hit counter script

Electrical Data - Siemens SCALANCE X-200 Operating Instructions Manual

Simatic net, industrial ethernet switches
Hide thumbs Also See for SCALANCE X-200:
Table of Contents

Advertisement

Type
Connectors for end devic-
es or network compo-
nents via twisted pair
RJ-45 jacks with MDI X
pinning
10/100 Mbps half / full
duplex
X201-3P IRT PRO
X202-2P IRT PRO
X204IRT PRO
Signaling contact
The following applies to all devices:
● Voltage for the signaling contact: 24 VDC
● Current through the signaling contact: maximum 100 mA

Electrical data

Type
Supply voltage with re-
dundant connection
Rated voltage 12 to 24
VDC SELV
Voltage range 10 VDC to
28.8 VDC
Permitted voltage range
incl. total ripple 10 VDC to
30.2 VDC
X204-2TS
X204-2LD TS
Type
Supply voltage with re-
dundant connection
Rated voltage 24 VDC
Voltage range 19.2 VDC
to 28.8 VDC
Permitted voltage range
incl. total ripple 18.5 VDC
to 30.2 VDC
X204-2
X204-2FM
X204-2LD
X206-1
X206-1LD
X208
X208PRO
X212-2
X212-2LD
SCALANCE X-200
Operating Instructions, 03/2015, C79000-G8976-C284-06
Connections for end
devices or network com-
ponents via FO cable
SC RJ jacks (push-pull),
100 Mbps, full duplex to
100BaseFX
1
3
2
2
4
Power loss at 12 VDC
+
6.60 W
+
6.60 W
Power loss at 24 VDC
+
6.36 W
+
6.36 W
+
6.36 W
+
5.28 W
+
5.28 W
+
3.84 W
+
4.4 W
+
7.92 W
+
7.92 W
Connector for power
supply
5-pin Power Plug PRO
connector (male)
2
2
-
2
Current consumption at
rated voltage
600 mA
600 mA
Current consumption at
rated voltage
265 mA
265 mA
265 mA
220 mA
220 mA
185 mA
185 mA
330 mA
330 mA
Technical specifications
Connector for signaling
contact
5-pin b-coded M12 con-
nector (male)
1
1
1
Overcurrent protection at
input
Non-replaceable fuse (F)
3.0 A / 32 V
3.0 A / 32 V
Overcurrent protection at
input
PTC resettable fuse
600 mA / 60 V
600 mA / 60 V
600 mA / 60 V
600 mA / 60 V
600 mA / 60 V
600 mA / 60 V
600 mA / 60 V
1.1 A / 33 V
1.1 A / 33 V