For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
Summary of Contents for Mitsubishi Electric CITY MULTI PQHY-P-TLMU-A
Page 1
Air-Conditioners For Building Application HEAT SOURCE UNIT PQHY-P-T(S)LMU-A PQRY-P-T(S)LMU-A For use with R410A PQHY-P-Y(S)LMU-A PQRY-P-Y(S)LMU-A INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. MANUEL D’INSTALLATION Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
Page 2
[Fig. 6.0.1] 8m [26ft] 8m [26ft] <P72 ~ P120> <P144 ~ P240> [Fig. 7.1.1] B : Check that the installation leg corners are securely supported to ensure that the legs do not bend. C : Check that the installation leg corners are securely supported.
Page 3
[Fig. 8.1.1] A : Main circulating water pipe B : Shutoff valve C : Shutoff valve D : Water outlet (upper E : Refrigerant pipes F : Y-type strainer G : Water inlet (lower H : Drain pipe Heat source unit sample installation [Fig.
Page 4
[Fig. 9.2.1] [PQHY-P72~P240TLMU-A/YLMU-A] [PQHY-P144~P360TSLMU-A/YSLMU-A] unit1 unit2 unit1 unit2 A Heat source unit B 1st branch C Indoor unit D Cap E Heat source twinning kit F Header * The total length of A and A less than 10 m [32 ft].
Page 5
[Fig. 9.2.2] [PQRY-P72~P240TLMU-A/YLMU-A] B C D [PQRY-P144~P336TSLMU-A/YSLMU-A] unit1 unit2 A : Heat source unit G : Heat source twinning kit NOTE1...
Page 6
Unit combination Heat source model Unit1 Unit2 Liquid Side Gas Side Liquid Side Gas Side Liquid Side Gas Side P72T/YLMU ø9.52[3/8] ø19.05[3/4] P96T/YLMU ø9.52[3/8] ø22.2[7/8] P120T/YLMU ø9.52[3/8] ø22.2[7/8] P144T/YLMU ø12.7[1/2] ø28.58[1-1/8] P144T/YSLMU ø12.7[1/2] ø28.58[1-1/8] ø9.52[3/8] ø19.05[3/4] ø9.52[3/8] ø19.05[3/4] P168T/YLMU ø15.88[5/8] ø28.58[1-1/8] P168T/YSLMU ø15.88[5/8]...
Page 7
Total capacity of indoor units Liquid pipe Gas pipe Total capacity of indoor units Liquid pipe Gas pipe ~ 54 ø9.52[3/8] ø15.88[5/8] ~ 54 ø9.52[3/8] ø15.88[5/8] 55 ~ 72 ø9.52[3/8] ø19.05[3/4] 73 ~ 108 ø9.52[3/8] ø22.2[7/8] Downstream High-pressure Low-pressure 109 ~ 144 ø12.7[1/2] ø28.58[1-1/8] Liquid pipe...
Page 8
[Fig. 9.2.3] If there is no trap, oil can accumulate inside the pipe, causing a shortage of oil damaging the compressor. 2m[6ft] A : Indoor unit C : Within 2 m [6ft] D : Twinning pipe E : Field-supplied piping F : Twinning kit G : Straight pipe length that is 500mm [19-11/16 in] or more [Fig.
Page 9
unit 2 unit 2 unit 1 unit 1 unit 1 unit 1 unit 2 unit 2 Make sure the slope of the twinning pipes are at an angle within ±15° to the horizontal plane. If the slope exceeds the angle specified, the unit may be damaged. A : Slope downward B : Slope upward D : Twinning pipe...
Page 10
10.2 [Fig. 10.2.1] <A> Service valve for refrigerant <B> Service valve for refrigerant A : Shaft B : Service port C : Cap D : Pinched connecting pipe severing portion E : Pinched connecting pipe brazing portion <P72 ~ P120> <P144 ~ P240>...
