Page 3
ENSURE THAT OUR PRODUCTS ARE DEVELOPED TO THE LATEST TECHNOLOGICAL STAN- DARDS. AS A RESULT, IT IS POSSIBLE THAT THERE MAY BE SOME DIFFERENCES BETWEEN THE HW/SW PRODUCT AND THIS INFORMATION PRODUCT. Manufacturer: ABB Power Technologies AB Substation Automation Products SE-721 59 Västerås Sweden...
Contents Chapter Page Chapter 1 Introduction ..............1 Introduction to the installation and commissioning manual ....2 About the complete set of manuals for a terminal ......2 About the installation and commissioning manual......2 Intended audience ................3 General..................3 Requirements ................
Page 5
Contents Installing the serial communication cable for RS485 SPA/IEC ..37 RS485 serial communication module ........... 37 Informative excerpt from EIA Standard RS-485 ......39 Data on RS485 serial communication module cable ....41 Installing the 56/64 kbit data communication cables......42 Chapter 6 Checking the external circuitry ........
Page 6
Contents Overview.................... 82 Entering settings through the local HMI..........83 Configuring the setting restriction of HMI function ......84 Activating the restriction of setting ............. 85 Local HMI ..................85 Serial communication, change of active group ......85 Serial communication, setting............85 Downloading settings and configuration from a PC......
Page 7
Contents Releasing the function(s) to be tested ........105 Checking the disturbance report settings ........105 Identifying the function to test in the technical reference manual ........... 106 Autorecloser (AR) ................107 Preparing ..................108 Checking the AR functionality............. 109 Checking the reclosing condition ..........
Page 8
Contents Pole discordance protection (PD) ............ 137 Pulse counter logic for metering (PC)..........138 Setting lockout (HMI) ............... 139 Verifying the settings ..............139 Completing the test..............139 Four parameter setting groups (GRP) ..........140 Verifying the settings ..............140 Single command (CD) ..............
Page 9
Contents Dependability test ..............156 Time delay test ..............156 Completing the test..............156 Residual overcurrent protection (ROCP) ......... 157 Measuring the operate limit of set values ........157 Residual overcurrent ............. 157 Dependability test ..............157 Time delay test ..............157 Completing the test..............
Introduction to the installation and Chapter 1 commissioning manual Introduction Introduction to the installation and commissioning manual About the complete set of manuals for a terminal The users manual (UM) is a complete set of four different manuals: Application Technical Installation and Operator´s manual...
Introduction to the installation and Chapter 1 commissioning manual Introduction • The chapter “Overview” gives an overview over the major tasks when installing and commissioning the terminal. • The chapter “Unpacking and checking the terminal” contains instructions on how to receive the terminal. •...
Introduction to the installation and Chapter 1 commissioning manual Introduction Related documents Documents related to REL 551*2.5 Identity number Operator's manual 1MRK 506 150-UEN Installation and commissioning manual 1MRK 506 151-UEN Technical reference manual 1MRK 506 152-UEN Application manual 1MRK 506 153-UEN Buyer's guide 1MRK 506 179-BEN Revision notes...
Page 14
Introduction to the installation and Chapter 1 commissioning manual Introduction C34.97 Controller Area Network. ISO standard (ISO 11898) for serial communi- cation CAP 531 Configuration and programming tool Circuit breaker Combined backplane module CCITT Consultative Committee for International Telegraph and Telephony. A United Nations sponsored standards body within the International Tele- communications Union.
Page 15
Introduction to the installation and Chapter 1 commissioning manual Introduction DLLB Dead line live bus Digital signal processor Direct transfer trip scheme EHV network Extra high voltage network Electronic Industries Association Electro magnetic compatibility ENGV1 Enable execution of step one ENMULT Current multiplier used when THOL is used for two or more lines Electro magnetic interference...
Page 16
Introduction to the installation and Chapter 1 commissioning manual Introduction HystAbs Overexcitation level of absolute hysteresis as a percentage HystRel Overexcitation level of relative hysteresis as a percentage IBIAS Magnitude of the bias current common to L1, L2 and L3 IDBS Integrating dead-band supervision IDMT...
Page 17
Introduction to the installation and Chapter 1 commissioning manual Introduction IP 40 Enclosure protects against solid foreign objects 1.0mm in diameter or larger but no protection against ingression of liquid according to IEC60529. IP 54 Degrees of protection provided by enclosures (IP code) according to IEC 60529.
Page 18
Introduction to the installation and Chapter 1 commissioning manual Introduction Pulse code modulation PISA Process interface for sensors & actuators Programmable Logic Device POTT Permissive overreach transfer trip Precise Positioning System Process bus Bus or LAN used at the process level, that is, in near proximity to the measured and/or controlled components Power supply module Parameter setting tool...
Page 19
Introduction to the installation and Chapter 1 commissioning manual Introduction SPGGIO Single Point Gxxxxx Generic Input/Output Switch for CB ready condition ST3UO RMS voltage at neutral point STL1 Start signal from phase L1 Switch or push-button to trip Static VAr compensation t1 1Ph Open time for shot 1, single phase t1 3PhHS...
Page 20
Introduction to the installation and Chapter 1 commissioning manual Introduction V.36 Same as RS449. A generic connector specification that can be used to support RS422 and others Volts Direct Current Week-end infeed logic Voltage transformer VTSZ Block of trip from weak-end infeed logic by an open breaker Source reactance A (near end) Source reactance B (far end) Positive sequence line reactance...
Page 21
Introduction to the installation and Chapter 1 commissioning manual Introduction...
About this chapter Chapter 2 Safety information Chapter 2 Safety information About this chapter This chapter contains safety information. Warning signs are presented which attend the user to be careful during certain operations in order to avoid human injuries or damage to equipment...
Warning signs Chapter 2 Safety information Warning signs Warning! Strictly follow the company and country safety regulations. Working in a high voltage environ- ment requires serious approach to avoid human injuries and damage to equipment. Warning! Do not touch circuitry during operation. Potentially lethal voltages and currents are present. Warning! Always avoid to touch the circuitry when the cover is removed.
Page 24
Warning signs Chapter 2 Safety information Warning! Never remove any screw from a powered IED or from a IED connected to powered circuitry. Potentially lethal voltages and currents are present.
