Although every commercially reasonable effort has been taken to ensure the quality and accuracy of the information, Gallagher Group makes no representation as to its accuracy or completeness and it should not be relied on as such. To the extent permitted by law, all express or implied, or other representations or warranties in relation to the information are expressly excluded.
1 x M3 Torx Post (T10) Security screw Power supply The Gallagher T30 Keypad Reader is designed to operate over a supply voltage range of 9 - 16 Vdc measured at the readers. The operating current draw is dependent on the supply voltage at the reader.
Page 5
The end devices on the HBUS cable should be terminated using 120 ohms resistance. To terminate the Gallagher Controller 6000, connect the supplied on-board termination jumpers to the Controller. To terminate the Gallagher T30 Keypad Reader, connect the orange (termination) wire to the green (HBUS A) wire. Termination is already included at the HBUS Module, (i.e.
• The recommendation for optimal performance is up to 20 T30 Keypad Readers can be connected to one Controller 6000. Of these 20 terminals, up to 4 could be configured for alarm zone (or fence controller) management.
Page 9
5. Connect the terminal tail extending from the facia assembly to the building cable. An HBUS device connects to a Gallagher Controller 6000, Gallagher 4H/8H Module, a Gallagher HBUS Door Module, or a Gallagher HBUS 8 Port Hub. HBUS connections:...
Access mode is Secure Flashes Green Access has been granted. Flashes Red Access has been denied. Flashes Blue Reading and validating a PIV card. Reading a Gallagher mobile credential. 6 Accessories Accessory Product Code T30 Dress Plate, Black, Pk 5 C300326...
(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Note: Changes or modifications not expressly approved by Gallagher Limited could void the user's authority to operate this equipment.