hit counter script
Panasonic PAW-FC Installation And Maintenance Manual
Panasonic PAW-FC Installation And Maintenance Manual

Panasonic PAW-FC Installation And Maintenance Manual

Hide thumbs Also See for PAW-FC:
Table of Contents

Advertisement

INSTALLATION AND
MAINTENANCE MANUAL
"
Original Language"
PAW-FC Fan Coils
Cassette
Read through the Installation Instructions before you proceed with the installation. In particular, you will need to read
under the " IMPORTANT ! " section at the top of the page
.
File name.
IMM_PAW-FC_CAS_EN_06.21
June 2021

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic PAW-FC

  • Page 1 MAINTENANCE MANUAL “ Original Language” PAW-FC Fan Coils Cassette Read through the Installation Instructions before you proceed with the installation. In particular, you will need to read under the “ IMPORTANT ! ” section at the top of the page IMM_PAW-FC_CAS_EN_06.21...
  • Page 2: Table Of Contents

    10. Optional Wired remote controller: PAW-FC-903TC ........23 10.1 Specifications ....................24 10.2 Dimensions ....................24 10.3 Functions ....................24 10.4 Installation ....................25 10.5 Mounting ..................... 25 10.6 Wiring ......................25 10.7 Operation instructions .................. 26 11. Optional Advanced wired remote controller: PAW-FC-RC1 ......27...
  • Page 3 Discrete Input Register ................. 30 12.3 Coils Register ....................31 12.4 Input Register ....................31 12.5 Holding Register ..................31 13. Optional Wired remote controller for EC fan: PAW-FC-907TC ..... 33 13.1 Specifications ....................34 13.2 Dimensions ....................34 13.3 Functions ....................34 13.4...
  • Page 4 IMPORTANT! tubing are completed or reconnected and checked. Highly dangerous electrical voltages are used in this • system. Carefully see the wiring diagram provided with Please Read Before Starting the IMM Manual when wiring. Improper connections This equipment must be installed by the sales dealer or and inadequate grounding can cause accidental injury installer.
  • Page 5: General Recommendations

    It is the installer’s responsibility to contact their pipe supplier and take into account the general instructions CAUTION for the use of plastic pipes. The manufacturer declines any responsibility and the Do not touch the air inlet or the sharp aluminium fins of •...
  • Page 6: Inspection And Storage

    2. Inspection and storage At the time of receiving the equipment carefully cross check and low temperatures). Excessively high temperatures (above all the elements against the shipping documents in order to 60°C) can harm certain plastic materials and cause ensure that all the crates and boxes have been received. permanent damage.
  • Page 7: Presentation

    4. Presentation The range of PAW-FC Fan Coil includes the Cassette (AC / EC) configuration which is available in different sizes. The cooling capacity is from 1,4 to 9,4 kW and the heating capacity is from 1,1 to 14,0 kW.
  • Page 8 − Ensure that a suitable water quality is maintained at all times, because the manufacturer and its representative decline all responsibility in the event of untreated or incorrectly treated water being used. Guidelines for water quality Substance Condition Effects Recommended content No NH ammonium ions in the water, highly detrimental to copper.
  • Page 9: Nomenclature

    4.2 Nomenclature The nomenclature reflects each model’s type, coil configuration, external static pressure configuration, size and service side. Example: PAW-FC Unit type PAW-FC = Fan Coil Unit Number of pipes 2 = 2-pipe configuration 4 = 4-pipe configuration Fan motor type...
  • Page 10: Installation

    PAW- FC2E-U020 FC2E-U030 FC2E-U040 FC2E-U050 FC2E-U060 FC2E-U070 EC fan 2-pipe Lo / Med / Hi 1,6 / 1,8 / 2,4 1,9 / 2,9 / 4,0 2,8 / 3,5 / 4,7 3,4 / 4,4 / 6,1 3,7 / 5,5 / 7,2 4,1 / 6,5 / 9,6 Total cooling capacity Lo / Med / Hi...
  • Page 11: Clearance