Caution signs Chapter 2 Safety information Caution signs Caution! Always transport modules using certified conductive bags. Always handle modules using a con- ductive wrist strap connected to protective ground and on a suitable antistatic surface. Electro- static discharge (ESD) may cause damage to the module. Caution! Do not connect live wires to the IED.
Note signs Chapter 2 Safety information Note signs Note! The protection assembly is designed for a maximum continuous current of four times rated val- Note! Activating the setting lockout function, which prevents unauthorised changes of the settings, without proper configuration may seriously affect the IED’s operation.
About this chapter Chapter 3 Overview Chapter 3 Overview About this chapter This chapter introduces the user to the installation and commissioning tasks.
Commissioning and installation overview Chapter 3 Overview Commissioning and installation overview The settings for each function must be calculated before the commissioning task can start. A configuration, made in the configuration and programming tool, must also be available if the ter- minal does not have a factory configuration downloaded.
About this chapter Chapter 4 Unpacking and checking the terminal Chapter 4 Unpacking and checking the terminal About this chapter This chapter contains instructions on how to receive the terminal.
Check for transport damages. In case of transport damage appropriate action must be taken against the latest carrier and the nearest ABB office or representative should be in- formed. ABB should be notified immediately if there are any discrepan- cies in relation to the delivery documents.
About this chapter Chapter 5 Installing the terminal Chapter 5 Installing the terminal About this chapter This chapter describes how to install the terminal.
Overview Chapter 5 Installing the terminal Overview The mechanical and electrical environmental conditions at the installation site must be within permissible range according to the technical data of the terminal. Dusty, damp places, places li- able to rapid temperature variations, powerful vibrations and shocks, surge voltages of high am- plitude and fast rise time, strong induced magnetic fields or similar extreme conditions should be avoided.
Mounting the terminal Chapter 5 Installing the terminal Mounting the terminal Most of the REx 5xx terminals can be rack, flush, semi-flush or wall mounted with the use of different mounting kits. An additional box of type RHGS can be mounted to one side of a 1/2 or 3/4 terminal.
Mounting the terminal Chapter 5 Installing the terminal Procedure Carefully fasten the mounting angles to the sides of the terminal. Use the TORX T20 screws available in the mounting kit. Place the terminal assembly in the rack. Fasten the mounting angles with appropriate screws. Mounting in a 19-inch rack with an additional box type RHGS Make sure a side-by-side mounting kit and a suitable 19-inch rack mounting kit are available before proceeding.
Mounting the terminal Chapter 5 Installing the terminal Fasten a side-by-side mounting plate (PosNo 1). Use four of the delivered screws. Carefully turn the two terminals up-side down. Fasten the second side-by-side mounting plate. Use the remaining four screws. Follow the instructions in section 2.1 "Mounting in a 19-inch rack"...
Page 38
Mounting the terminal Chapter 5 Installing the terminal xx00000129.eps PosNo Description Sealing strip Distance frame (only for semi-flush) Sealing strip for distance frame (only for semi-flush) Side holder Groove Locking screw (TORX T10) Figure 3: Flush and semi-flash mounting Note! Flush or semi-flush mount cannot be used for side-by-side mounted terminals when IP 54 must be fulfilled.
Mounting the terminal Chapter 5 Installing the terminal Procedure Cut the sealing strip in appropriate lengths. The strip is delivered with the mounting kit. In the semi-flush mounting kit two strips are delivered, one for the terminal and one self-adhering for the distance frame.
Mounting the terminal Chapter 5 Installing the terminal xx00000130.eps PosNo Description Mounting bar Side plate Figure 4: Wall mounting 2.4.1 Mounting the terminal on a wall Procedure Mount the bars (posNo 1) onto the wall. See the Technical reference manual for measurements. Depending on the wall different preparations may be needed, like drilling and inserting plastic or expander plugs (concrete/plasterboard walls) or threading (metal sheet wall).
Mounting the terminal Chapter 5 Installing the terminal Make all external electrical connections to the terminal blocks. It is much easier to do this without the unit in place. Mount the side plates (posNo 2) to the terminal. Mount the terminal to the mounting bars. 2.4.2 Preparing a wall mounted terminal for electrical installation Procedure...
Making the electrical connections Chapter 5 Installing the terminal Making the electrical connections Always make sure established guidelines for this type of terminal is followed during installation. When necessary use screened twisted-pair cables to minimize susceptibility. Otherwise use any kind of regular nonscreened tinned cable or equivalent. When using screened cabling always use 360°...
Page 43
Making the electrical connections Chapter 5 Installing the terminal X20:5 (98000035) Figure 6: Voltage connector, showing connection point X20:5 Where: is ferrule Figure 7: Connected cables with ferrules...
Making the electrical connections Chapter 5 Installing the terminal If the terminal is equipped with a test-switch of type RTXP 24 COMBIFLEX wires with 20 A sockets must be used to connect the VT circuits and the auxiliary power. Connecting to protective earth Connect the unit to the earthing bar of the cubicle with a green/yellow conductor, cross section at least 1.5 mm (AWG16), connected to the protective earth connector at the back of the termi-...
Installing the optical fibres Chapter 5 Installing the terminal Installing the optical fibres Connectors are generally color coded; connect blue or dark grey cable connectors to blue or dark grey (receive) back-side connectors. Connect black or grey cable connectors to black or grey (transmit) back-side connectors.
Installing the serial communication cable for Chapter 5 RS485 SPA/IEC Installing the terminal Installing the serial communication cable for RS485 SPA/IEC RS485 serial communication module en03000109.vsd Where: Signal A Signal B Do not use Ground Figure 8: Pin arrangement on modem terminal. Baud rate: 9600 The distance between earth points should be <...
Page 47
Installing the serial communication cable for Chapter 5 RS485 SPA/IEC Installing the terminal External Terminal Terminal Equipment (PC) PE 1) en03000111.vsd Where: The inner shields shall be connected together (with an isolated terminal block) and only have one earthing point in the whole system, preferably at the external equipment (PC). The outer shield shall be connected to Protective Earth (PE) in every cable end i.e.
Installing the serial communication cable for Chapter 5 RS485 SPA/IEC Installing the terminal en03000110.vsd Where: is cable is screw Figure 10: Cable contact, Phoenix: MSTB2.5/6-ST-5.08 1757051 The EIA standard RS-485 specifies the RS485 network. An informative excerpt is given in sec- tion 5.2.
