Technical Assistance If you encounter a problem with your Watlow controller, see the Trouble- shooting Table in the Appendix of the Series 96 User’s Manual and review all of your configuration information to verify that your selections are consistent with your application: inputs; outputs; alarms; limits; etc. If the problem persists after checking the above, you can get technical assistance from your local Watlow representative, or by dialing (507) 454-5300, ext.
Calibrating the Series 96 Warm up the unit (20 minutes). To enter a calibration menu, enter the Factory Page by holding down the ˆ and ‰ keys for six seconds. Once in the Factory Page [Fcty] use the Up-arrow ¿ or Down-arrow ¯...
Precision millivolt source, 0 to 50mV minimum range, 0.002mV resolution. Input 1 Setup and Calibration 1. Connect the correct power supply to terminals 8 and 9 (see Series 96 User’s Manual). 2. Connect the millivolt source to terminals 6 (-) and 7 (+) with copper wire.
Precision voltage source, 0 to 10V minimum range, with 0.001V resolution. Input 1 and 2 Setup and Calibration 1. Connect the correct power supply to terminals 8 and 9 (see Series 96 User’s Manual). Input 1 2. Connect the voltage source to terminals 4 (+) and 6 (-) of the controller.
Precision volt/ammeter with 3.5-digit resolution. Output 1 Setup and Calibration 1. Connect the correct power supply to terminals 8 and 9 (see Series 96 User’s Manual). Milliamperes 2. Connect the volt/ammeter (set to milliamperes) to terminals 13 (+) and 14 (-).
Page 7
Output 4 Setup and Calibration 1. Connect the correct power supply to terminals 8 and 9 (see Series 96 User’s Manual). Milliamperes 2. Connect the volt/ammeter (set to milliamperes) to terminals 20 (-) and 21 (+). 3. At Output Calibration 4, 4mA [4``4] (Process Output Calibration Menu) enter the reading from the ammeter.
Series 96 Factory Page Calibration Parameters The resting-state display shows one of the following sets of data, depending on controller setup. The first prompt appears in the top display, the second in the bottom. To enter the calibration mode, first enter the diagnostics mode; send value 1789 to register 1512.
Page 9
[hide]. bration for input 2 process. **These parameters are not available if the ramping software option has been ordered (96 _ _ - _ _ _ _ - AA _ _ ) Watlow Series 96 Calibration...
Page 10
Active if output 4 is process (96 _ tion 4, 4mA _- _ _ _ M -_ _ _ _) and Calibra- tion Lock (Lockout Menu) is not Enter the output set to [hide]. value in milliamps as measured. Calibration Watlow Series 96...