Dimension drawings and mounting................26 In addition to this general part the following descriptions of the individual modules are included in the complete manual of the feeder terminal relay SPAS 348 C: Directional overcurrent relay modules SPCS 4D11 and SPCS 4D12 1MRS 750115-MUM EN...
Eight freely configurable output relays and out- put relay for internal relay fault The feeder protection relay SPAS 348 C is The relays are also applied for the selective short- Application designed to be used in applications requiring...
Description of opera- The feeder protection relay SPAS 348 C is a The feeder protection relay includes three pro- tion secondary relay system to be connected to the tection relay modules: current and voltage transformers of the network two directional overcurrent relay modules SPCS section to be protected.
D connector on the rear panel ule. The selector switches of the bus connection and a bus connection module type SPA-ZC 17 module are set into the position "SPA". or SPA-ZC 21. The optical fibres are connected ABB Automation...
The I/O module of the feeder protection relay The output signals SS1...SS4, TS1...TS3 and I/O module SPAS 348 C is fitted in the rear part of the relay, TS4 control an output relay with the same in the same direction as the mother PC board.
- make and carry for 3 s 15 A Breaking capacity for dc when the control circuit time constant L/R ≤40 ms at the control voltage levels - 220 V dc - 110 V dc - 48 V dc Contact material AgCdO ABB Automation...
Page 11
10 W/15 W Combined overcurrent and earth-fault relay module SPCS 4D11, SPCS 4D12 - see "Technical data" in the manual for the module. Directional earth-fault relay module SPCS 2D26 - see "Technical data" in the manual for the module. ABB Automation...
Page 12
Degree of protection by enclosure of flush mounting relay case (IEC 529) IP 54 Weight of fully equipped relay 6 kg *) The insulation and disturbance tests do not apply to the serial port, which is used for the bus connection module only. ABB Automation...
I / O X2/3 X2/4 (SPCS 2D26) CBFP X2/1 X2/2 BS1/U3 X1/15 X1/16 RRES I / O EF trip X1/11 X1/12 X1/13 X1/14 SPAS 348 C Fig. 5. Feeder protection relay SPAS 348 C used for protecting an infeeder cubicle ABB Automation...
Page 14
SPAS SPAS Since the relay SPAS 348 C includes three 348 C 348 C overcurrent stages and a versatile earth-fault module, one relay can be used for the overcur-...
Page 15
> start signal not linked to output contacts SGR4 > trip signal linked to trip contact TS3 and SS4 SGR5 > start signal not linked to output contacts SGR6 > trip signal linked to trip contacts TS2 and SS4 ABB Automation...
Page 16
SGB2 SGR2 SGB1 SGR2 SGR1 SGF2 SGR2 SGR1 SGR2 SGR1 SGR2 SGR1 Checksum Fig. 7. Configuration of the internal signals of SPAS 348 C in application example 1 Note! The above configuration is not the factory default settings ABB Automation...
Page 17
When the switches are set as shown on page 16 the output contacts of SPAS 348 C have the following functions: Contact Relay Function X2/12-13 Earth fault detected only by the delayed alarm stage U > X2/3-4 CPFP (= Circuit-Breaker Failure Protection)
Page 18
X2/4 (SPCS 2D26) CBFP X2/1 X2/2 BS1/U3 X1/15 X1/16 RRES I / O X1/11 X1/12 X1/13 X1/14 SPAS 348 C Fig. 8. Feeder protection relay SPAS 348 C used for protecting a feeder in a resonant earthed network ABB Automation...
Page 19
The requirements regarding oper- ate times are mainly fulfilled by the operation of the high-set stage I >. ABB Automation...
Page 20
> start signal not linked to output contacts SGR4 > trip signal linked to trip contact TS2 and SS4 SGR5 > start signal not linked to output contacts SGR6 > trip signal linked to trip contacts TS2 and SS4 ABB Automation...
Page 21
SGB3 SGB2 SGR2 SGB1 SGR2 SGR1 SGF2 SGR2 SGR1 SGR2 SGR1 SGR2 SGR1 Checksum Fig. 10. Configuration of the internal signals of SPAS 348 C, application example 2 Note! The above configuration is not the factory default settings ABB Automation...
2 times the setting value. In such a case the protective algorithm adds about 20 ms to the operate times. ABB Automation...
Page 23
The resetting time is the time from closing the switch until the relay operates. from the opening of the current switch until the The operate times should be within the permit- relay resets. ted tolerances, except when the injected current ABB Automation...
SPAS 348 C2: RS 431 022-AA, CA, DA, FA SPAS 348 C3: RS 431 023-AA, CA, DA, FA Feeder protection relay SPAS 348 C with test adapter RTXP 18: SPAS 348 C: RS 431 220-AA, CA, DA, FA SPAS 348 C1:...
SPA-ZX 301 SPA-ZX 302 SPA-ZX 303 Fig. 11. Dimension and mounting drawings for feeder protection relay SPAS 348 C The relay case is made of profile aluminium and are included in the delivery. The female part can finished in beige.