Page 49
Installing the serial communication cable for Chapter 5 RS485 SPA/IEC Installing the terminal Three isolation options exist: a) The entire node electronics can be galvanically isolated b) The bus interface circuit can be isolated form the rest of node electronics by optoisola- tors, transformer coupling or otherwise.
Installing the serial communication cable for Chapter 5 RS485 SPA/IEC Installing the terminal Data on RS485 serial communication module cable Type: Twisted-pair S-STP (Screened – Screened Twisted Pair) Shield: Individual foil for each pair with overall copper braid Length: Maximum 100 m from one system earth to the next system earth (includes length from platform point to system earth on both sides) Temp: According to application...
Installing the 56/64 kbit data communication Chapter 5 cables Installing the terminal Installing the 56/64 kbit data communication cables When using galvanic connection between protection terminal and communication equipment or point to point galvanic connection between two protection terminals it is essential that the cable installation is carefully done.
Page 52
Installing the 56/64 kbit data communication Chapter 5 cables Installing the terminal External Equipment en03000087.vsd Communication cable Line connector Receive input Screen (or earth/ground) connection Transmit output Figure 12: Communication cable installation...
Page 53
Installing the 56/64 kbit data communication Chapter 5 cables Installing the terminal...
About this chapter Chapter 6 Checking the external circuitry Chapter 6 Checking the external circuitry About this chapter This chapter describes what to check and which checks that should be made to ensure a correct connection to the external circuitry, such as auxiliary power supply, CT’s and VT’s. These checks must be made with the protection terminal de-energised.
Overview Chapter 6 Checking the external circuitry Overview The user must check the installation which includes verifying that the terminal is connected to the other parts of the protection system. This is done with the terminal and all connected circuits de-energised.
Checking the CT and VT circuits Chapter 6 Checking the external circuitry Checking the CT and VT circuits Check that the wiring is in strict accordance with the supplied wiring diagram. Note! Do not continue further until any errors are corrected. Test the circuitry.
Checking the power supply Chapter 6 Checking the external circuitry Checking the power supply Check that the value of the auxiliary supply voltage remains within the permissible range under all operating conditions. Check that the polarity is correct.
Checking the binary I/O circuits Chapter 6 Checking the external circuitry Checking the binary I/O circuits Binary input circuits Preferably, disconnect the binary input connector from the binary input cards. Check all con- nected signals so that both input level and polarity are in accordance with the terminal’s speci- fications.
Page 59
Checking the binary I/O circuits Chapter 6 Checking the external circuitry...
About this chapter Chapter 7 Energising the terminal Chapter 7 Energising the terminal About this chapter This chapter describes the start up sequence and what to check after the terminal has been eneri- gsed.
Overview Chapter 7 Energising the terminal Overview Before the procedures in this chapter can be carried out the connection to external circuitry must have been checked which ensures that the installation was made correctly. The user must energise the power supply to the terminal to start it up. This could be done in num- ber of ways, from energising a whole cubicle to energising a single terminal.
Energising the terminal Chapter 7 Energising the terminal Energising the terminal When the terminal is energised the window on the local HMI remains dark. After 10 seconds the green LED starts flashing and after approximately 30 seconds the window lights up. After an- other 10 seconds the window displays ‘Terminal Startup’...
Page 63
Energising the terminal Chapter 7 Energising the terminal LEDs green yellow red Liquid Crystal Display four rows Ready Start Trip 16 characters/row REx 5xx Ver X.X C=Quit E=Enter menu Optical connector Push buttons for local PC en00000422.vsd Figure 14: Example of the local HMI531.
Checking the self supervision signals Chapter 7 Energising the terminal Checking the self supervision signals Reconfiguring the terminal I/O modules configured as logical I/O modules (BIM, BOM, IOM, DCM, IOPSM or MIM) are supervised. Not configured I/O modules are not supervised. Each logical I/O module has an error flag that is set if anything is wrong with any signal or the whole module.
None. MPM-modWarning = There is a problem with: Set the clock. Warning • the real time clock. If the problem persists, contact your ABB repre- sentative for service. • the time synchroniza- tion. ADC-module = OK No problem detected. None.
About this chapter Chapter 8 Configuring the 56/64 kbit data communication modules Chapter 8 Configuring the 56/64 kbit data communication mo dules About this chapter This chapter contains instructions on how to configure the 56/64 kbit data communication mod- ules, such as galvanic and optical modems.
Configuring the fibre optical modem Chapter 8 Configuring the 56/64 kbit data communication modules Configuring the fibre optical modem Two different levels of optical output power can be set on the HMI under: Configuration/TerminalCom/RemTermCom/OptoPower For the optical module, the optical output power has to be set according to the total attenuation of the fibre optic link.
Calculation of optical power budget Chapter 8 Configuring the 56/64 kbit data communication modules Calculation of optical power budget Refer to table 2 table 3 for maximum distance in a back-to-back application Table 2: Input data for calculation of optical power budget General data Attenuation Type of optical Tx/Rx-module...
Configuring the short range fibre optical Chapter 8 modem Configuring the 56/64 kbit data communication modules Configuring the short range fibre optical modem No setting is available for the short range fibre optical modem on the HMI. There are however some settings that can be made on a DIP-switch located behind the cover around the fibre optic connectors at the back of the terminal according to figure...
Page 70
Configuring the short range fibre optical Chapter 8 modem Configuring the 56/64 kbit data communication modules Table 4: Setting of the timing signal Switch no. Function Timing created by the modem Timing recovered from received optical signal Timing created by the MPM module No timing, the data transmission will not work There are also some jumpers on the circuit board that have to be correctly set.
Page 71
Configuring the short range fibre optical Chapter 8 modem Configuring the 56/64 kbit data communication modules JTAG/ISP 1MRK001471-BA 1MRK001471-DA xx01000138.vsd Delivered with version 1.1, 1.2 and 2.0 Delivered with version 2.3 or higher Figure 17: Jumper location on short range optical modem The jumpers are accessible after the modem has been pulled out.
Page 72
Configuring the short range fibre optical Chapter 8 modem Configuring the 56/64 kbit data communication modules Table 5: Indications Color Explanation Yellow Request to send Yellow Clear to send Yellow Data communication correct Yellow Detection of carrier signal Yellow Transmitted data Yellow Received data Remotely detected problem with link...
