Repair the product or products dealt with in this service information by anyone else could result in serious injury or death 2016 (Qingdao Haier Air Conditioner General corp. , Ltd) All rights reserved. Unauthorized copying and distribution is a violation of law...
Introduction 1 Introduction 1.1 Model name explanation Apply toT1; 220~240V50HZ/1ph Heat pump & R410A refrigerant Version number District Platform of outdoor units:G Platform Nominal cooling capacity (24000BTU/h) Type of outdoor unit : U (normal type) The maximum combination number Domestic air conditioner...
Introduction 1.2 Safety Cautions Be sure to read the following safety cautions before conducting repair work. The caution items are classified into “Warning” and “Caution”. The “Warning” items are especially important since they can lead to death or serious injury if they are not followed closely. The “Caution” items can also lead to serious accidents under some conditions if they are not followed.
Introduction Warning Do not repair the electrical components with wet hands . Working on the equipment with wet hands can cause an electrical shock Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock.
Page 6
Introduction Warning Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire. Be sure to use the specified cable to connect between the indoor and outdoor units.
Introduction Caution Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks. Do not install the equipment in a place where there is a possibility of combustible gas leaks. If a combustible gas leaks and remains around the unit, it can cause a fire.
Introduction Caution Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, fire or an electrical shock. If the installation platform or frame has corroded, replace it.
Specification 2 Specifications NOMINAL DISTRIBUTION SYSTEM VOLTAGE Phase Frequency Voltage NOMINAL CAPACITY and NOMINAL INPUT cooling heating Capacity rated Btu/h 23210 24580 Power Consumption(Rated) 2.11 1.99 EER/COP 3.22 3.62 Moisture Removal m³/h 2.8*10 ³ TECHNICAL SPECIFICATIONS-UNIT Dimensions H*W*D 860×308×730 Packaged H*W*D 995×420×815 Dimensions...
Page 10
Specification TECHNICAL SPECIFICATIONS-OTHERS Refrigerant type R410A Refrigerant charge Refrigerant Maximum allowable distance circuit between indoor an outdoor Maximum allowable level difference Refrigerant control Capillary liquid 6.35 Piping connections 15.88 (external diameter) drain Heat insulation type Both liquid and Gas pipes Max.
Service diagnosis 8 Service Diagnosis 8 .1 Caution for Diagnosis The operation lamp flashes when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation.
Service diagnosis 8.3 Problem Symptoms and Measures Symptom Check Item Details of Measure Check the power supply. Check to make sure that the rated voltage is supplied. None of the units operates Check the indoor PCB Check to make sure that the indoor PCB is broken Operation A power failure of 2 to 10 cycles can stop air conditioner Check the power supply.
Service diagnosis 8.4Codes and Description 8.4.1Problem Symptoms and Measures Symptom Check Item Details of Measure Check to make sure that the rated voltage is Check the power supply. None of the units supplied. operates Check the indoor PCB Check to make sure that the indoor PCB is broken Equipment operates but does Diagnosis...
Service diagnosis Check the connector connection. Correct the connection Is it normal? Thermistor resistance check Replace the thermistor Is it normal? Replace the indoor unit PCB Thermistor resistance check method: Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester. The relationship between normal temperature and resistance is shown in the value of indoor thermistor.
Service diagnosis 8.4.2.3 Indoor AC fan motor malfunction Indoor Display The rotation speed detected by the Hall IC during fan motor operation is used to determine Method of abnormal fan motor operation Malfunction Detection when the detected rotation feedback signal don’t received in 2 minutes Malfunction Detection Conditions...
Performance Curves Diagram 9 Performance Curves Diagram 9.1 Cooling capacity-temperature curves performance curves cooling value-temerature table outdoor tem p.(hum idity 46% ) indoor tem p. D B /W B 18 ℃ 20 ℃ 25 ℃ 32 ℃ 35 ℃ 40 ℃ 43 ℃...
Page 21
Performance Curves Diagram 9.2 heating capacity-temp.curves performance curves heating capacity and indoor/outdoor temp.table indoor tem p.(hum idity 46% ) outdoor tem p. D B /W B 15 ℃ 20 ℃ 25 ℃ -15 ℃ 4034 3586 3148 -5 ℃ 6270 5678 4963 5 ℃...
Page 22
Performance Curves Diagram 9.3 Coolin g power consumption-temp.curves power consumption value-temp.table indoor tem p. outdoor tem p.(hum id ity 46% ) D B /W B 18 ℃ 20 ℃ 25 ℃ 32 ℃ 35 ℃ 40 ℃ 43 ℃ 46 ℃ 1707 1801 1895...
Page 23
Performance Curves Diagram 9.4 heating power consumption-temp.curves p e rfo rm a n ce cu rve s p o w e r co n su m p tio n va lu e -te m p .ta b le in d o o r te m p .(h u m id ity 4 6 % ) o u td o o r te m p .
Page 24