hit counter script

Fan Control; Function Principle; Activating The Vsd / Pwm Fan - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

96/213
Building Technologies
HVAC Products

11 Fan control

11.1 Function principle

Optionally, the LMV37.4... system can be operated with a VSD or PWM fan. Control is
accomplished via a DC 0...10 V interface. For control of the fan's speed, a safety-
related speed feedback signal is required. With pneumatic air-fuel ratio control, the
speed feedback signal is not evaluated. To facilitate the use of fans with different speed
ranges, the fan's speed is standardized between 0...100%. If a fan control is not con-
nected, a power output and, alternatively, a fuel meter output are available (refer to
chapter Power output X74.3 and chapter Fuel meter input X75.1 / X75.2 ).
LMV...
5
4
3
2
1
Bild 332e/0409
Figure 45: Function principle of VSD

11.2 Activating the VSD / PWM fan

The VSD can be activated in any of the operating modes (P201).
No.
Parameter
Activation of VSD / PWM fan
542
0 = inactive
1 = active
Note
For configuration of the analog output when the VSD is activated, refer to chapter
Power output X74.3 !
Basic documentation LMV37.4...
11 Fan control
5
Actual speed
4
3
2
1
Sensor disk
FU
Or
PWM
Sensor
L
CC1P7546en
01.12.2009

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv37.400a1Lmv37.400a2Lmv37.420a1

Table of Contents

Save PDF