Configuring the short range galvanic modem Chapter 8 Configuring the 56/64 kbit data communication modules Configuring the short range galvanic modem No setting is available for the short range galvanic modem on the HMI. There are however some settings that can be made on the DIP-switch located behind the cover around the line connector at the back of the terminal as shown in figure 18.
Page 74
Configuring the short range galvanic modem Chapter 8 Configuring the 56/64 kbit data communication modules Table 7: Indications Explanation Detection of carrier signal Transmitted data Received data...
Configure the interface modules for V.36, Chapter 8 X.21 and RS530 Configuring the 56/64 kbit data communication modules Configure the interface modules for V.36, X.21 and RS530 The connector for X.21 is a 15 pin DSUB according to the X.21 standard. For RS530 the con- nector is a 25 pin DSUB according to the RS530 standard.
Page 76
Configure the interface modules for V.36, Chapter 8 X.21 and RS530 Configuring the 56/64 kbit data communication modules Designation Explanation Received data SCREEN Connection of cable screen TCLK DCE Transmitter signal timing from DCE TCLK DTE Transmitter signal timing from DTE Transmitter data For the co-directional operation the transmission rate of the transmitted signal must be set.This setting, 56 or 64 kbit/s, is done on the HMI under:...
Configuring the interface modules for Chapter 8 G.703 co-directional Configuring the 56/64 kbit data communication modules Configuring the interface modules for G.703 co-directional No setting is available for the G.703 modem on the HMI. There are however some settings that can be made on a DIP-switch located behind the cover around the line connector at the back of the terminal according to figure...
Fault tracing Chapter 8 Configuring the 56/64 kbit data communication modules Fault tracing Procedure Check that the settings are correct. Check that the optical budget is correct. COMFAIL occurs for the following reasons: The COMFAIL signal will be triggered when there is a problem in the communication link be- tween the two terminals, depending on type of 56/64 modem.
Fault tracing Chapter 8 Configuring the 56/64 kbit data communication modules Table 10: Summary COMFAIL triggering COMFAIL trigger- Remark ing time (Drop-out delay 200 ms) ≥ 50 ms Transmit error Messages can not be sent ≥ 100 ms Receive error No valid messages received Block differential protection 0 ms...
Page 80
Fault tracing Chapter 8 Configuring the 56/64 kbit data communication modules 3. Block differential protection. Block of differential protection occurs during change of settings or setting group. 4. Remote terminal COMFAIL. For error No 1, 2, 3 and No 5, 6, 7, 8, 9, 10 the COMFAIL is sent in the second consecutive message (within 10 ms).
Page 81
Fault tracing Chapter 8 Configuring the 56/64 kbit data communication modules surements presented on the front HMI are not connected to COMFAIL or by in- dications of channel delay exceeding 12 ms, since the delay is not a channel interrupt, the channel is still working.
Here follow some recommendations on settings and connections when operating together with protection systems from ABB. In the following the transceiver is regarded as a DTE (although it is actually designed as a DCE) and is supposed to be connected to communication equipment that acts as a DCE.
Co-directional operation Chapter 8 Configuring the 56/64 kbit data communication modules Co-directional operation The connection is made according to table Table 11: Connections Transceiver Pin No. V.35 V.36 Comm. eq. Signal Signal Direction Comm. eq. -> Transceiver Transceiver -> Comm. eq. Comm.
Page 84
Co-directional operation Chapter 8 Configuring the 56/64 kbit data communication modules Table 12: Settings Switch, jumper Setting Gives Middle position V.35 Bottom position V.36 64 kbit/s Middle position External clock Has no influence on operation...
Contra-directional operation Chapter 8 Configuring the 56/64 kbit data communication modules Contra-directional operation Connected according to table Table 13: Connections Transceiver Pin No. V.35 V.36 Comm. eq. Signal Signal Direction Comm. eq -> Transceiver Transceiver -> Comm. eq. Comm. eq. -> Transceiver Either RC - 115 or TC - 114 can be used.
Page 86
Contra-directional operation Chapter 8 Configuring the 56/64 kbit data communication modules Table 14: Settings Switch, jumper Setting Gives Middle position V.35 Bottom position V.36 64 kbit/s Middle position External clock Has no influence on operation...
For setting jumpers, follow the instructions in the document delivered with the transceiver. Here follow some recommendations on settings and connections when using protection systems from ABB. In the following, the transceiver is regarded as a DTE and is supposed to be connect- ed to communication equipment that acts as a DCE.
Configuring the transceiver 21-16xx Chapter 8 Configuring the 56/64 kbit data communication modules Table 16: Settings Switch, jumper Setting Gives S2, S3, S4, S15, S16 Jumpers downwards Second position from bottom X.21 64 kbit/s Jumper at middle position External clock Has no influence on operation 11.2 G.703 co-directional operation...
Page 89
Configuring the transceiver 21-16xx Chapter 8 Configuring the 56/64 kbit data communication modules Table 18: Settings Switch, jumper Setting G.703 co - con, balanced Nx64 kbps Co-directional Has no influence on operation Has no influence on operation Has no influence on operation 9 (64 kbit/s) S14 timing source External clock...
About this chapter Chapter 9 Setting and configuring the terminal Chapter 9 Setting and configuring the terminal About this chapter This chapter describes how to set the terminal, either through a PC or the local HMI, and down- load a configuration to the terminal in order to make commissioning possible. The chapter does not contain instructions on how to create a configuration or calculate settings.
Overview Chapter 9 Setting and configuring the terminal Overview The customer specific values for each setting parameter and a configuration file has to be avail- able before the terminal can be set and configured, if the terminal is not delivered with a config- uration.
Entering settings through the local HMI Chapter 9 Setting and configuring the terminal Entering settings through the local HMI Each of the included functions in the terminal has to be set and this can be performed through the local HMI. The user must browse to the desired function and enter the appropriate value. The parameters for each function can be found in the local HMI.
Configuring the setting restriction of HMI Chapter 9 function Setting and configuring the terminal Configuring the setting restriction of HMI function Configuring the HMI--BLOCKSET functional signal can only be done from the local HMI. REx 5xx HMI--BLOCKSET SWITCH & WITH KEY SettingRestrict=Block RESTRICT SETTINGS...
