1MRK 502 048-UUS A
17.4
17.4.1
Technical manual
More than one input may be activated at the same time. In such cases the lower order
setting group has priority. This means that if for example both group four and group two
are set to be activated, group two will be the one activated.
Every time the active group is changed, the output signal GRP_CHGD is sending a pulse.
This signal is normally connected to a SP16GGIO function block for external
communication.
The parameter MaxNoSetGrp defines the maximum number of setting groups in use to
switch between.
ANSIC09000063 V1 EN
Figure 303:
Connection of the function to external circuits
The above example also shows the five output signals, GRP1 to 4 for confirmation of
which group that is active, and the GRP_CHGD signal which is normally connected to a
SP16GGIO function block for external communication to higher level control systems.
Test mode functionality TESTMODE
Identification
Function description
Test mode functionality
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1
IOx-Bly1
Æ
IOx-Bly2
Æ
IOx-Bly3
Æ
IOx-Bly4
Æ
IEC 61850
IEC 60617
identification
identification
TESTMODE
Section 17
Basic IED functions
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
GRP4
ACTGRP4
GRP_CHGD
ANSI09000063_1_en.vsd
ANSI/IEEE C37.2
device number
-
-
679