Page 11
10.2 A Shape PQHY-P72TLMU-A/YLMU-A PQHY-P96TLMU-A/YLMU-A PQHY-P120TLMU-A/YLMU-A PQHY-P144TLMU-A/YLMU-A PQHY-P168TLMU-A/YLMU-A PQHY-P192TLMU-A/YLMU-A PQHY-P216TLMU-A/YLMU-A PQHY-P240TLMU-A/YLMU-A PQRY-P72TLMU-A/YLMU-A PQRY-P96TLMU-A/YLMU-A PQRY-P120TLMU-A/YLMU-A PQRY-P144TLMU-A/YLMU-A PQRY-P168TLMU-A/YLMU-A PQRY-P192TLMU-A/YLMU-A PQRY-P216TLMU-A/YLMU-A PQRY-P240TLMU-A/YLMU-A A Shape PQHY-P72TLMU-A/YLMU-A PQHY-P96TLMU-A/YLMU-A PQHY-P120TLMU-A/YLMU-A PQHY-P144TLMU-A/YLMU-A PQHY-P168TLMU-A/YLMU-A PQHY-P192TLMU-A/YLMU-A PQHY-P216TLMU-A/YLMU-A PQHY-P240TLMU-A/YLMU-A PQRY-P72TLMU-A/YLMU-A PQRY-P96TLMU-A/YLMU-A PQRY-P120TLMU-A/YLMU-A PQRY-P144TLMU-A/YLMU-A PQRY-P168TLMU-A/YLMU-A PQRY-P192TLMU-A/YLMU-A PQRY-P216TLMU-A/YLMU-A PQRY-P240TLMU-A/YLMU-A <A> Front pipe routing B Without a low-pressure twinning pipe <C>...
Page 12
10.3 [Fig. 10.3.1] [Fig. 10.3.2] A : Nitrogen gas A : System analyzer B : To indoor unit B : Low knob C : System analyzer C : High knob D : Low knob D : Valve E : High knob E : Low-pressure/liquid F : Valve pipe...
Page 13
10.5 [Fig. 10.5] A : Position the edge of the supplied paper with mark at the edge of the pipe cover. Then, wind the sealing material to the pipe, using the mark on the paper to properly align it. of the sealing material described in step A. C : Install the water stopper at the end face of the insulation.
Page 14
11.2 [Fig. 11.2.1] Power supply terminal block Terminal block for indoor – Terminal block for (TB1) outdoor transmission line centralized control Control box (TB3) (TB7) L1 L2 L3 A : Power source B : Transmission line C : Ground terminal [Fig.
Page 15
11.3 [Fig. 11.3.1] PQHY CN41 CN40 from CN41 to CN40 *1 (51) <B> SW5-1:ON *2 (01) (04) (05) (06) M1 M2 M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1M2 S (101) (105) (155) on CN41 <B>...
Page 16
11.3 [Fig. 11.3.3] PQHY Ground (52) (51) M1M2 S M1M2 S CN41 CN41 A B S M1 M2 M1 M2 M1M2 S M1M2 S M1M2 S M1M2 S DATA BOOK. [Fig. 11.3.4] PQRY tor from CN41 to CN40 *1 CN41 CN40 <B>...
Page 17
11.3 [Fig. 11.3.5] PQRY CN41 CN40 tor from CN41 to CN40 *1 (51) <B> SW5-1:ON *2 (52) (01) (04) (55) (05) (06) TB02 TB02 TB15 TB15 TB15 TB15 M1 M2 S M1 M2 S M1 M2 M1 M2 M1 M2 S M1 M2 S M1 M2 S M1M2 S...
- It may also be in violation of applicable laws. Do not reconstruct or change the settings of the protection devices. - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible - If the pressure switch, thermal switch, or other protection device is shorted for malfunctions or accidents resulting from the use of the wrong type of refrigerant.
1.2. Precautions for devices that use 1.4. Before installation (relocation) - R410A refrigerant electrical work Caution: Caution: Do not use existing refrigerant piping. Ground the unit. - The old refrigerant and refrigerant oil in the existing piping contains a large - Do not connect the ground wire to gas or water pipes, lightning rods, or amount of chlorine which may cause the refrigerant oil of the new unit to telephone ground lines.
2. About the product This unit uses R410A-type refrigerant. Do not use the existing piping, as it contains chlorine, which is found in conventional refrigerating machine oil and refrigerant. This chlorine will Piping for systems using R410A may be different from that for systems using deteriorate the refrigerant machine oil in the new equipment.
5. Parts list Check if the unit is shipped with the parts listed below. For precautions, see section 10.2. PQHY-P·TLMU-A/YLMU-A Model 1 Connecting elbow 2 Connecting elbow 3 Connecting pipe 4 Connecting pipe 5 Connecting pipe 6 Connecting pipe 7 Connecting pipe 8 Water stopper 9 Water stopper IDø25.4, ODø25.4...