Activating the restriction of setting Chapter 9 Setting and configuring the terminal Activating the restriction of setting Local HMI Activating the restriction of setting via local HMI can only be done from the local HMI. Procedure Navigate the menus to: Configuration/BuiltInHMI/SettingRestrict Set SettingRestrict = Block.
A special cable is needed when connecting a PC to the front of the REx 5xx terminal. This cable can be ordered from ABB. It must be plugged into the optical contact on the left side of the local HMI. The other end of the cable shall be plugged directly into the COM-port on the PC. The cable includes an optical contact, an opto/electrical converter and an electrical cable with a stan- dard 9-pole D-sub contact.
Downloading settings and configuration from Chapter 9 a PC Setting and configuring the terminal Selecting the protocols for the rear ports To define the protocols to be used, a setting is done on the local HMI under the menu: Configuration/TerminalCom/SPA-IEC-LON When the protocols have been selected the terminal will automatically restart.
Page 97
Downloading settings and configuration from Chapter 9 a PC Setting and configuring the terminal...
About this chapter Chapter 10 Requirement of trig condition for disturbance report Chapter 10 Requirement of trig condition for disturbance report About this chapter This chapter describes how to override the limitation on the storage capacity of the flash mem- ory.
Requirement of trig condition for disturbance Chapter 10 report Requirement of trig condition for disturbance report Requirement of trig condition for disturbance report Disturbance reports, setting and internal events in REx 5xx are stored in a non volatile flash memory. Flash memories are used in many embedded solutions for storing information due to high reliability, high storage capacity, short storage time and small size.
About this chapter Chapter 11 Establishing connection and verifying the SPA/IEC-communication Chapter 11 Establishing connection and verifying the SPA/IEC-communi cation About this chapter This chapter contains instructions on how to establish connection and verify that the SPA/IEC-communication operates as intended, when the terminal is connected to a monitoring or control system via the rear SPA/IEC port.
Entering settings Chapter 11 Establishing connection and verifying the Entering settings If the terminal is connected to a monitoring or control system via any of the rear SPA and/or IEC ports, the applicable selection of protocols for the rear ports must be made. Entering SPA settings When using the SPA protocol, the rear SPA/IEC port must be set for SPA use.
Page 102
Entering settings Chapter 11 Establishing connection and verifying the SPA/IEC-communication Configuration/TerminalCom/SPA-IEC-LON When the setting is entered the terminal will automatically restart. After the restart the selected IEC port operates as a IEC port. Set the slave number and baud rate for the rear IEC port The slave number and baud rate can be found on the local HMI at: Configuration/TerminalCom/IECCom/Communication Set the same slave number and baud rate as set in the IEC master system...
Verifying the communication Chapter 11 Establishing connection and verifying the Verifying the communication To verify that the rear communication with the SMS/SCS system is working, there are some dif- ferent methods. Choose one of the following. Verifying SPA communication Procedure Use a SPA-emulator and send “RF”...
Optical budget calculation for serial Chapter 11 communication with SPA/IEC Establishing connection and verifying the SPA/IEC-communication Optical budget calculation for serial communication with SPA/IEC Table 20: Example Distance 1 km Distance 25 m Glass Plastic Maximum attenuation for REx 5xx - 11 dB - 7 dB 4 dB/km multi mode: 820 nm - 62.5/125 um...
Page 105
Optical budget calculation for serial Chapter 11 communication with SPA/IEC Establishing connection and verifying the...
About this chapter Chapter 12 Establishing connection and verifying the LON communication Chapter 12 Establishing connection and verifying the LON communication About this chapter This chapter referes to another document.
Reference Chapter 12 Establishing connection and verifying the LON communication Reference We refere to document: LNT 505 Operator’s Manual 1MRS751706-MUM, Issued: 31.10.99, Program rev: 1.1.1 Doc. version: B. Verification of the optical budget 1.1.1 Optical budget calculation for serial communication with LON Table 21: Example Distance 1 km...
About this chapter Chapter 13 Verifying settings by secondary injection Chapter 13 Verifying settings by secondary injection About this chapter This chapter describes how to verify that the protection functions operates correctly according to the settings. Only the tested function should be in operation.
Overview Chapter 13 Verifying settings by secondary injection Overview Required tools for testing of a terminal: • Calculated settings • Configuration diagram • Terminal diagram • Technical reference manual • Three-phase test equipment The terminal has to be set and configured before the testing can start. The terminal diagram, available in the Technical reference manual, is a general diagram for the terminal.
Page 110
Overview Chapter 13 Verifying settings by secondary injection Note! Please observe the measuring accuracy of the terminal, the test equipment and the angular ac- curacy for both of them. Note! Please consider the configured logic from the function block to the output contacts when mea- suring the operate time.
Preparing for test Chapter 13 Verifying settings by secondary injection Preparing for test Overview This section describes how to prepare the terminal in order to verify settings. The preparation starts with making the connections to the test switch if included. This means connecting the test equipment according to a valid terminal diagram for the specific REx 5xx terminal.
Preparing for test Chapter 13 Verifying settings by secondary injection Warning! Never disconnect a secondary connection of current transformer circuit without short-circuiting the transformer's secondary winding. Operating a current transformer with the secondary wind- ing open will cause a massive potential build-up that may damage the transformer and may cause injuries to humans.
Preparing for test Chapter 13 Verifying settings by secondary injection IN (I4,I5) UN (U4,U5) TRIP L1 TRIP L2 TRIP L3 en01000162.vsd Figure 27: Connection of the test set to the REx 5xx terminal. Verifying the connection and the analog inputs The user must verify that the connection and that the analog signals are measured correctly.
Preparing for test Chapter 13 Verifying settings by secondary injection ServiceReport/Phasors/Primary and Secondary Releasing the function(s) to be tested The user can release the function(s) to be tested. This is done in order to set only the tested func- tion(s) in operation and prevent other functions from operating. The user can release the tested function(s) by setting the corresponding parameter under BlockFunctions to NO in the local HMI.
Preparing for test Chapter 13 Verifying settings by secondary injection Test/TestMode/DisturbReport Table 22: Disturbance report settings Operation DisturbSum- Then the results are... mary • Disturbances are not stored. • LED information is not displayed on the HMI and not stored. •...