    Unit installation will be facilitated using a stacker. Plastic diffuser only: If plaster board ceiling panels are installed the maximum dimensions of the unit housing must not exceed: 660 x 660 mm (mod. PAW-FC**-U020 to PAW-FC**-U040) and; 900 x 900 mm (mod. PAW-FC**-U050 to PAW-FC**-U070).
  • Page 12 Installation Mark the position of the hangers, connection lines and condensate drain pipe, power supply cables and remote control cable (see dimensions); the cardboard template (supplied with the kit) may be of assistance for this operation. Depending on the type of ceiling the hangers can be fixed as shown in the drawing.
  • Page 13: Hydraulic Connections

    An air bleed valve is also provided (See figure), which can be adjusted using an 8 mm wrench. IMPORTANT To make water connections to the heat exchanger or the valves use threaded joints and suitable materials that can ensure perfect tightness. Models PAW-FC**-U020 to PAW-FC**-U040 Models PAW-FC**-U050 to PAW-FC**-U070 2-pipe 4-pipe...
  • Page 14: Installing The 3-Way Regulating Valve - Accessory

    6.2 Installing the 3-way regulating valve - accessory The water flow has to be controlled by installing the motorized thermo-electric valves supplied an accessory or by installing motorized field supplied valves. 2-pipe 4-pipe PAW-FC2*-U020 to PAW-FC2*-U050 to PAW-FC4*-U020 to PAW-FC4*-U050 to Ref.
  • Page 15: Operation Of The Thermo-Electric Valve

    To connect the steel pipes to the system, ensure they are aligned and supported to avoid excess strain on the unit. If the system is filled with water, check all fitting seals. After ending the hydraulic connections, make sure there are no leaks Insulate the valve using the shell, fix it by means of the clips and make sure that all cold parts are insulated (see figure).
  • Page 16: Installation Of The Plastic Diffuser

    maximum height difference of 200 mm from the top of the unit (See figure). IMPORTANT Non-level installation will cause condensate dripping Do not flatten or crush the condensate drain pipe 7. Installation of the plastic diffuser Carefully unpack the assembly and check for damage sustained in transit. Attach the assembly to the unit, fastening it onto its two fixing supports (ref.
  • Page 17: Electrical Connections

    8. Electrical connections WARNING Danger to life from electric shock. Before carrying out any work on the equipment, make sure that the electrical power supply is disconnected and that there is no possibility of the unit being started inadvertently. Non-compliance with the above instructions can lead to injury or death by electrocution. The devices are operated with 230-V alternating voltage.
  • Page 18: Terminal Block

    Neutral Phase Condensate Pump phase Heating Default contact condensate pump Cooling valve 1 – Power supply cable V1, V2, V3 Motor speed 2 – Auxiliary cable Connect power supply L (line), N (neutral) and (earthing) according to the wiring diagram and respect the polarities shown on the bottom of the electrical boxes.
  • Page 19: Connecting A Field-Supplied Controller

    WARNING Daisy chain WARNING: it is forbidden to supply other units from the terminal block. 8.4 Connecting a field-supplied controller When installing a field-supplied controller, keep the following aspects in mind: Make sure the device and the electricity supply are switched off prior to installation / service. −...
  • Page 20: Wiring Diagram - Models Paw- Fc*A-U

    Wiring diagram - Models PAW- FC*A-U*** AC Fan motor Wire colouring code Black Orange Brown Yellow Green Blue Violet Grey White Electrical data - Models PAW- FC*A-U*** PAW- FC*A-U020 FC*A-U030 FC*A-U040 FC*A-U050 FC*A-U060 FC*A-U070 AC fan 2/4-pipe Voltage Power supply Phase Single phase Single phase...
  • Page 21: Wiring Diagram - Models Paw- Fc*E-U

    Wiring diagram - Models PAW- FC*E-U*** EC Fan motor Wire colouring code Black Orange Brown Yellow Green Blue Violet Grey White Electrical data - Models PAW- FC*E-U*** PAW- FC*E-U020 FC*E-U030 FC*E-U040 FC*E-U050 FC*E-U060 FC*E-U070 EC fan 2/4-pipe Voltage Power supply Phase Single phase Single phase...
  • Page 22: Safety Requirements For Electric Appliances

