Installation Manual Bently Nevada™ Asset Condition Monitoring 3300 System Installation Part Number 80172-01 Rev. N (08/07)
Page 2
Bently Nevada Keyphasor, Proximitor Contact Information The following ways of contacting Bently Nevada are provided for those times when you cannot contact your local representative: Mailing Address 1631 Bently Parkway South Minden, Nevada USA 89423 Telephone 1.775.782.3611 1.800.227.5514 1.775.215.2873 Internet www.ge-energy.com/bently...
Page 3
Additional Information Notice: This manual does not contain all the information required to operate and maintain the product. Refer to the following manuals for other required information. 3300 System Overview (Part Number 80171-01) 3300 System Troubleshooting (Part Number 80173-01) The above two documents and 80172 are available as Part Number 80170-01 or -02. 3300/12 AC Power Supply (Part Number 89602-01) 3300/14 DC Power Supply (Part Number 101256-01) 3300/03 System Monitor (Part Number 89604-01)
Section 1 - RECEIVING INSPECTION 1. RECEIVING INSPECTION 1. Visually inspect the exterior of rack assembly and components for obvious shipping damage. 2. Inspect interior of monitors and power supply. Loosen screws to pull each monitor and power supply out from rack. DAMAGE CLAIMS If shipping damage is apparent, file a claim with the carrier and...
3300 System Installation Manual 2. HANDLING & STORING CONSIDERATIONS Handling and storing of printed circuit boards is extremely critical. Circuit boards contain devices that are susceptible to damage when exposed to electrostatic charges. Damage caused by obvious mishandling of the board will void the warranty. To avoid damage, observe the following precautions in the order given.
Section 8 - POWER SUPPLY INSTALLATION 8. POWER SUPPLY INSTALLATION For systems with the AC Power Supply, perform the following steps. For systems with the DC Power Supply, perform the steps on the following page. WARNING High voltage present could cause shock, burns, or death.
Page 18
3300 System Installation Manual For systems with the DC Power Supply, perform the following steps. WARNING High voltage present could cause shock, burns, or death. Do not touch exposed wires or terminals. 1. Slide Power Supply into rack and fasten two screws.
Section 9 - SYSTEM MONITOR INSTALLATION 9. SYSTEM MONITOR INSTALLATION 1. Slide System Monitor panel to the right before inserting monitor. Slide System Monitor board into rack to engage connector on backplane. 2. Slide front panel to the left and fasten two screws.
3300 System Installation Manual 10. MONITOR INSTALLATION [TYPICAL] 1. Slide monitor front panel to the right before inserting monitor. Slide monitor circuit board into rack to engage connector on backplane. If the monitor is a dual width monitor with two separate circuit boards, line the lower edges of both boards up with the slots in the rack and slide the boards in simultaneously.
3300 System Installation Manual 12. SIGNAL INPUT RELAY MODULES WARNING CAUTION High voltage present The following information is not could cause shock, applicable to the Velomitor. Refer to burns, or death. the 3300/55 Maintenance Manual for jumper configuration of the Do not touch exposed Velomitor Relay Module.
Page 23
Section 12 - SIGNAL INPUT RELAY MODULES WARNING CAUTION High voltage present The following information is not applicable to the Velomitor. could cause shock, Refer to the 3300/55 burns, or death. Maintenance Manual for jumper Do not touch exposed configuration of the Velomitor wires or terminals.
Page 24
3300 System Installation Manual SIGNAL INPUT/QUAD RELAY CARD OPTION * RELAY OPTIONS INSTALL REMOVE ALERT RELAYS W2,3C W3A,4C NORMALLY W3D,4D DE-ENERGIZED ALERT RELAYS W3A,4C W2,3C NORMALLY W3D,4D ENERGIZED DANGER RELAYS W1,3B W4B,4F NORMALLY W4A,4E DE-ENERGIZED DANGER RELAYS W4B,4F W1,3B NORMALLY W4A,4E ENERGIZED * For more information on relay configuration refer to...
Page 25
Section 12 - SIGNAL INPUT RELAY MODULES WARNING CAUTION High voltage present The following information is not applicable to the could cause shock Velomitor. Refer to the burns or death 3300/55 Maintenance Manual for jumper Do not touch exposed configuration of the wires or terminals Velomitor Relay Module.
Section 13 - ALERT RELAY ACTUATION CIRCUITS 13. ALERT RELAY ACTUATION CIRCUITS The following diagram shows the functional concept of jumper configurations for Alert relay bus actuation for the Dual Relay Module. For more detail refer to schematics in the applicable monitor manuals.
Page 28
3300 System Installation Manual FUNCTION JUMPER INSTALL REMOVE Set Alert relay for normally energized operation* W4,W11 Set Alert relay for normally de-energized operation* W4,W11 Select Alert bus 1 Select Alert bus 2 * REFER TO SECTION 12 FOR JUMPER CONFIGURATION OF RELAYS IN A SYSTEM WITH INTERNAL BARRIERS.
Page 29
Section 13 - ALERT RELAY ACTUATION CIRCUITS The following diagram shows the functional concept of jumper configurations for Alert relay actuation for the Quad Relay Module. Note: The jumper configuration shown is not applicable to the Velomitor Signal Input Relay Module. Refer to the Dual Velocity Monitor Maintenance Manual.
3300 System Installation Manual 14. DANGER RELAY ACTUATION CIRCUITS The following diagram shows the functional concept of jumper configurations for Danger relay bus actuation for the Dual Relay Module. Note: The jumper configuration shown is not applicable to the Velomitor Signal Input Relay Module.
Page 31
Section 14 - DANGER RELAY ACTUATION CIRCUITS The following diagram shows the functional concept of jumper configurations for Danger Relay actuation for the Quad Relay Module. Note: The jumper configuration shown is not applicable to the Velomitor Signal Input Relay Module. For more details refer to schematics in the applicable monitor manuals.
3300 System Installation Manual 15. FIELD GROUNDING TECHNIQUE 1. Refer to the applicable monitor manual for monitor connections. 2. For single point ground on typical system installations, install a jumper wire between the terminals labeled "Single Point Ground" on the Power Input Module. For systems with external safety barriers, refer to the field wiring diagrams in the appropriate monitor maintenance manuals for grounding requirements.