Panasonic S-36PU1E5A Technical Data & Service Manual page 576

R410a models
Hide thumbs Also See for S-36PU1E5A:
Table of Contents

Advertisement

P14 O
Sensor Detect
2
1.
Error Detection Method
It is judged an error whenever the outdoor unit receives the signal "O
With the indoor unit's EEPROM setting (item code 0B) set to 0001, the EXCT input was shorted.
2.
Error Diagnosis
1 System
configuration
2 Indoor unit's
EEPROM
setting
3
Indoor EXCT
wiring
4
Indoor unit's
control
PC board
5
1-1
Is an O
sensor being used?
2
Is the indoor EEPROM setting, item code 0B, on the indoor unit's
2-1
control PC board set to 0001?
3-1
Is the indoor EXCT socket (wire) shorted?
Is the alarm triggered if the indoor EXCT socket (wire) is
4-1
disconnected, and the power is reset?
4-2
Since there is no error, see what happens.
4-3 Indoor unit control PC board error
Alarm Occurred" from the indoor unit.
2
replace PC board.
5-54
Yes
3-1
No
2-1
After correcting the
Yes
setting, 3-1
No
4-1
Yes
Correct wiring
No
4-1
Yes
4-3
No
4-2