Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(Low-voltage directive 2006/95/ EC). This conformity is the result of a test conducted by ABB in accordance with Article 10 of the directive in agreement with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN 60255-27 for the low voltage directive.
IED perspective. The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. 615 series Communication Protocol Manual...
The manual provides procedures for energizing and checking of external circuitry, setting and configuration as well as verifying settings and performing directional tests. The chapters are organized in chronological order in which the IED should be commissioned. 615 series Communication Protocol Manual...
Document revision/date Product series version History A/04.03.2009 First release Download the latest revision of the document from the ABB web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Product-specific point list manuals and other product series- and product-specific manuals can be downloaded from the ABB web site http://www.abb.com/...
To navigate between the options, use • HMI menu paths are presented in bold, for example: Select Main menu/Configuration/HMI. • Menu names are shown in bold in WHMI, for example: Click Information in the WHMI menu structure. 615 series Communication Protocol Manual...
Page 13
Parameter values are indicated with quotation marks, for example: The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font, for example: When the function starts, the START output is set to TRUE. 615 series Communication Protocol Manual...
Unpacking the data link frame received from the physical layer into user data, check and remove CRC checksums. • Controlling all aspects of the physical layer. • Responding to all valid frames received from the physical layer. Data link responsibilities: 615 series Communication Protocol Manual...
Page 16
1, 2 or 3. Instead, the outputs are available as binary inputs, which may then be assigned to generate events. The actual status of the binary outputs can be read from the binary inputs. A read of the binary outputs returns the last value 615 series Communication Protocol Manual...
1,2,3) and occasionally makes integrity polls (class 1, 2, 3, 0) Documentation This implementation of DNP 3.0 is fully compliant with DNP 3.0 Subset Definition Level 2, and contains significant functionality beyond Subset Level 2. 615 series Communication Protocol Manual...
DNP 3.0 serial can be assigned to a serial communication port in the IED. Serial communication ports are named COM1...COMn, depending on how many serial ports the 615 series IED hosts.. DNP 3.0 protocol ignores any parity setting in the COM settings group;...
From the IED's perspective, there are two types of CROB points. Most are internally mapped to IEC 61850 SPC, while the breaker control is mapped to 61850 DPC. SPC based CROB, for example, physical outputs and LEDs: 615 series Communication Protocol Manual...
Page 21
CROB command is ignored, but the command is accepted. It should be noticed that control pulse lengths for CB controls in this IED are configurable via PCM600. Pulse lengths for other types of outputs are in internally fixed. 615 series Communication Protocol Manual...
Change event object number Static variation reported when variation 0 3 (32 bit analog input w/o flag) requested (default setting) Change event variation reported when variation 0 1 (32 bit analog change event w/o time) requested (default setting) 615 series Communication Protocol Manual...
destMaxVal (Equation 3) GUID-01F26415-274B-4844-B861-DB7D6E56D91B V1 EN 3.2.3.2 Fault record timestamp When a new fault occurs, the fault number (LD0.FLTMSTA1.OpCnt.stVal) increments, and it is stored in the DNP AI event buffer. Other points associated with 615 series Communication Protocol Manual...
Class assignment cannot be performed on CROBs. They can only be performed on the corresponding BOS points in a limited fashion; they may only be assigned Class 0 or None and only affect the class 0 scan. This means they cannot be configured to 615 series Communication Protocol Manual...
Page 25
Section 3 1MRS756709 A Vendor-specific implementation generate events. The BOS points, however, have been made available as BI points, which can be configured to generate events. 615 series Communication Protocol Manual...
App confirm TO is the application layer confirmation timeout in milliseconds. Application layer confirmations received from the master after App confirm TO has expired are not acknowledged by the IED. 615 series Communication Protocol Manual...
Page 28
Power must be cycled to the unit after making changes to the DNP 3.0 parameters. The LHMI or WHMI will not notify the user that this action must be taken. Only one session is allowed to place the unit in write (edit) mode. 615 series Communication Protocol Manual...
1=32 bit AI; 2=16 bit AI; 3=32 bit AI without flag; 4=16 bit AI without flag. Default Var Obj 32 1...4 1=32 bit AI event; 2=16 bit AI event; 3=32 bit AI event with time; 4=16 bit AI event with time. 615 series Communication Protocol Manual...
DNP 3.0 protocol ignores any parity setting in the COM settings group; DNP 3.0 is defined as an 8 bit/no parity protocol with a 16-bit CRC every 16 bytes. This provides better error detection than parity. 615 series Communication Protocol Manual...
DNP 3.0. The internal latency between the protection logic and the communication processor is 4 ms for BI, and 500 ms for AI. Data link layer filtering is not performed based on the source address. 615 series Communication Protocol Manual...
IEC 61850-8-1 A communication protocol based on the IEC 61850 standard series and a standard for substation modelling. Intelligent Electronic Device Internet Protocol International Standard Organization Local/Remote Light-emitting diode LHMI Local Human-Machine Interface Open Systems Interconnection PCM600 Protection and Control IED Manager 615 series Communication Protocol Manual...
Page 36
Section 7 Glossary Remote Terminal Unit Service Data Unit Single Point Status of a controllable object. TCP/IP Transmission Control Protocol / Internet Protocol WHMI Web Human-Machine Interface 615 series Communication Protocol Manual...
Page 40
ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...