Autorecloser (AR) Chapter 13 Verifying settings by secondary injection Autorecloser (AR) The test can be divided into to parts; one to verify the internal logic and one to verify the co-op- eration with the protection system. This section deals with the first test. Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test"...
Autorecloser (AR) Chapter 13 Verifying settings by secondary injection Terminal AR01 - CLOSE CB Trip AR01 - CB CLOSE AR01 - CB READY To test en02000446.vsd Figure 28: Simulating breaker operation with two auxiliary relays. Preparing Check the settings of the autorecloser (AR) function. The operation can be set at Stand-by (Off) in HMI tree: Settings/Functions/Group n/AutoRecloser/AutoRecloser n If any timer setting is changed so as to speed-up or facilitate the testing,...
Autorecloser (AR) Chapter 13 Verifying settings by secondary injection ServiceReport/Functions/AutoRecloser/AutoRecloser n/Counters Do the testing arrangements outlined above, for example, as in fig- The AR01-CBCLOSED breaker position, the commands Trip and Closing, AR01-CLOSECB, and other signals should preferably be ar- ranged for event recording provided with time measurements. Otherwise, a separate timer or recorder can be used to check the AR open time and other timers.
Autorecloser (AR) Chapter 13 Verifying settings by secondary injection 3.3.1 Checking the Inhibit signal Check that the function is operative and that the breaker conditions are okay. Apply an AR01-INHIBIT input signal and start the reclosing function. Check that there is no reclosing. 3.3.2 Checking the closing onto a fault Set the breaker simulating relay, BR, in position open.
Autorecloser (AR) Chapter 13 Verifying settings by secondary injection Testing the multi-breaker arrangement If a multi-breaker arrangement is used for the application and priorities are given for the master (high) and slave (low) terminals, test that correct operation takes place and that correct signals are issued.
Breaker failure protection (BFP) Chapter 13 Verifying settings by secondary injection Breaker failure protection (BFP) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. Consider to release used start criteria. The trip is a pulse with a length of 150 ms. Fault condition: the current in a phase must exceed the set IP>...
Breaker failure protection (BFP) Chapter 13 Verifying settings by secondary injection 4.2.3 Checking the retrip function without current check Procedure Set RetripType = No I> check. Apply the fault condition with current below the set value. Verify that retrip is achieved after t1. Apply the fault condition with current over the set value.
Broken conductor check (BRC) Chapter 13 Verifying settings by secondary injection Broken conductor check (BRC) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. Measuring the operate and time limit of set values Procedure Check that the input logical signal BRC-BLOCK is logical zero and note on the local HMI that the BRC-TRIP logical signal is equal to the...
Communication channel test logic (CCHT) Chapter 13 Verifying settings by secondary injection Communication channel test logic (CCHT) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. Testing the logic Set all the timers according to the recommendations. Activate the CCHT--CR binary input.
Current circuit supervision (CTSU) Chapter 13 Verifying settings by secondary injection Current circuit supervision (CTSU) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. The current circuit supervision function is conveniently tested with the same 3-phase test set as used when testing the measuring functions in the REx 5xx.
Time delayed residual overcurrent protection Chapter 13 (TEF) Verifying settings by secondary injection Time delayed residual overcurrent protection (TEF) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. Normally, the test of the earth-fault overcurrent protection is made in conjunction with the test- ing of the distance protection functions, using the same multiphase test-set.
Page 127
Time delayed residual overcurrent protection Chapter 13 (TEF) Verifying settings by secondary injection Upol = -3U ϕ 65° IN Operation IN>Dir 99000052.vsd Figure 29: Measuring characteristic of the directional element. To activate the directional function, set Direction = Directional. Set the polarising voltage to 2% of U and the phase angle between voltage and current to 65°.
Page 128
Time delayed residual overcurrent protection Chapter 13 (TEF) Verifying settings by secondary injection Table 23: Operate time formulas Characteristics Operate time (s) Normal inverse 0.14 ------------------- - k ⋅ 0.02 (Equation 1) – Very inverse 13.5 ---- ------- k ⋅ (Equation 2) –...
Disturbance recorder (DR) Chapter 13 Verifying settings by secondary injection Disturbance recorder (DR) Evaluation of the results from the disturbance recording function requires access to a worksta- tion either permanently connected to the terminal or temporarily connected to the serial port on the front.
Event counter (CN) Chapter 13 Verifying settings by secondary injection Event counter (CN) The function can be tested by connecting a binary input to the counter under test and from out- side apply pulses to the counter. The speed of pulses must not exceed 10 per second. Normally the counter will be tested in connection with tests on the function that the counter is connected to, such as trip logic.
Event function (EV) Chapter 13 Verifying settings by secondary injection Event function (EV) During testing, the terminal can be set in test mode from the PST. The functionality of the event reporting during test mode is set from the PST as follows: •...
Event recorder (ER) Chapter 13 Verifying settings by secondary injection Event recorder (ER) During testing, the event recorder can be switched off if desired. This is found in the SMS or Substation Control System (SCS).
Instantaneous non-directional overcurrent Chapter 13 protection (IOC) Verifying settings by secondary injection Instantaneous non-directional overcurrent protection (IOC) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. To verify the settings the following fault type should be tested: •...
Line differential protection, phase Chapter 13 segregated (DIFL) Verifying settings by secondary injection Line differential protection, phase segregated (DIFL) When testing the differential protection it is important to be aware of that actions taken locally may cause operation of the terminal in the remote end. At commissioning and after changes in the current circuits, the trip signals at both terminals must be blocked permanently before the dc supply is connected.
Page 135
Line differential protection, phase Chapter 13 segregated (DIFL) Verifying settings by secondary injection When one of the protections is in test mode, the opposite terminal mode of operation is changed. In the opposite terminal, the received current values (a and b Fourier coefficients) are echoed back to the other terminal, but transposed in the following way: the received value for the L1 phase is returned as the L2 current, L2 is returned as L3, and L3 as L1.
Line differential protection, phase Chapter 13 segregated (DIFL) Verifying settings by secondary injection Local Remote ------------------------------------------ - Bias (Equation 6) ] OR ⋅ Bias Bias Bias Evaluate Own phase Other phases (Equation 7) The test is performed by injecting a single and a symmetrical three-phase current. If the optional charging current compensation function is included, the CCComp shall be Off and no measuring voltage connected to the terminal.