7. Installation 7.1. Installation Warning: Install the unit in a location strong enough to withstand its weight. [Fig. 7.1.1] (P.2) Any lack of strength may cause unit to fall down, resulting in a personal injury. Check that the installation leg corners are securely supported to ensure that Have installation work in order to protect against strong winds and the legs do not bend.
- It may also be in violation of applicable laws. ø34.93 ø1-3/8" Type-1/2H or H - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible ø41.28 ø1-5/8" Type-1/2H or H for malfunctions or accidents resulting from the use of the wrong type of refrigerant.
Precautions for heat source unit combinations may cause pipe corrosion and degrade the refrigerant oil. Refer to [Fig. 9.2.3] for the positioning of twinning pipes. Contact Mitsubishi Electric for more details. [Fig. 9.2.3] (P.8) e Never perform piping connections when raining.
10. Additional refrigerant charge At the time of shipping, the heat source unit is charged with refrigerant. 10.1. Calculation of additional refrigerant This charge does not include the total amount necessary for extended piping charge lengths, so an additional charge of each refrigerant line will be required on site.
Limitation of the amount of refrigerant to be charged The above calculation result of the amount of refrigerant to be charged must become below the value in the table below. Heat source unit model P120 P144 P144S P168 P168S P192 P192S Maximum amount of refrigerant kg [LBS]...
N To indoor unit O Heat source unit - It may also be in violation of applicable laws. - MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant.
Insulation for the pipes to be added on site must meet the following 10.4. Thermal insulation of refrigerant piping Heat source unit High-pressure pipe 10 mm [13/32''] or more -BC controller Add insulation to refrigerant piping by covering high-pressure/liquid pipe and low-pressure/gas pipe separately with enough heat resistant polyethylene, so Low-pressure pipe 20 mm [13/16''] or more...
Note: 11.2. Control box and connecting position of wiring 1 Heat source unit 1. Remove the front panel of the heat source unit by unscrewing the screws, Make sure that the spring washers are parallel to the terminal block. and pushing it up, then pulling it out. Make sure that the wires are securely fastened to the terminal screws.
Page 32
2 Wiring examples Controller name, symbol and maximum number of controllers. Name Code Possible unit connections Heat source unit Main unit Sub unit BC controller Main unit One controller for one OC Sub unit Zero, one or two controllers for one OC Indoor unit Indoor unit controller Remote controller...
<Maximum Lengths> 1 ME Remote controller [Fig. 11.3.1] [Fig. 11.3.4] (P.15, 16) Max length via heat source units: L and L and L 500 m [1,640 ft] (1.25 mm Max transmission cable length: L and L and L and L and L 200 m [656 ft] (1.25 mm Remote controller cable length:...
Warning: Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current. Caution: Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric shock.
- Une installation incorrecte par l'utilisateur peut avoir comme conséquence une fuite d'eau, un choc électrique ou un incendie. Mitsubishi Electric sont utilisées, un incendie ou une explosion peut en résulter. Installez l'unité à un endroit qui peut soutenir son poids.
L'installateur et le spécialiste système assureront la sécurité contre les 1.4. Avant l'installation (déménagement) fuites conformément aux normes et règlements locaux. - travaux électriques - Choisissez la taille de câble appropriée et les capacités du commutateur d'alimentation principale indiquées dans le présent manuel si les Attention : règlements locaux ne sont pas disponibles.
2. À propos du produit Cette unité utilise le frigorigène de type R410A. N'utilisez pas la tuyauterie existante, car elle contient du chlore, qui est présent dans l'huile et le frigorigène de machines conventionnelles de Pour les systèmes utilisant le R410A, la tuyauterie peut être différente de celle des systèmes utilisant un frigorigène conventionnel parce que les nouvel équipement.
5. Liste des pièces Reportez-vous à la section 10.2 pour plus d'informations sur les consignes de sécurité. PQHY-P·TLMU-A/YLMU-A Modèle 1 Raccord coudé 2 Raccord coudé 3 Tube de raccord 4 Tube de raccord 5 Tube de raccord 6 Tube de raccord 7 Tube de raccord 8 Embout conique 9 Embout conique D.I.ø25,4,...
