PRODUCT SETUP
For a Configurable Report to operate, its members must be selected (that is, its data set configured) and a client must open
a connection to, configure, and enable its report control block. Control blocks and data sets can be pre-configured by
sending the B30 a CID file. See the UR Family Communications Guide for details. EnerVista UR Setup also can be used to
select the data set members and to pre-configure the control blocks.
Each buffered report has the following settings.
Buffered Report1 RptID
Range: 0 to 129 VisibleString characters
Default: empty string
The name of the report. The entered value sets the RptID value in Buffered Report1 messages, and it can be used by the
client to discriminate Buffered Report1 messages from other messages. If the number of characters entered is zero, the
value used for RptID in messages is an ObjectReference to the report's control block, that is, "<LDName>/
LLN0$BR$"BRCB01".
Buffered Report1 Name
Range: 0 to 32 VisibleString characters
Default: BRCB01
The entered value sets the report control block name value for Buffered Report1.
Buffered Report1 DatSet
Range: None, TT6DataSet1, TT6 DataSet2, ..., TT3DataSet01, TT3DataSet02, ...
Default: None
This setting selects the data set whose members' status is reported in Buffered Report1 messages using the UR Setup
software designator for the data set. The IEC 61850 name of the data sets are configured in the Datasets panel, as
described later.
5
An ObjectReference to the data set, which consists of the concatenation of the string "<LDName>/LLN0$" and the data
set name, is used in the datSet field of report messages, and it can be used by the client to discriminate Buffered Report1
messages from other messages.
The performance of the report is determined by the performance of the selected dataset. When the selection is
TT3DataSet01, TT3DataSet02, ... it is possible that transient events can be missed.
To configure a DataSet, select it at the top of the window from the drop-down list, for example DataSet02 shown in the
previous figure. In the lower part of the window, drag and drop configuration items to the right side. For example select
the ST Ind001 stVal item and drag it to DataSet Member 1. Dataset members configured here affect other Report or
TxGOOSE control blocks that use the same DataSet.
Buffered Report1 ConfRev
Range: 0 to 4294967295 in steps of 1
Default: 1
The entered value sets the confRev value in Buffered Report1 messages, and it can be used by clients to discriminate
report messages of the expected configuration revision from messages of a different revision. The standard requires
that confRev be incremented each time the members or the order of the members is changed, and each time the data
set name is changed. The standard states that the value of 0 is reserved.
Buffered Report1 OptFlds
Range: The check box for each individual bit can be enabled or not (see figure)
Default: All bits enabled/ true
The OptFlds setting is bitstring that controls which of the optional fields are included in report messages. The figure
shows the available option bits. To reduce message size, uncheck any fields that are not needed.
5-68
CHAPTER 5: SETTINGS
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL