Page 1
AIR CONDITIONER Ceiling type SERVICE MANUAL INDOOR ABYG36KRTA ABYG45KRTA OUTDOOR AOYG36KBTB AOYG45KBTB SR_AB004EF_01 2020.01.07...
Page 2
• Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google Inc. ®...
Page 3
CONTENTS 1. GENERAL INFORMATION 2. TECHNICAL DATA AND PARTS LIST...
Page 5
1. GENERAL INFORMATION 2020.01.07 SR_CH01_AB004EF_01...
1. Specifications 1-1. Indoor unit Ceiling Type Inverter heat pump Model name ABYG36KRTA ABYG45KRTA Power supply 230 V ~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V 12.1 Rated Btu/h 32,400 41,300 Cooling 2.8—11.2 4.0—13.5 Min.—Max.
Page 8
Specifications for ErP Lot10 Model name ABYG36KRTA Cooling Energy efficiency class Heating (Average) Cooling 9.5 (35°C) Pdesign Heating (Average) 8.7 (-10°C) SEER Cooling 6.37 kWh/kWh SCOP Heating (Average) 4.21 Annual energy consump- kWh/a tion QHE (Average) 2,904 Cooling Sound power level...
1-2. Outdoor unit Type Inverter heat pump Model name AOYG36KBTB AOYG45KBTB Power supply 230 V ~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Starting current 13.0 18.6 Cooling 3,750 4,450 Airflow rate Heating 3,750 4,450 Type ×...
2. Dimensions 2-1. Indoor unit ¢ Models: ABYG36KRTA and ABYG45KRTA Unit: mm 1,700 1,543 49 84 125 103 Side view Top view ø100-mm hole Rear view Suspension bolt pitch 1,543 Dimensions (Space required for installation) Indoor unit (Top view) The length of the bolt here is 30 mm.
Page 11
Installation space requirements Unit: mm Ceiling Indoor unit 30 or more Ceiling 200 or more 0 or more Obstruction Floor Required ceiling height varies according to the ceiling mode setting of function setting No. 20. Ceiling height Ceiling mode Standard High ceiling - (01-5) -...
2-2. Outdoor unit ¢ Model: AOYG36KBTB Unit: mm 35.7 Top view 3 Way valve (Liquid) 3 Way valve (Gas) 25 67 Ф28: Cable port Pipe port Ф28: Cable port Ф28: Cable port Ф28: Cable port Ф28: Cable port Ф28: Cable port Pipe port Pipe port Front view...
Page 13
¢ Model: AOYG45KBTB Unit: mm 35.7 Top view 3 Way valve (Liquid) 3 Way valve (Gas) 129.1 Pipe port Ф28 Ф28 85.3 Cable port Pipe port Ф28: Cable port Cable port Pipe port Pipe port Pipe port Front view Side view Rear view 62.6 15.2...
Page 14
- (01-8) - 2-2. Outdoor unit 2. Dimensions...
Page 15
2. TECHNICAL DATA AND PARTS LIST 2020.01.07 SR_CH02_AB004EF_01...
Page 16
CONTENTS 2. TECHNICAL DATA AND PARTS LIST 1. Precautions....................02-1 2. Indoor unit parts list..................02-2 2-1. Models: ABYG36KRTA and ABYG45KRTA ..............02-2 3. Outdoor unit parts list.................02-4 3-1. Model: AOYG36KBTB ....................02-4 3-2. Model: AOYG45KBTB ....................02-8 4. Accessories ....................02-12 4-1. Indoor unit ........................02-12 4-2.
• Service parts information and design are subject to change without notice for product improve- ment. • For the latest information of the service parts, refer to our Service Portal. https://fujitsu-general.force.com/portal/ • Precise figure of the service parts listed in this manual may differ from the actual service parts. - (02-1) -...
2. Indoor unit parts list 2-1. Models: ABYG36KRTA and ABYG45KRTA ¢ Chassis - (02-2) - 2-1. Models: ABYG36KRTA and ABYG45KRTA 2. Indoor unit parts list...