Page 137
Line differential protection, phase Chapter 13 segregated (DIFL) Verifying settings by secondary injection Inject a current in L1 and increase the current until operation in phase L1 and L2 takes place. The injected operation value must correspond to the set IMinOp· Ir·CT- Factor.
Line differential protection, phase Chapter 13 segregated (DIFL) Verifying settings by secondary injection 14. With a through load current of minimum 20% of the Ir · CTFactor, the and I are read in all phases. Diff Bias The I should be lower than 10% of the actual secondary current divid- Diff ed by the CTFactor, the I should be equal to this current.
Line differential protection, phase Chapter 13 segregated (DIFL) Verifying settings by secondary injection Disconnect the voltages from the terminal and connect only one phase to all three voltage inputs of the terminal. Increase the measured voltage to the rated phase value and observe the values of the differential and bias currents, presented on the ter- minal.
Supervision of AC input quantities (DA) Chapter 13 Verifying settings by secondary injection Supervision of AC input quantities (DA) Stabilized ac current and voltage generators and corresponding current, voltage, power and fre- quency meters with very high accuracy are necessary for testing the alternating quantity mea- suring function.
Supervision of mA input quantities (MI) Chapter 13 Verifying settings by secondary injection Supervision of mA input quantities (MI) A stabilized direct current generator and mA meter with very high accuracy for measurement of direct current is needed in order to test the dc measuring module. The generator operating range and the measuring range of the mA meter must be at least between -25 and 25 mA.
Supervision of mA input quantities (MI) Chapter 13 Verifying settings by secondary injection 16.2 Completing the test Continue to test another function or complete the test by setting the test mode to off. Restore connections and settings to the original values, if they were changed for testing purpose.
Multiple command (CM) Chapter 13 Verifying settings by secondary injection Multiple command (CM) Test of the multiple command function block is recommended to be performed in a system, that is, either in a complete delivery system as an acceptance test (FAT/SAT) or as parts of that sys- tem, because the command function blocks are connected in a delivery-specific way between bays and the station level.
Overload supervision (OVLD) Chapter 13 Verifying settings by secondary injection Overload supervision (OVLD) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. 18.1 Measuring the operate and time limit of set values Procedure Check that the input logical signals OVLD-BLOCK is logical zero and note on the local HMI that the OVLD-TRIP logical signal is equal to...
Page 145
Overload supervision (OVLD) Chapter 13 Verifying settings by secondary injection 12. Continue to test another function or complete the test by setting the test mode to off.
Pole discordance protection (PD) Chapter 13 Verifying settings by secondary injection Pole discordance protection (PD) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. Procedure Activate the PD---POLDISC binary input, and measure the operating time of the PD protection.
Pulse counter logic for metering (PC) Chapter 13 Verifying settings by secondary injection Pulse counter logic for metering (PC) The test of the pulse counter function requires at least the PST Parameter Setting Tool or SPA (or LON) connection to a station HMI including corresponding functionality. A known number of pulses are with different frequency connected to the pulse counter input.
Setting lockout (HMI) Chapter 13 Verifying settings by secondary injection Setting lockout (HMI) 21.1 Verifying the settings Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. Procedure Configure the HMI--BLOCKSET functional input to the binary input, which is determined by the engineering or the input that is not used by any other function.
Four parameter setting groups (GRP) Chapter 13 Verifying settings by secondary injection Four parameter setting groups (GRP) 22.1 Verifying the settings Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. Procedure Check the configuration of binary inputs that control the selection of active setting group.
Single command (CD) Chapter 13 Verifying settings by secondary injection Single command (CD) For the single command function block, it is necessary to configure the output signal to corre- sponding binary output of the terminal. The operation of the function is then checked from the local HMI by applying the commands with the MODE Off, Steady, or Pulse and by observing the logic statuses of the corresponding binary output.
Thermal phase overload protection (THOL) Chapter 13 Verifying settings by secondary injection Thermal phase overload protection (THOL) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. Check that the input logical signal THOL-BLOCK is logical zero and note on the local HMI that the logical signal THOL-TRIP, THOL-START and THOL-ALARM are equal to the logical 0.
Page 152
Thermal phase overload protection (THOL) Chapter 13 Verifying settings by secondary injection 10. Check the reset limit (TdReset). Measure the signal THOL-START until it disappears on the correspond- ing binary output or on the local HMI unit, take the “T Line” readings and compare with the setting of TdReset.
Definite time non-directional overcurrent Chapter 13 protection (TOC) Verifying settings by secondary injection Definite time non-directional overcurrent protection (TOC) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. To verify the settings the following fault type should be tested: •...
Definite time non-directional overcurrent Chapter 13 protection (TOC) Verifying settings by secondary injection Compare the measured operating current with the set value IN>. Set the fault current to about 1.5 times the measured operating cur- rent. Switch on the fault current and measure the operating time of the TOC protection.
Tripping logic (TR) Chapter 13 Verifying settings by secondary injection Tripping logic (TR) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. The function is tested functionally together with other protection functions (distance protection ZMn--, line differential protection DIFL-, earth-fault overcurrent protection IOC-- or TOC--, etc.) within the REx 5xx terminals.
Tripping logic (TR) Chapter 13 Verifying settings by secondary injection If not the autoreclosing function is used the functional outputs TRIP-TRIP, TRIP-TR1P and the corresponding phase signal (TRIP-TRLn) should be active at each fault. Initiate a single-phase-to-earth fault and switch it off immediately when the trip signal is issued for the corresponding phase.
Tripping logic (TR) Chapter 13 Verifying settings by secondary injection If not the autoreclosing function is used the functional outputs TRIP-TRIP, TRIP-TR1P and the corresponding phase signal (TRIP-TRLn) should be active at each fault. Initiate a single-phase-to-earth fault and switch it off immediately when the trip signal is issued for the corresponding phase.
Two step time delayed non-directional phase Chapter 13 overcurrent protection (TOC2) Verifying settings by secondary injection Two step time delayed non-directional phase overcurrent protection (TOC2) Prepare the terminal for test as outlined in section 2 "Preparing for test" in this chapter. Ensure that the maximum continuos current of a terminal does not exceed four times its rated value, if the measurement od the operating characteristics runs under constant voltage condi- tions.
