11.2
Indoor Unit
11.2.1
How to Fix Installation Plate
The mounting wall shall be strong and solid enough to prevent it from the vibration.
Measuring
Tape
E9RKUAW,
E12RKUAW
The center of installation plate should be at more than at right and left of the wall.
The distance from installation plate edge to ceiling should more than .
From installation plate left edge to unit's left side is .
From installation plate right edge to unit's right side is .
○
B
: For left side piping, piping connection for liquid should be about from this line.
: For left side piping, piping connection for gas should be about from this line.
1
Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
o
a level gauge.
2
Drill the piping plate hole with ø2 3/4" (ø70 mm) hole-core drill.
Line according to the left and right side of the installation plate. The meeting point of the extended line is
o
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram
above. The hole center is obtained by measuring the distance namely 5 1/16" (128 mm) for left and right
hole respectively.
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
o
side.
11.2.2
To Drill a Hole in the Wall and
Install a Sleeve of Piping
1
Insert the piping sleeve to the hole.
2
Fix the bushing to the sleeve.
3
Cut the sleeve until it extrudes about 19/32"
(15 mm) from the wall.
CAUTION
When the wall is hollow, please be sure
to use the sleeve for tube assembly to
prevent dangers caused by mice biting
the connection cable.
4
Finish by sealing the sleeve with putty or
caulking compound at the final stage.
Wall
More than 1
Indoor unit
9
17
/
"
32
(241.5 mm)
5
1
/
"
16
(128 mm)
Model
or
Wall
More than
2
2 screw
3
5
1
/
" (128 mm)
16
6
5
Installation plate 1
For best strength of
INDOOR unit installation,
it is highly recommended
to locate " " at 5 position
as shown.
Dimension
1
2
3
9
7
9
19
/
"
3
/
"
17
/
32
32
32
(490 mm)
(82 mm)
(439 mm)
Sleeve for
tube
assembly
ø2
through hole
34
More than 1
4
9
17
/
"
32
(241.5 mm)
1
5
/
"
16
(128 mm)
4
5
11
"
17"
1
/
"
3
16
(432 mm)
(43 mm)
(95 mm)
Wall
Indoor
Outdoor
19
/
" (15 mm)
32
Bushing for tube
assembly
3
/
" (ø70 mm)
4
Putty or caulking compound
Wall
6
3
/
"
4
Approx.
7 /32" - 9 /32"
(5-7 mm)