Troubleshooting guide
If you have installed and connected the fitting as per the instructions listed earlier and it does
not function correctly, use the following table as a guide to fixing the problem. Look up the
type of fault in the left column and check the possible causes from the right column.
If the fitting still does not work after checking these possible causes, contact ABB customer
service in Australia on 1800 60 20 20.
No. Fault
1
LED light source and indicating LED not lit
2
LED light source is lit but indicating LED not lit
3
LED light source does not switch to emergency
mode when the test button is pressed
4
LED light source works momentarily on emergency
when the test button is pressed
ABB Australia Pty Limited
For enquiries
ABB contact centre: 1800 60 20 20
E-mail: AU-ABB-Stanilite@abb.com
www.stanilite.com.au
Possible causes
AC supply not connected; or
AC supply turned off; or
Test switch damaged
Test switch damaged; or
Battery not connected or faulty
Test switch damaged; or
Battery not connected or faulty
Battery not yet charged (allow up to 24 hours)
© Copyright 2019 ABB. All rights reserved.
I N S TA L L AT I O N M A N U A L
Stanilite®
Platinum Spitfire® LED recessed
Nexus® RF
Thank you for choosing ABB product
Please read this document thoroughly before
commencing installation and retain for future
reference. Contact ABB customer service in
Australia on 1800 60 20 20 if you need any
assistance. The installation instructions were
correct at the time of print. To reflect changes in
technology and Australian standards; ABB
reserves the right to amend the instructions
without notice. Updated document can be found
on the Stanilite website.
Safety warning
In Australia and New Zealand, only licensed
electricians are permitted by law to work with
240 volt electrical installations.
Do not attempt to install or connect this product
unless you are a licensed electrician.
Turn off and isolate the electrical supply before
connecting this fitting to the building wires.
Do not touch the terminals of the terminal block
when the light fitting is energised.
The only user-serviceable parts are the lamp head
assembly and battery pack. LED light source is
not user-serviceable.
Do not attempt to service other parts of the
This document covers
What's inside the box
Safety warning
Lamp head assembly
Installation instructions
Battery and control pack
Removal instructions
Accessory kit
Testing precautions
Installation manual
Troubleshooting guide
Warranty information
fitting as this will void the warranty.
As the installer, it is your responsibility to ensure
compliance with all relevant building and safety
codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to
the applicable standards for data and mains
cabling installation procedures and
requirements.
As per AS 60598.2.2:2016 the recessed luminaire
classification is CA90.
Note: Not suitable for use with loose-fill
insulation.
The control pack and battery pack must be
installed above the insulation. No fire rated box is
required for the product.
Important to note:
• This product is designed for indoor use only.
Nexus RF (wireless system)
The Nexus RF range of light fittings are designed to
communicate via a proprietary RF network, however
the electrical installation of the fittings is identical
to that of a standard non-monitored fitting.
Doc no. 29-WSIS001_A

Advertisement

loading

Summary of Contents for ABB Nexus RF

  • Page 1 I N S TA L L AT I O N M A N U A L If the fitting still does not work after checking these possible causes, contact ABB customer Stanilite®...
  • Page 2 Installation instructions 1. Note: The circuit supplying mains power to the fitting must not be energised until installation of Data connections - Nexus RF product range the fitting is completed. 2. Mark and cutout a hole in the ceiling to suit either small or large Spitfire head. The cut-out size for Nexus RF fitting the standard lamp head is 50mm.