Technical Information
G50A
User Guide
0/Remote Prohibit Timer Mode
Initial Settings
When the G50A is powered for the first time select
group setting option 4 (press 4), after the initialisation
has finished.
If system is already working Press "
together for 3 sec until the second menu appears.
Select group setting option 1 (press "1").
Select the group to change with the group select switch.
Enter the indoor addresses (001 enter, 002 enter etc)
in that group.
To enter the remote controller address press "
key until the curser is underneath "remote controller"
and enter the remote controller address.
If you want to name the group press "
name set is flashing, then press enter.
Use the curser keys to highlight the letter required
and press enter.
When the name is complete press the back screen
button to return to the group screen.
Try to make the group number the same as first
address in that group.
When all groups are complete, press back screen
to return to the menu. Press "
together for 3 sec to return to the user menu.
1/On/Off
2/Mode
3/Fan Speed
Del/Reset
" curser keys
"
" until group
" curser keys
>
Group Select
Curser Keys
Enter
Timer Setting
Press the back screen until the user menu is displayed.
Select option 3 schedule setting (press 3).
Use the curser keys to select the timer pattern
P1, P2, P3 or
P4
then press enter.
Use the clock pattern buttons to set the On time.
Move the curser and set the Off time.
Once all the on/off 's have been set press the back
screen to return to the previous screen.
Move the curser under the day of the week you
want to apply the pattern to and with clock pattern
buttons set the pattern number.
If you want to apply the same timer patterns to each
group move the curser to M in the bottom right of the
screen and press enter to put the settings into memory
change the group with the group setting button and
use MR enter to put the timer settings into that group.
When this is complete back screen to the menu and
the timer is set.
Back Screen Button
Repeated pressing of the back screen button will
return to a menu screen.
www.mitsubishielectric.co.uk/aircon
4/Temp
5/Clock Pattern
6/Air Direction
Back Screen
7/Temp
8/Clock Pattern
9/Ventilation