Doc. N.° 2TSA451037P0000 REV A
KP-800, KP-1600, or KP-2000 TO EMAX 2
2TSA451021P0000
Retrofitting between KP-800 800A, KP-1600 1600A, or KP-2000 2000A, and an Emax
n
circuit breaker with a cradle-in-cradle (CiC) adapter.
This retrofitting kit is designed for replacing the KP-800 800A, KP-1600 1600A, or KP-2000 2000A air circuit breaker
in the KP-line switchgear. It allows an Emax 2 withdrawable air circuit breaker of the same size as indicated in Table
A to be attached to the original switchgear cradle assembly and racked into the switchgear enclosure.
Full correspondence of the electrical characteristics is guaranteed (rated current excluding derating if indicated in the
table, and breaking capacity) so long as the kit is chosen in accordance with the indications in the ABB technical
catalogues dedicated to retrofitting products. The kit has been designed also to preserve the insertion/extraction
operations functionality and the optional auxiliary (secondary) circuits of the obsolete circuit breaker. The CiC is
installed and then locked on the switchgear cradle, thus making use of the of its plug-in features as established in the
operation and maintenance manual of the new Emax 2 circuit breaker without having to modify any of the live parts
of the switchgear.
ATTENTION !
The instructions concern the sole assembly of the retrofitting kit. They do not substitute for the instruction in the
installation, operation, and maintenance manual of the Emax 2 circuit breaker installation instructions document
number, 1SDH001000R0002.
If optional auxiliary (secondary) circuits are required, refer to section 12.
IMPORTANT !
Retrofitting allows an obsolete control and protection device to be replaced, but does not allow the ratings of the
original switchboard to be altered in any way.
The retrofitting kits are dimensioned and validated for the obsolete device performances which may be lower than the
new Emax 2 ratings.
Consult ABB for further details.
Structure Details
The fixed part of the new Emax 2 is mounted to a steel sheet structure (CiC) that is then mounted into the KP-line
switchgear cell. The Emax 2 cradle is fitted with custom silver flashed copper run backs and finger clusters that align
to and mate with the existing KP-line switchgear power circuit stabs. The entire assembly mounts on the original K-
line cell rails. No additional phase barriers were required for this CiC. The weight of the low voltage cradle-in-cradle
assembly is listed in table B.
Table A
RATING
KP-800
800A
KP-1600
1600A
KP-2000
2000A
Table B
CiC Model
KP-800
KP-1600
KP-2000
EMAX 2
RATING
E-2.2 (S)
800A
E-2.2 (S)
1600A
E-4.2 (V)
2000A
Weight (lbs./kg)
160/73
200/91
235/107

Advertisement

loading

Summary of Contents for ABB KP-800

  • Page 1 Full correspondence of the electrical characteristics is guaranteed (rated current excluding derating if indicated in the table, and breaking capacity) so long as the kit is chosen in accordance with the indications in the ABB technical catalogues dedicated to retrofitting products. The kit has been designed also to preserve the insertion/extraction operations functionality and the optional auxiliary (secondary) circuits of the obsolete circuit breaker.
  • Page 2 Ÿ Set the obsolete circuit breaker to the open position with the springs unloaded. Ÿ Double-check to ensure that the line has been placed out of service. NOTE: The trained personnel in charge of handling and lifting must use appropriate safety equipment. KP-800 KP-1600 KP-2000...
  • Page 3 WARNING: THE CiC COULD DROP DURING THIS OPERATION. BEFORE PROCEEDING ATTACH APPROPRIATELY SIZED AND RATED LIFTING DEVICE. KP-800 (fig. 4), KP-1600 (fig. 5), and KP-2000 Lifting Points • Lower the CiC on to the rails. The studs (e) on both sides Fig.
  • Page 4 Slide the CiC to the back of the cutouts (f)(fig. 5) so that the locking lever (h)(fig. 6) drops down. Fig. 6 • Press down on the rail levers on the KP-800, KP- 1600, and KP-2000 (b)(fig. 7) on both sides to release the rails. •...
  • Page 5 KP-800, KP-1600, and KP-2000 • Rack in the CiC into the gear cradle by placing both 1-1/4 inch wrenches (l)(fig. 8) on to the cam lever protrusions (m)(fig. 9). Simultaneously pull them down to and use the extra cam lever protrusions to continue rotating them until the cam levers reach their stop position (n)(fig 9).
  • Page 6 • Lock out pins should protrude into the path of the cam levers and prevent them from being rotated when the breaker is installed in its cradle. KP-800, KP-1600, and KP-2000 (fig. 11) Fig. 15 • Fig. 12 If a flange for the old circuit breaker exists on the...
  • Page 7 KP-800, KP-1600, and KP-2000 • To make it easier to make the hole in the existing switchgear door, the kit comes complete with an adhesive template for attaching as shown (fig. 13). • See 2TSE431186P1000. • Position the template by aligning the dotted lines with the existing cut out.
  • Page 8 • Install Emax 2 Breaker • Install the moving part of the circuit breaker into the fixed part per instructions in the Emax 2 installation, operation and maintenance manual 1SDH001000R0002. • Comply with the instructions in that manual for commissioning the new circuit breaker . •...
  • Page 9 For more information please contact your local ABB Field Representative or Service Center listed below: ABB Inc. 1555 Scott Street Senatobia, MS 38668 Phone: 1-662-562-0700 Copyright 2020 ABB. All rights reserved www.abb.com...

This manual is also suitable for:

Kp-1600Kp-2000Emax 2