    The following table shows which valve model must be chosen for the relevant Fan Coil Cassette model. Fan Coil Cassette units Valves Model Pipe configuration Size 2-way valve 3-way valve U020 – U040 PAW-FC2-2WY-U020 PAW-FC2-3WY-U020 2-pipe configuration U050 – U070 PAW-FC2-2WY-U050 PAW-FC2-3WY-U050 PAW-FC**-U*** U020 – U040 PAW-FC4-2WY-U020 PAW-FC4-3WY-U020 4-pipe configuration U050 – U070 PAW-FC4-2WY-U050 PAW-FC4-3WY-U050...
  • Page 23: Optional Wired Remote Controller: Paw-Fc-903Tc

    The PAW-FC-903TC thermostat is both easy to operate and install. The devices feature microprocessor-based control and large backlit LCD screens which display operation status (cooling, heating, and ventilation), fan speed, room temperature and set- point.
  • Page 24: Specifications

    10.1 Specifications Built-in sensing element 100 kΩ NTC, type 3 Housing Flame-retardant PC Accuracy ±1 °C Dimensions 86 x 86 x 14.5 mm Set-point range 5 to 35 °C (3.40” x 3.40” x 0.57”) 0 to 50 °C (shown in 0.5 °C Display range Wall box BS wall box, min.
  • Page 25: Installation

    10.4 Installation − Install the thermostat about 1.5 m (59”) above the floor. In the event that the controller is intended for use by wheelchair users, please refer to local regulations Make sure the device is powered off prior to installation/service −...
  • Page 26: Operation Instructions

    10.7 Operation instructions The meaning of each key is shown below. On/Off M - Mode selection Down Fan speed / Eco Mode Power On/Off automatically set to 16 °C with the fan running at low speed. A short press of the On/Off button will turn the power on. When the key card is returned to the reader, the indoor Another short press of the On/Off button will turn off the power, display and ECO...
  • Page 27: Optional Advanced Wired Remote Controller: Paw-Fc-Rc1

    11. Optional Advanced wired remote controller: PAW-FC-RC1 PAW-FC-RC1 is a 230 VAC electronic fan-coil thermostat for room temperature control. It is suitable for every kind of building where reduced energy consumption and high comfort need to be met. The ability to switch between control modes depending on occupancy, makes it particularly suitable for public spaces, such as hotel rooms, offices, schools, hospitals, etc.
  • Page 28: Dimensions

    11.2 Dimensions 11.3 Functions The room thermostat regulates heating and/or cooling in a room via digital outputs on/off for valves and for 3-speed fan control. The touch screen shows the actual operating state and is also used to access all parameters, such as setpoint, hysteresis, fan speed etc. The unit has a built-in room temperature sensor.
  • Page 29: Settings

    The thermostat can be in one of the following states: Off: Energy stop state where the Occupied: Comfort (Standard) state Standby: Energy saving state where controller neither heats nor cools. No or if a presence detector is connected reduced heating or cooling takes background light is lit, only the On/Off and someone is in the room.
  • Page 30: Error Messages

    Error: short circuit or open connection at AI Check the cable between controller AI and the sensor 12. Modbus communication protocol PAW-FC-RC1 The Modbus protocol is a general-purpose protocol for data exchange between for instance control units, Building Management Systems, instruments and electricity meters. It’s an asynchronous, serial Master Slave protocol. It’s widely used, well documented and simple to understand.
  • Page 31: Coils Register

    12.3 Coils Register Variable address Description Minimum fan speed. The fan runs at least at speed 1, except in Off state. 0 = Not Active 1 = Active Mould protection 0 = Not Active 1 = Active Not used NC/NO for terminal DI 0 = NO 1 = NC 11-14 Not used...
  • Page 32 Default Variable address Description Unit Scale value value value Change-over mode (0-3) and fan release function (4-7) via heat pump supply sensor 0 = Manual setting in display 1 = Manual Heat 2 = Manual Cool 3 = Automatic via analog or digital input 4 = manual setting in the display via button 5 = Manual Heat 6 = Manual Cool 7 = Automatic via digital input DI...
  • Page 33: Optional Wired Remote Controller For Ec Fan: Paw-Fc-907Tc

