Panasonic 4414 Quick Start Manual

Panasonic 4414 Quick Start Manual

Fire alarm systems address setting tool

Advertisement

Quick Links

Fire Panels - Accessories
Fire Alarm Systems Address Setting Tool
Model 4414
Used for COM loop address and mode settings
COM loop address setting
Address setting tool 4414 is used to set the COM loop
unit's address (001-255) on the analogue detector types
33xx / 430x / 440x and all other addressable COM loop
units (33xx / 43xx / 44xx).
Mode setting
The address setting tool 4414 is also used to set the
COM loop unit's mode:
M0 = NORMAL mode
M1 = 2330 mode (COM loop address 001-127)
M2 = 2312 mode (COM loop address 001-127)
M3 = Advanced mode See instructions for the COM loop
unit respectively.
Connection cable
Some units have flying leads and some units only screw
terminals. A connection cable with insulated crocodile
clips and push-on terminals is supplied with the address
setting tool, to be used for the COM loop units that
cannot be plugged directly on the tool.
Product applications
Used for address and mode settings when analogue
detectors and other addressable COM loop units are to
be used in the systems FT128V2 and FT1020G3.
4414 has to be used to set the analogue detectors 440x
in Advanced mode.
 
Fire System Technology
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior
Sydney
-
Melbourne
 
-
Adelaide
-
Brisbane
User friendly
The address setting tool is powered by four 1.5 V Alkaline
batteries (LR6 / AA). Battery life time is approx. 250 hours or
up to 50000 readings / writings.
An analogue detector's contact pins (SA / SB) are plugged into
the address setting tool's snap connectors (SA / SB). The
connection cable is used to connect to other units.
The tool is turned on by the On/Off / CLR button. "MØ" and a
blinking cursor will be shown in the display.
How to read:
Turn on the tool.
Press the Read button.
Wait for a beep ("READ" will be shown in the display).
"OK", the address and the mode will be shown in the display.
How to write:
Turn on the tool.
Default mode is M0 (NORMAL mode). The mode can be
changed by pressing the Write and Read buttons at the same
time and then select a mode (0-3).
Type the COM loop address (001-255)
Press the Write button.
Wait for a beep ("WRITE" will be shown in the display).
"OK", the address and the mode will be shown in the display.
Write the COM loop address on the Address label on the COM
loop unit respectively.
If the tool is not used for approx. 20 seconds, it will be
automatically turned off in order to save the batteries
Australia
Head Office: 4 Pike Street Rydalmere NSW 2116
Ph+61 2 9684 1466 Fx+61 2 9684 4146
New Zealand
Unit 106, The Zone, 23 Edwin Street Mount Eden
1024
Ph+64 9 638 4644 Fx+64 9 6384645
Web:
www.brooks.com.au (Aus) www.brooks.co.nz (NZ)
-
Perth
-
Hobart
-
.
Toll Free
1300 78 FIRE
Toll Free
0800 220 007
DS4414 10/11/14
notice.
Darwin
-
New Zealand
fire products and solutions

Advertisement

loading

Summary of Contents for Panasonic 4414

  • Page 1 COM loop address setting The address setting tool is powered by four 1.5 V Alkaline Address setting tool 4414 is used to set the COM loop batteries (LR6 / AA). Battery life time is approx. 250 hours or unit's address (001-255) on the analogue detector types up to 50000 readings / writings.
  • Page 2 Address setting tool (incl. connection cable but excl. batteries) 3315 Connection cable for Address setting tool 4414 (spare part) Left: An analogue detector is plugged into the address setting tool's snap connectors. Right: Connection cable, to be used when required.