Major DIN1 Alarm Enable Minor DIN2 Alarm Enable Minor DIN3 Alarm Enable Minor DIN4 Alarm Enable Minor Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 43 Disconnected LLVD2 Warning Enable Major LLVD2 Disconnected Enable Major LLVD2 Low Voltage Enable Critical Disconnected LLVD2 Manual Enable Major Disconnected LLVD2 High Enable Major Temperature Disconnected LLVD2 Timed Enable Major Disconnected Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 44: Electronic Lock Alarm Table

    Certs Pre Enable Major Overtime Certs Overtime Enable Major A.8 Li Battery Alarm Table Table A-8 Li Battery Alarm Settings WebUI Alarm Alarm Enabled Alarm Severity Relay Communication Enable Minor Failure Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 45 Cell 5 Fault Battery Enable Major Electrochemical Cell 6 Fault Battery Enable Major Electrochemical Cell 7 Fault Battery Enable Major Electrochemical Cell 8 Fault Battery Enable Major Electrochemical Cell 9 Fault Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 46 Major Battery Enable Major Electrochemical Cell Abnormal Communication Enable Minor Failure Low Temperature Disable Minor Overdischarge Enable Warning Charge Enable Warning Overcurrent Charge Enable Minor Overcurrent Protection Discharge Enable Warning Overcurrent Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 47: Lithium Battery Group Alarm Table

    Enable Minor Temperature Low Battery Enable Minor Temperature BLVD Enable Major Disconnected Battery Fuse Enable Critical Break Battery Enable Warning Temperature Sensor 1 Missing Battery Enable Warning Temperature Sensor 2 Missing Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 48: Door Sensor Alarm Table

    Enable Minor Temperature Battery Low Enable Warning Temperature Battery Enable Warning Temperature Sensor 1 Missing Battery Enable Warning Temperature Sensor 2 Missing Battery Equalized Disable Warning Charging BLVD Enable Major Disconnected Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 49 Battery Very Low Disable Minor Temperature Battery Test Disable Warning Cancelled Battery Testing Disable Warning Battery Test Disable Major Negative Battery Current Enable Warning Imbalance Battery Enable Major Temperature Sensor 2 Fault Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 50: Camera Alarm Table

    Warning Battery Config Enable Minor Incorrect A.12 Camera Alarm Table Table A-12 Camera Alarm Settings WebUI Alarm Alarm Enabled Alarm Severity Relay Communication Enable Major Failure Motion Detection Enable Minor Alarm Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 51: Mains Alarm Table

    Mains Phase L3 Enable Major Failure Mains L1-L2 Enable Minor Overvoltage Mains L2-L3 Enable Minor Overvoltage Mains L3-L1 Enable Minor Overvoltage Mains L1-L2 Enable Minor Undervoltage Mains L2-L3 Enable Minor Undervoltage Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 52: Water Sensor Alarm Table

    Indoor Return Enable Major Vent Temperature Sensor Fault Outdoor Enable Warning Temperature Sensor Fault Indoor Vent High Enable Critical Temperature System Noise Too Disable Major Loud Indoor Vent High Enable Major Temperature Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 53: Humiture Sensor Alarm Table

    Relay Communication Enable Minor Failure High Ambient Enable Minor Temperature Low Ambient Enable Warning Temperature Very High Enable Major Ambient Temperature High Ambient Enable Warning Humidity Low Ambient Enable Warning Humidity Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 54: Tem_Hum_Group Alarm Table

    Table A-20 Rectifier Alarm Settings WebUI Alarm Alarm Enabled Alarm Severity Relay Rectifier Fault Enable Major Rectifier Enable Minor Protection Communication Enable Minor Failure Rectifier Power Enable Major Failure Rectifier Enable Major Overvoltage Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 55: Rectifier Group Alarm Table

    All Rectifiers Fail Enable Major to Communicate Rectifier Disable Warning Hibernation Activated High Rectifier Disable Minor Capacity Low Rectifier Enable Critical Capacity Rectifier Upgrade Enable Major Fault Not Config Enable Major Rectifier Addr Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 56: Dc Energy Meter Alarm Table

    Major High Temperature Frequent Low Enable Major Pressure A/C Run Enable Minor Abnormal Compressor Enable Minor Current Exception AC Input Enable Major Abnormal AC Failure Enable Major AC Overvoltage Enable Major Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 57 Alarm Enabled Alarm Severity Relay AC Undervoltage Enable Major Nonautomatic Enable Major Mode Alarm Air Conditioner Disable Warning Air Conditioner Disable Warning Door Open Alarm Disable Major External Fan Disable Major Alarm Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.
  • Page 58: B Acronyms And Abbreviations

    SMU11B Site Monitoring Unit User Manual B Acronyms and Abbreviations Acronyms and Abbreviations Control area network Internet Protocol SNMP Simple Network Management Protocol Site monitoring unit User interface Issue 03 (2022-06-06) Copyright © Huawei Technologies Co., Ltd.