Two step time delayed non-directional phase Chapter 13 overcurrent protection (TOC2) Verifying settings by secondary injection Set tLow to the correct value and check with a high current that the operation time is equal to tMin+tLow. 27.1.4 Measuring the operate limit of the high step overcurrent protection Set temporarily tHigh=0.000 s.
Sudden change in phase current Chapter 13 protection (SCC1) Verifying settings by secondary injection Sudden change in phase current protection (SCC1) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. 28.1 Measuring the operate limit of set values 28.1.1 Sudden change in current in any phase The sudden change in current protection algorithm measures the difference in amplitude of the...
Sudden change in phase current Chapter 13 protection (SCC1) Verifying settings by secondary injection Measure the time between the change in current and the SCC1_START (SCC1_TRIP) signal. Compare the measured time with the set values tHStart and tHTrip. Repeat item 11-16 for the other two phases. 28.1.4 Completing the test Continue to test another function or complete the test by setting the test mode off.
Sudden change in residual current Chapter 13 protection (SCRC) Verifying settings by secondary injection Sudden change in residual current protection (SCRC) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. 29.1 Measuring the operate limit of set values 29.1.1 Sudden change in residual current The sudden change in residual current protection algorithm measures the difference in amplitude...
Sudden change in residual current Chapter 13 protection (SCRC) Verifying settings by secondary injection Measure the time between the change in residual current and the SCRC_START (SCRC_TRIP) signal. Compare the measured time with the set values tHStart and tHTrip. 29.1.4 Completing the test Continue to test another function or complete the test by setting the test mode off.
Undercurrent protection (UCP) Chapter 13 Verifying settings by secondary injection Undercurrent protection (UCP) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. 30.1 Measuring the operate limit of set values 30.1.1 Undercurrent in any phase 30.1.2 Dependbility test Procedure...
Phase overcurrent protection (OCP) Chapter 13 Verifying settings by secondary injection Phase overcurrent protection (OCP) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. 31.1 Measuring the operate limit of set values 31.1.1 Overcurrent in any phase 31.1.2...
Residual overcurrent protection (ROCP) Chapter 13 Verifying settings by secondary injection Residual overcurrent protection (ROCP) Prepare the terminal for verification of settings as outlined in section 2 "Preparing for test" this chapter. 32.1 Measuring the operate limit of set values 32.1.1 Residual overcurrent The residual overcurrent protection algorithm measures the amplitude of the residual current and...
Residual overcurrent protection (ROCP) Chapter 13 Verifying settings by secondary injection Change the level of the injected current and measure the operating time of the ROCP function. Use the ROCP_TRHIGH signal. Compare this operating time with the set value tHigh 32.1.4 Completing the test Continue to test another function or complete the test by setting the test mode off.
About this chapter Chapter 14 Verifying the internal configuration Chapter 14 Verifying the internal configuration About this chapter The aim of this chapter is to verify that the internal communications and output signals are ac- cording to the specification and normal protection praxis. This means that all included protection functions must be in operation.
Overview Chapter 14 Verifying the internal configuration Overview Before start of this process, all individual devices that are involved in the fault clearance process must have been tested as individuals and set in operation. The breaker must be ready for an open-close-open cycle.
Testing the interaction of the distance Chapter 14 protection Verifying the internal configuration Testing the interaction of the distance protection This procedure describes how to test the interaction of the distance protection zone 1 at phase L1-earth fault in forward direction. It is recommended that all other distance protection zones and other protection functions are tested in a similar way.
Page 171
Testing the interaction of the distance Chapter 14 protection Verifying the internal configuration...
About this chapter Chapter 15 Testing the protection system Chapter 15 Testing the protection system About this chapter This chapter describes how to verify the conformity of the protection system without the pro- tected object energised.
Overview Chapter 15 Testing the protection system Overview Before start of this process, all individual devices that are involved in the fault clearance process of the protected object must have been tested as individuals and set in operation. The breaker must be ready for an open-close-open cycle.
Testing the interaction of the distance Chapter 15 protection Testing the protection system Testing the interaction of the distance protection This procedure describes how to test the interaction of distance protection zone 1 at a transient phase L1-L2 fault in forward direction. The test must be done without the test switch in order to verify the interaction between the terminal and surrounding equipment.
Page 175
Testing the interaction of the distance Chapter 15 protection Testing the protection system...
About this chapter Chapter 16 Fault tracing and repair Chapter 16 Fault tracing and repair About this chapter This chapter describes how to carry out fault tracing and eventually, a change of circuit board.
Fault tracing Chapter 16 Fault tracing and repair Fault tracing Using information on the local HMI If an internal fault has occurred, the local HMI displays information under: TerminalReport SelfSuperv Under these menus the indications of eventual internal failure (serious fault) or internal warning (minor problem) are listed.
Fault tracing Chapter 16 Fault tracing and repair Using front-connected PC or SMS • Self-supervision summary = INT--FAIL and INT--WARNING • CPU-module status summary = INT--CPUFAIL and INT--CPUWARN When an internal fault has occurred, extensive information can be retrieved about the fault from the list of internal events.
Page 179
Fault tracing Chapter 16 Fault tracing and repair • Module that should be changed. • Sequence of faults, if more than one unit is faulty. • Exact time when the fault occurred.
An alternative is to open the terminal and send only the faulty circuit board to ABB for repair. When a printed circuit board is sent to ABB, it must always be placed in a metallic, ESD-proof, protection bag.
Page 181
Repair instruction Chapter 16 Fault tracing and repair 9. Check that the springs on the card rail have connection to the corresponding me- tallic area on the circuit board when the new module is inserted. 10. Reassemble the terminal. If the REx 5xx terminal has the optional increased measuring accuracy, a file with unique cali- bration data for the transformer module is stored in the Main processing module.
Fault tracing and repair Repair support If a REx 5xx terminal needs to be repaired, the whole terminal must be removed and sent to ABB Logistic Center. Before returning the material, an inquiry must be sent to ABB Logistic Center.
Page 183
Repair support Chapter 16 Fault tracing and repair...
Page 184
ABB Power Technologies AB Substation Automation Products SE-721 59 Västerås Sweden Telephone: +46 (0) 21 34 20 00 Facsimile: +46 (0) 21 14 69 18 Internet: www.abb.com/substationautomation Printed on recycled and ecolabelled paper at Elanders Novum...