Page 19
♦ 9900892029 Thermistor (Pipe) ♦ 9384287007 Evaporator total assy ♦ 9384364005 Drain pan total assy (4-fan) ♦ 9358746004 Drain cap ♦ 9384241009 Front panel (4-fan) assy ♦ - (02-3) - 2-1. Models: ABYG36KRTA and ABYG45KRTA 2. Indoor unit parts list...
3. Outdoor unit parts list 3-1. Model: AOYG36KBTB ¢ Exterior parts and chassis - (02-4) - 3-1. Model: AOYG36KBTB 3. Outdoor unit parts list...
Page 21
Item no. Part no. Part name Service part 9383880001 Top panel assy ♦ 9383779008 Protective net ♦ 9375361013 Net rubber ♦ 9900984038 Thermistor (Heat exchanger) ♦ 9900727154 Thermistor assy ♦ 9383607004 Thermo holder ♦ 9383874000 Right panel sub assy ♦ 9383879005 Rear pipe cover ♦...
Page 22
¢ Compressor - (02-6) - 3-1. Model: AOYG36KBTB 3. Outdoor unit parts list...
Page 23
Item no. Part no. Part name Service part 9380516064 S-ABS (top) ♦ 9900565091 Thermistor (Outdoor temp.) ♦ 9900186029 Pressure switch ♦ 9374425631 4-way valve assy ♦ 9970194016 Solenoid ♦ 9970158018 Sensor ♦ 9375250140 Accumulator assy ♦ 9970209000 Expansion valve coil ♦...
3-2. Model: AOYG45KBTB ¢ Exterior parts and chassis - (02-8) - 3-2. Model: AOYG45KBTB 3. Outdoor unit parts list...
Page 25
Item no. Part no. Part name Service part 9383880001 Top panel assy ♦ 9381013005 Protective net ♦ 9375361013 Net rubber ♦ 9900984038 Thermistor (Heat exchanger) ♦ 9900727154 Thermistor assy ♦ 9383607004 Thermo holder ♦ 9383874017 Right panel sub assy ♦ 9383879005 Rear pipe cover ♦...
Page 26
¢ Compressor - (02-10) - 3-2. Model: AOYG45KBTB 3. Outdoor unit parts list...
Page 27
Item no. Part no. Part name Service part 9380516019 S-ABS (top) ♦ 9900565091 Thermistor (Outdoor temp.) ♦ 9900186029 Pressure switch ♦ 9374425624 4-way valve assy ♦ 9970194016 Solenoid ♦ 9970158018 Sensor ♦ 9375250133 Accumulator assy ♦ 9970209000 Expansion valve coil ♦...
4. Accessories 4-1. Indoor unit ¢ Models: ABYG36KRTA and ABYG45KRTA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Insulation Operating manual Drain hose (CD-ROM) Installation manual Hose band Template Cable tie (large) M10 nut A Cable tie (small)
5. Optional parts 5-1. Indoor unit ¢ Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD Wired remote panel. Backlit LCD enables easy UTY-RNRYZ* controller operation in a dark room. Wire type: Non-polar 2-wire High visibility and easy operation. Room temperature can be accurately Wired remote controlled using the built-in thermo...
Page 30
¢ Others Exterior Part name Model name Summary Optional drain lift-up mechanism Drain pump unit UTR-DPB24T allows more flexible installation. For piping direction other than right- rear piping. Auxiliary pipe UTP-FX24A assembly • For gas: 6.35 mm (1/4 in) • For liquid: 12.70 mm (1/2 in) For piping direction other than right- rear piping.
Page 31
Exterior Part name Model name Summary For connection between indoor unit KNX converter UTY-VKSX with UART interface and a KNX open network. This converter is required when Split system UTY-VTGX connecting single split system to VRF converter network system. Split system This converter is required when converter UTY-VTGXV...