This symbol indicates that failure to follow the instructions exactly as stated poses the risk of serious injury or dam- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant.
Only use accessories (i.e., air cleaners, humidifiers, electric • Exercise special care when handling tools for use with R410A. MITSUBISHI ELECTRIC CORPORATION cannot be held heaters) recommended by Mitsubishi Electric. – Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerator oil to deteriorate.
PAC-AH001-1 3.3. Installation Detail for 2 LEV Assemblies in Parallel Ⓐ To AHU Heat exchanger (field Piping configuration with Y-Distributors supply) Ⓑ LEV Assembly Ⓒ Brazing Ⓓ LEV Ⓔ To Outdoor unit Ⓕ Refrigerant pipe size ø1/2” (field supply) Ⓖ Distributor (field supply) Ⓗ...
Page 12
PAC-AH001-1 2. City Multi Remote Controller Display * All icons are displayed for explanation. CENTRAL icon *1 CHECK icon *2 Preset temperature *3 icon appears while the unit is operated in the energy-save mode icon appears when Operation lock setting is effective.
PAC-AH001-1 5.2. Single Valve LEV Assembly PAC-LEV24AC-1 16.4 [416] PAC-LEV48AC-1, PAC-LEV60AC-1 16.5 [419] Specifications are subject to change without notice.
Page 20
PAC-AH001-1 Control Type Type 1 (For Temperature Control) Type 2 (For Capacity Control) (SWA-2) (SWA-3) Set point temperature = 5.625 X Ain Set point temperature = -5.625 X Ain + 40.775 [°F] + 100.4 [°F] [Ain = Input Temperature] [Ain = Input Temperature] Setting Temperature Setting Temperature Control...
PAC-AH001-1 VII Microprocessor Control ] 7.1.4. Float switch control In the air : Detected that the float switch is OFF for 15 seconds. Float SW 15sec. 15sec. 15sec. 1min.30sec. 1min.30sec. Drain pump In the water In the air In the water Error postponement abnormal...
PAC-AH001-1 7.3.1. How to operate 1. Press POWER ON/OFF button. 2. Press the operation MODE button to display FAN. 7.3.2. Fan (1) Set by remote controller Type Fan speed notch 3 speeds [Low], [Med], [High] • [Auto] fan speed control is not available. VII Microprocessor Control ] 7.3.3.
PAC-AH001-1 NOTE HEAT operation mode must be set using City Multi controller Heating Set-point Range with 3rd Party Controller • Discharge Air Control: 46.4~82.4 °F [8~28 °C] 7.4.2. Thermo-regulating function (1) Thermo-regulating function (Function to prevent restarting for 3 minutes) When indoor units are connected to the PUHY/PURY/PQHY/PQRY series of outdoor units.
PAC-AH001-1 VII Microprocessor Control ] 7.4.4. Float switch control In the air : Detected that the float switch is OFF for 15 seconds. Float SW 15sec. 15sec. 15sec. 1min.30sec. 1min.30sec. In the water In the air In the water Error Drain pump abnormal postponement...
PAC-AH001-1 7.6. Heater Control 7.6. Heater Control Control Mode Heater Operation (Available Control Modes) Return Air Control Discharge Air Control ● 8.5 Electric Heater Control City Multi Controller Controller Type 1 Party Type Controls Type 2 *1 Heater operation only available when operating in Return Air Control using a City Multi Controller NOTE •...
PAC-AH001-1 7.7. Humidifier Control 13.5. Humidiier max 30 ft. Sequence of operation: Humidiier Control The humidistat closes CNF The fan starts on high 1. The humidistat closes CNF CN25 provides 12VDC to turn on the Humidifier (do not exceed 1 Watt draw per relay) 3.
PAC-AH001-1 8. Troubleshooting 8.1. Check Methods 1. Component and check points (1) Thermistor • Return air thermistor (TH21) • Liquid pipe thermistor (TH22) • Gas pipe thermistor (TH23) • Discharge air thermistor (TH24) Rt: Thermistor Resistance [kΩ] t: Thermistor Measurement Temperature [°C] Disconnect the connector and measure the resistance between terminals with a tester.
Page 36
PAC-AH001-1 (A) Brown (F) White (B) Red (G) Control board (C) Black (H) Connection (CN60, CN7V) (D) Green (I) Drive circuit (E) Yellow (J) Linear expansion valve Pulse signal output and valve operation Output pulse Phase number Φ1 Φ2 Φ3 Φ4 The output pulse changes in the following order: When the valve closes 1 ->...
PAC-AH001-1 Symptom Checking Criteria Remedy Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly lower than the inlet temperature on the remote controller, valve closure failure is suspected.
PAC-AH001-1 (3) SW4 - Function Setting Switch Switch Setting Function Position Position Model Code Model Code (Not Available) (Not Available) Not Available Not Available Control Method Control Method Discharge Air Control Return Air Control Discharge Air Control Return Air Control Selection Selection Not Available...
PAC-AH001-1 8.4.3. SW2 – Capacity Code Setting Dip switch settings must be made while the unit is stopped. There is no need to power cycle the unit. Capacity Code Design Capacity Setting LEV Assembly Setting Range Cooling switches Model [Ton] [Btu/h] SW3-6 4,800-6,000...
PAC-AH001-1 8.4.7. SW11, SW12, SW14 - Address Setting (Factory Setting) SW11, SW12 (Rotary switch) Factory Setting Address switch settings must be made while the unit is stopped and the remote controller is stopped. SW14 (Rotary switch) This switch is used when the unit connected to an R2 series of outdoor unit. Factory Setting Address switch settings must be made while the unit is stopped and the remote controller is stopped.