    1 = 9600 bps 2 = 19200 bps 3 = 38400 bps 13. Optional Wired remote controller for EC fan: PAW-FC-907TC The PAW-FC-907TC thermostat is optimized for office building, hotel, hospital and residential applications. It can be used for 2-pipe or 4-pipe applications and is available in a housing finish with white glass display with mechanical buttons on a white base.
  • Page 34: Specifications

    13.1 Specifications Built-in sensing element 100 kΩ NTC, type 3 Housing Flame-retardant PC Accuracy ±1 °C Dimensions 86 x 86 x 14.5 mm Set-point range 5 to 35 °C (3.40” x 3.40” x 0.57”) 0 to 50 °C (shown in 0.5 °C Display range Wall box BS wall box, min.
  • Page 35: Installation

    13.4 Installation − Install the thermostat about 1.5 m (59”) above the floor. In the event that the controller is intended for use by wheelchair users, please refer to local regulations Make sure the device is powered off prior to installation/service −...
  • Page 36: Operation Instructions

    RS-485 connection, allowing for the transfer of established serial communication protocol used in building real-time data. automation. The support of Modbus communication allows The RS-485 communication parameters can be adjusted as simple integration of the PAW-FC-907TC with a building follows: management system using...
  • Page 37 Connection to the RS-485 network is made via dedicated terminals on the back of the thermostat and marked A (+) and B (-). The following Modbus register types and formats are supported: Code Register Type Data Format Read coils Boolean Binary/digital Read discrete inputs Boolean...
  • Page 38 0 = Disable Auto fan 1 = Enable 00 = Room temp. Display temperature 01 = Set-point 00 = Built-in sensor Temperature sensor 01 = External sensor 0 - Disable Modbus connection 1 - Enable Modbus address setting 1 to 64 00 = 4800 bps 01 = 9600 bps Modbus baud rate...
  • Page 39: Commissioning

    15. Commissioning 15.1 Performing pre-start checks Once all components have been installed, you can start commissioning by performing the prestart checks. CHECKING HYDRAULIC INSTALLATION CHECKING ELECTRICAL INSTALLATION The electrical installation has been carried out The water inlet and outlet connections are correctly according to the applicable local electrical code and connected to the unit the wiring diagram for the relevant model...
  • Page 40 Carry out a visual inspection of the complete installation in service. − Check and ensure the general cleanness of the installation. − Check the condition of the condensate tray by pulling it out of the casing, and ensure that the condensate evacuation pipe −...
  • Page 41 CAUTION: Securely isolate the power before performing the following operations. Check that the main power supply cable is not damaged or altered in such a way as to affect the insulation. Check the tightness of the screw terminals. Check the general tightness of all cable connections. Perform a visual check of the condition of the contacts.
  • Page 42 APPENDIX −−−−− Contents −−−−− Dimensions......................43 Hydraulic connections .......... Errore. Il segnalibro non è definito.
  • Page 43: Dimensions And Weights

    Dimensions and weights Unit dimensions Models PAW- FC**-U020 to PAW- FC**-U040 Unit dimensions Models PAW- FC**-U050 to PAW- FC**-U070 Weights PAW- FC**-U020 PAW- FC**-U030 PAW- FC**-U040 PAW- FC**-U050 PAW- FC**-U060 PAW- FC**-U070 2-pipe [Kg] 14,8 16,5 16,5 37,1 37,1 39,6 Weight of base unit (without valve) 4-pipe [Kg]...
  • Page 44: Information Requirements For Fan Coil Units

    European Parliament and of the Council establishing a framework for the setting of ecodesign requirements for energy-related products, with regard to ecodesign requirements for air heating products, cooling products, high temperature process chillers and fan coil units. Fan speed Medium High setting Unit PAW-FC- dB(A) dB(A) dB(A) 2A-U020 1,29 0,25...
  • Page 45 Notes ......................
  • Page 46 Notes ......................
  • Page 47 Notes ......................
  • Page 48 Panasonic Appliances Air-Conditioning Europe a division of Panasonic Marketing Europe GmbH Hagenauer Strasse 43, 65203 Wiesbaden, Germany IMM_PAW-FC_CAS_EN_06.21 Panasonic. June 2021 www.aircon.panasonic.eu...

Table of Contents