Summary of Contents for Siemens Flowrite 599 Series
Page 1
Maintenance-free Application These electronic actuators are designed to be used with Flowrite 599 Series valves with either 3/4-inch (20 mm) stroke (SKB/D) or a 1-1/2 inch (40 mm) stroke (SKC) in liquid and steam service applications; or other manufacturer's valves with appropriate Universal Valve Linkage Kits.
Page 2
Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Document Number 155-717 September 25, 2018 Product Numbers Table 1. Product Numbers. Actuator Order Number Stroke SKB62UA 3/4-inch (20 mm) SKD62UA 1-1/2 inch (40 mm) SKC62UA Warning/Caution Notations...
Page 3
Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions Document Number 155-717 September 25, 2018 Terminal Y Signal Inputs Voltage 0 to 10 Vdc Input impendence 100K ohm Current 4 to 20 mA Input impedance 240 ohm Signal resolution <1%...
Page 4
Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Document Number 155-717 September 25, 2018 Materials Miscellaneous Actuator housing and bracket Die-cast aluminum Housing box and manual adjustor Plastic Conduit opening 1/2-inch NPSM Dimensions See Figure 23, Figure 24, Figure 25 and Figure 26.
Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions Document Number 155-717 September 25, 2018 Accessories, 599-10071 The SKD actuator is UL listed to Continued meet NEMA TYPE 3R requirements (a degree of protection against rain, sleet, and damage...
Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions Document Number 155-717 September 25, 2018 Mounting and The vertical position is the recommended position for mounting and the only position for NEMA Type 3R rating with the Weather Shield. Acceptable mounting positions are shown Installation in Figure 10.
Page 8
Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Document Number 155-717 September 25, 2018 Stroke Calibration To determine the stroke positions 0% and 100% in the valve, calibration is required when the valve/actuator are commissioned for the first time. The actuator must be mechanically connected to a valve and must have a supply voltage of 24 Vac.
Page 9
Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions Document Number 155-717 September 25, 2018 Start-up, Continued Advanced Features Figure 13. DIP Switches. DIP Switches Select Sequence Control Selection of Selection of (From Left to Right) Direction of...
Page 10
Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Document Number 155-717 September 25, 2018 • With normally-closed valves, "direct-acting" means that with a 0 Vdc signal input, the valve Start-Up, is closed. continued • With Normally-open valves, "direct-acting" means that with a 0 Vdc signal input, the valve is open.
Page 11
Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions Document Number 155-717 September 25, 2018 Start-up, continued When actuator pressure cylinder: Moves outward (0 to 1): Valve opens. Normally Closed Valve Moves inward (1 to 0): Valve closes.
Page 12
Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Document Number 155-717 September 25, 2018 Start-up, Continued When returning to automatic control, you must turn the crank arm of the manual setting knob counterclockwise until the red numbers disappear. It is essential that the Automatic Operation window is clear and the crank arm is snapped into position.
Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions Document Number 155-717 September 25, 2018 Wiring Do not use auto-transformers. Use earth ground isolating step-down Class II power supplies. Determine supply transformer rating by summing total VA of all actuators used.
Page 14
Technical Instructions Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Document Number 155-717 September 25, 2018 Wiring Diagrams, Continued System neutral (SN) red System potential (SP) black 24 Vac/30W Figure 21. Figure 22. Auxiliary Switch Stem Heating Element ASC1.6.
Page 15
Flowrite 599 Series SKB/C/D 62UA Electronic Valve Actuator Advanced Features Technical Instructions Document Number 155-717 September 25, 2018 Dimensions, Continued Figure 24. Dimensions of 599-10071 SKD Weather Shield in Inches (Millimeters). Figure 25. Dimensions of SKB/C Weather Shield, 599-10071 in Inches (Millimeters).
Page 16
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Flowrite is a trademark of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners.