FLEXLOGIC DESIGN AND MONITORING USING ENGINEER
Timing
Timing Information can be displayed in the monitoring window. This timing information is only an approximate
representation of how Engineer sees transitions. Use the device's Event Record to view accurate timing information.
The timing information can also be streamed to a comma-separated values (CSV) spreadsheet.
The timing information displayed and recorded can be filtered based on six categories. If a category is not selected, any
timing information related to that category does not display and is not recorded to the CSV file.
Show Timing Information in Output Window — Enable to display times in the monitoring window.
Because of the update rate of the Logic Monitoring, the timing information cannot be used as an accurate representation
of the events that occur within the relay. Use instead the device's event record. Timing information can be delayed by 30
seconds.
Save Timing Information to CSV File — Enable to write timing information in a spreadsheet. The timing information is
recorded in a text file that uses commas to separate each of the fields. This file uses the extension CSV that is supported by
any spreadsheet application.
Every change written to the CSV file requires a timestamp.
The format for the timing information in the output window is as follows:
yyyy/mm/dd hh:dd:ss
4
devicename offline
yyyy/mm/dd hh:dd:ss
devicename ONLINE
yyyy/mm/dd hh:dd:ss
VO1: Virt Out 1- 0
VI4: Virt In 4- 1
DI3: Direct In 3- 0
RI2: Remote In 2- 1
H5a: Contact In 1- 1
H1: Contact Output 1- 0
Data is only appended to the CSV file. The format for the data is as follows:
yyyy/mm/dd hh:dd:ss, devicename, offline
yyyy/mm/dd hh:dd:ss, devicename, ONLINE
yyyy/mm/dd hh:dd:ss, VO1: Virt Out 1, 0
yyyy/mm/dd hh:dd:ss, VI4: Virt In 4, 1
yyyy/mm/dd hh:dd:ss, DI3: Direct In 3, 0
yyyy/mm/dd hh:dd:ss, RI2: Remote In 2, 1
yyyy/mm/dd hh:dd:ss, H5a: Contact In 1, 1
yyyy/mm/dd hh:dd:ss, H1: Contact Output 1, 0
Options display for filtering, such as recording timing for Virtual Inputs and Outputs, but not Communications Status.
4.4.6.4 COMTRADE waveforms
Waveform files are viewable in the EnerVista software. The preferences are unrelated to Engineer and are outlined in the
UR Family Communications Guide.
4-50
CHAPTER 4: INTERFACES
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL

Advertisement