hit counter script

Relay Self-Tests - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

CHAPTER 7: COMMANDS AND TARGETS

7.2.2 Relay self-tests

7.2.2.1 Description
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major
and minor) are listed in the following tables. When either type of error occurs, the Trouble LED Indicator turns on and a
target message displays. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
key, providing the condition is no longer present.
RESET
Major self-test errors also result in the following:
The critical fail relay on the power supply module de-energizes
All other output relays de-energize and are prevented from further operation
The faceplate In Service LED indicator turns off
A RELAY OUT OF SERVICE event is recorded
7.2.2.2 Major self-test error messages
The major self-test errors are outlined in this section.
MODULE FAILURE___:
Contact Factory (xxx)
Latched target message: Yes.
Description of problem: Module hardware failure detected.
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
module (for example, F8L).
INCOMPATIBLE H/W:
Contact Factory (xxx)
Latched target message: Yes.
Description of problem: One or more installed hardware modules is not compatible with the C30 order code.
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
module (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
Latched target message: No.
Description of problem: The configuration of modules does not match the order code stored in the C30.
How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five
seconds.
What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail
Latched target message: No.
Description of problem: A FlexLogic equation is incorrect.
How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified
What to do: Finish all equation editing and use self tests to debug any errors.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
TARGETS MENU
7
.
7-5

Advertisement

Table of Contents
loading