7. Installation 7.1. Installation Avertissement : Installez l'unité dans un endroit assez résistant pour soutenir son [Fig. 7.1.1] (P.2) poids. Toute faiblesse de résistance peut faire tomber l'unité et causer des blessures. éviter qu'ils ne se tordent. tremblements de terre. Toute installation incorrecte peut faire tomber l'unité...
8.3. Traitement de l'eau et contrôle de la 8.4. Engrenage des pompes L'appareil risque d'être endommagé s'il est mis en service sans circulation d'eau qualité de l'eau dans les tuyaux. Pour préserver la qualité de l'eau, utiliser une tour de refroidissement de type fermée.
- Cela pourrait également constituer une violation des lois applicables. 4 branches 8 branches 10 branches - MITSUBISHI ELECTRIC CORPORATION ne peut être tenue responsable de CMY-Y104C-G CMY-Y108C-G CMY-Y1010C-G tout dysfonctionnement ou accident résultant de l'utilisation du mauvais type de réfrigérant.
Précautions pour les combinaisons d'unités extérieures Attention : [Fig. 9.2.3] (P.8) <A> N'utilisez pas les outils indiqués ci-dessous qui sont utilisés avec les hauteur du siphon soit de 200 mm [7-7/8 in] ou plus. S'il n'y a aucun siphon, l'huile peut s'accumuler à l'intérieur du tube, frigorigènes conventionnels.
10. Charge supplémentaire de frigorigène Au moment de l'expédition, l'unité extérieure est chargée de frigorigène. Cette 10.1. Calcul de la charge supplémentaire de charge n'inclut pas la quantité totale requise pour l'extension de tuyauterie, de frigorigène sorte qu'une charge supplémentaire de chaque ligne de frigorigène est requise Calculez la quantité...
Restriction de la quantité de réfrigérant à charger Modèle de la source de chaleur P120 P144 P144S P168 P168S P192 P192S Quantité maximale de réfrigérant kg [LBS] 22,0 [49] 28,5 [63] 29,5 [66] 42,0 [93] 42,0 [93] 51,5 [114] 51,5 [114] 53,5 [118] 53,5 [118] Modèle de la source de chaleur...
à vide soit réduite de 130 Pa maximum.) - Cela pourrait également constituer une violation des lois applicables. - MITSUBISHI ELECTRIC CORPORATION ne peut être tenue responsable de tout dysfonctionnement ou accident résultant de l'utilisation du mauvais appropriée de frigorigène pendant le fonctionnement.
Si les tubes sont situés dans un environnement à haute température et 10.4. Isolation thermique de la tuyauterie haute humidité, tel que l'étage supérieur d'un bâtiment, une isolation plus du frigorigène Quand le client présente certaines caractéristiques, assurez-vous qu'elles pression/liquide et basse pression/gaz séparément avec une épaisseur répondent également aux caractéristiques du diagramme ci-dessus.
11.2. Boîtier de commande et emplacement pour le raccordement des câbles 1 Unité extérieure Assurez-vous que les rondelles à ressort sont parallèles au bloc de 1. Retirez le panneau avant de l'unité extérieure en retirant les vis et en le jonction.
Page 51
2 Exemples de câblage Nom du contrôleur, symbole et nombre maximal possible de contrôleurs. Code Connexions d'appareils possibles Unité extérieure Unité principale Unité secondaire Contrôleur BC Unité principale Un contrôleur par OC Unité secondaire Aucun, un ou deux contrôleurs par OC Appareil intérieur Contrôleur de l'appareil intérieur Télécommande...
<Longueurs maximales> 1 Télécommande ME [Fig. 11.3.1] [Fig. 11.3.4] (P.15, 16) Longueur maxi via les appareils extérieurs : L et L et L 500 m [1,640 ft] (1,25 mm Longueur maxi du câble de transmission : L et L et L et L et L 200 m [656 ft] (1,25 mm...
Avertissement : connexions ne sont pas fermement réalisées, un échauffement ou un incendie peut en résulter. Soyez sûr d'utiliser le type approprié de commutateur de protection de surintensité. Notez que la surintensité produite peut inclure une certaine quantité de courant continu. Attention : Certains sites d'installation peuvent requérir la connexion d'un disjoncteur de fuite de terre pour l'inverseur.
Page 56
This product is designed and intended for use in the residential, commercial and light-industrial environment. Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN WT07800X01...